Tenn. Comp. R. & Regs. 1200-03-05-.06 - WOOD-FIRED FUEL BURNING EQUIPMENT

(1) Wood-fired fuel burning equipment, which commenced operation before March 1, 1978, with a heat input of 100 million Btu/hr or greater must meet an emission limit of forty (40) percent opacity except for four six (6) minute periods per day not to exceed one six (6) minute period per hour.
(2) Wood-fired fuel burning equipment, subject to Rule 1200-3-6-.05(1), (a), (c), (d), (e), or (2) must meet an emission limit of twenty (20) percent opacity except for one six (6) minute period per hour.
(3) Wood-fired fuel burning equipment subject to Rule 1200-3-6-.05(8)(d) must meet an emission limit of forty (40) percent opacity except for one six (6) minute period per hour.
(4) Opacity for purposes of this rule shall be determined by the reference method as specified in the Federal Register, Vol. 39, No. 219, November 12, 1974.
(5) Other emission sources constructed on or after June 16, 1978, that exhaust through the same stack as wood-fired fuel burning equipment subject to Rule 1200-3-5-.06 shall meet an opacity standard where V is:

Click to view Image

(6) This rule does not apply in Davidson, Hamilton, Knox, and Shelby Counties but facilities in these counties will be subject to Rule 1200-3-5-.01.

Notes

Tenn. Comp. R. & Regs. 1200-03-05-.06
Original rule filed May 17, 1978; effective June 16, 1978. Amendment filed December 20, 1984; effective January 19, 1985. Amendment filed September 21, 1988; effective November 6, 1988.

Authority: T.C.A. ยงยง 68-25-105 and 4-5-201 et. seq.

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.