34 Pa. Code § 50.61 - General requirements
(a)
Approval. All emergency lighting systems installed to provide
emergency illumination as required by this chapter shall be approved.
(b)
Location. The emergency
source of energy for illumination shall be a device installed within the
building. Special permission may be granted by the Department to locate the
emergency lighting system on the premises when not located within the building.
The device shall be either an approved engine generator or approved battery
system.
(c)
Automatic
control. The control of the emergency source shall be fully automatic
and not dependent upon the manual operation of any switch or device. The
emergency source shall supply power when a loss of normal source power occurs
on any phase or line to a panel serving an area requiring emergency lighting
due to breaker opening, fuse failure or removal, cable failure or similar
conditions.
(d)
Control
panel functional requirement. Each emergency lighting system shall
include an approved control panel for area protection. The control panel shall
include low voltage sensing devices (three for three phase and one for one
phase systems) capable of detecting a reduction in normal source voltage to
approximately 80% of rated source voltage, coded visual indication of the space
experiencing the power failure and isolated means for activating the emergency
source. A break in any conductor feeding the control panel shall cause a
failure indication.
(e)
Control panel location. The control panel shall be of an
approved type and shall be enclosed in a metal cabinet having a hinged door
equipped with an effective lock and catch. The visual indicators of a failure
shall be visible with or without opening the cabinet door. A nameplate affixed
to the door of the cabinet shall designate the equipment as the area protection
control panel. Suitable marking plates shall be provided at visual indicators
to enable field marking of areas protected. The control panel shall be securely
mounted in a clean dry location where it will be conspicuous and readily
accessible at all times. Nonlocking type over-current devices are acceptable in
all circuits to the control panel.
(f)
Full illumination within 15
seconds. Emergency lighting systems shall provide full illumination
within 15 seconds after normal source power failure.
(g)
Nameplate. Emergency
lighting systems shall be provided with a nameplate setting forth the name of
the manufacturer, model number, and such other details as may be specifically
mentioned in the special requirements for the different types of equipment. The
nameplate shall be securely fastened to the equipment and shall not be
removed.
(h)
Permissible
load. The total connected emergency load shall not be greater than
that which the system is designed to carry for a period of 1 hour.
(i)
Connection with normal supply.
Except unit systems, emergency systems utilizing a device which makes
the system inoperative when the building is not occupied shall be connected so
that some of the normal circuits necessary for illumination, in each location
requiring emergency illumination, cannot be used unless the emergency source is
ready for use.
(j)
Switches. No protective or disconnecting devices other than
the following shall be permitted to be installed in the emergency lighting
circuits:
(1) Panelboards for emergency
lighting distribution may contain circuit breakers, each of which shall be
equipped with a handle locking device to prevent unauthorized operation of the
breaker and disconnection of the circuit. The panelboards shall be clearly
marked with the legend "emergency lighting."
(2) Location disconnecting devices, such as
wall switches, designed to disconnect the emergency supply from rooms which are
not being used shall also disconnect the entire normal supply to the rooms, but
they may not cut off the emergency source from the hallways, stairways, ramps
and similar passageways leading to outside building exits.
(k)
Submission and approval of plans.
No device or system required by this chapter shall be installed until
floor plans or sketches have been filed with and approved by the Department.
The plans or sketches shall be in triplicate and shall show the proposed
location of the equipment, the location of all exit or other lights connected
to the emergency system and other information which the Department may request.
The Department approval denotes approval only of the location of emergency
fixtures throughout the building. The information required by this subsection
may be included on the general building plans and submitted for
approval.
(l)
Testing
required. Systems shall be proved with a test switch to simulate a
power failure to the emergency throwover switch or equipment. A complete test
of all emergency lighting systems and inspection of all circuits for
satisfactory operation shall be made at least once each week, except that when
buildings or rooms are used less than once a week, tests may be made within 1
hour prior to the opening of the room or building on each day of use. A record
of tests shall be maintained and shall be available for inspection. No building
or room within the scope of this chapter shall be used unless both regular and
emergency sources of illumination are available.
(m)
Interlocks required.
Emergency throwover switches and equipment shall be interlocked so that no line
or phase of the emergency source of supply shall be connected to a line or
phase of the normal supply. Grounded neutrals may be interconnected.
(n)
Transfer switch capability to
withstand high-fault currents. The transfer switch or switchgear shall
be capable of carrying the maximum fault current available on the load side of
the transfer switch or switchgear for the time required for circuit to be
cleared of the fault current by fuses or circuit breakers on the service sides
of the transfer switch or switchgear. The ability of the switch to carry rated
current within recognized temperature rise limits shall be unimpaired after
being subjected to one operation at the maximum fault current
available.
(o)
Minimum
intensity of illumination. Emergency lighting systems, other than unit
systems utilizing floor or spot light type of distribution, shall produce and
maintain for at least 1 hour a minimum intensity of illumination, measured on a
horizontal plane 30 inches above the floor as follows:
(1) An intensity of 5/10 of a footcandle at
exit doors, hallways, corridors, passageways, stairways, runways, ramps and the
like, leading to the outside building exits.
(2) An intensity of 25/100 of a footcandle at
other locations requiring emergency lighting.
(3) An intensity of 15/100 of a footcandle,
with special permission from the Department, in theaters and motion picture
theaters where arrangements have been made to automatically continue the
performance even though a power failure has occurred.
(p) Where unit storage battery systems
utilizing flood or spot light type of distribution are used, the distance
between adjacent units shall not exceed 50 feet. The projectors shall be
directed towards the exits and located so as to provide distribution of light
over the entire floor area. Glare and sharp shadows shall be held to a minimum.
The minimum total operating lamp load measured after 1 hour of battery
operation shall be in accordance with the following:
(1) A rating of 1/10 watt per square foot of
floor area of hallways, passageways, stairways, ramps, corridors, and the like,
leading to the outside building exits.
(2) A rating of 5/100 watt per square foot at
other locations requiring emergency lighting.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.