55 Pa. Code § 2600.130 - Smoke detectors and fire alarms
(a) There shall be an operable automatic
smoke detector located within 15 feet of each bedroom door.
(b) The smoke detectors specified in
subsection (a) shall be located in hallways.
(c) Smoke detectors and fire alarms must be
of a type approved by the Department of Labor and Industry, the appropriate
local building authority or local fire safety expert, or listed by Underwriters
Laboratories.
(d) If the home serves
nine or more residents, there shall be at least one smoke detector on each
floor interconnected and audible throughout the home or an automatic fire alarm
system that is interconnected and audible throughout the home.
(e) If one or more residents or staff persons
are not able to hear the smoke detector or fire alarm system, a signaling
device approved by a fire safety expert shall be used and tested so that each
resident and staff person with a hearing impairment will be alerted in the
event of a fire.
(f) Smoke detectors
and fire alarms shall be tested for operability at least once per month. A
written record of the monthly testing shall be kept.
(g) If a smoke detector or fire alarm becomes
inoperative, repair shall be completed within 48 hours of the time the detector
or alarm was found to be inoperative.
(h) The home's emergency procedures shall
indicate the procedures that will be immediately implemented until the smoke
detector or fire alarms are operable.
(i) In homes housing five or more residents
with mobility needs, the fire alarm system shall be directly connected to the
local fire department or 24-hour monitoring service approved by the local fire
department, if this service is available in the community.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.