Utah Admin. Code R309-545-21 - Operation and Maintenance of Storage Tanks

(1) Inspection and Cleaning.

Tanks that are entered for inspection or cleaning shall be disinfected in accordance with AWWA Standard C652-11 prior to being returned to service.

(2) Recoating or Repairing.

Any substance used to recoat or repair the interior of a drinking water storage tank shall be certified to conform to ANSI/NSF Standard 61. If the tank is not drained for recoating or repairing, any substance or material used to repair the interior coatings or cracks shall be suitable for underwater application, as indicated by the manufacturer, as well as comply with both ANSI/NSF Standards 60 and 61. Recoating of the interior of a drinking water tank shall comply with the plan review requirements of R309-500-5(1)(c)(i).

(3) Seasonal Use.

Water storage tanks which are operated seasonally shall be flushed and disinfected in accordance with AWWA Standard C652- 11 prior to each season's use. Certification of proper disinfection shall be obtained by the water system and kept on file. During the non-use period, care shall be taken to see that openings to the water storage tank (those which are normally closed and sealed during normal use) are closed and secured.