Tenn. Comp. R. & Regs. 0400-45-01-.12 - SECONDARY DRINKING WATER REGULATIONS

(1) The following maximum contaminant levels are established to provide a water that is aesthetically pleasing to the consumer. These standards will apply to all community water systems and to those non-community water systems as may be deemed necessary by the Department. Monitoring for these contaminants will be set in the Monitoring Program for each system, but in no event less than once every year for a surface and surface/ground supply and once every three years for a ground water supply.

Maximum Contaminant Level

Contaminant Milligrams per Liter (unless otherwise indicated)
(a) Chloride 250
(b) Color 15 (Color Units)
(c) Copper 1
(d) MBAS (Methyl Blue Active Substance) 0.5
(e) Iron 0.3
(f) Manganese 0.05
(g) Odor 3 (Threshold Odor Number)
(h) pH 6.5-8.5
(i) Sulfate 250
(j) TDS (Total Dissolved Solids) 500
(k) Zinc 5
(l) Fluoride 2
(m) Aluminum 0.2
(n) Silver 0.1
(2) The system may apply for monitoring waivers from the monitoring frequency specified in paragraph (1) of this rule. The Department may issue monitoring waivers after considering: historical data, whether or not there have been customer complaints concerning the contaminant to be waived, any corrective action taken by the water supplier to correct the secondary contaminant problem, and whether or not the system routinely monitors for the contaminant as part of its treatment process monitoring program. The Department shall determine the frequency, if any, a system must monitor after considering the historical data available, the number and nature of customer complaints and other factors that may affect the contaminant concentration, and specify the decision in writing to the system.

Notes

Tenn. Comp. R. & Regs. 0400-45-01-.12
Original rule filed August 1, 2012; effective October 30, 2012. Rule was previously numbered 1200-05-01.

Authority: T.C.A. ยงยง 68-221-701 et seq. and 4-5-201 et seq.

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.