12 Va. Admin. Code § 35-105-840 - Requirements for seclusion room
A.
The room used for seclusion shall meet the design requirements for buildings
used for detention or seclusion of individuals.
B. The seclusion room shall be at least six
feet wide and six feet long with a minimum ceiling height of eight
feet.
C. The seclusion room shall
be free of all protrusions, sharp corners, hardware, fixtures or other devices
which may cause injury to the individual.
D. Windows in the seclusion room shall be so
constructed as to minimize breakage and otherwise prevent the individual from
harming himself.
E. Light fixtures
and other electrical receptacles in the seclusion room shall be recessed or so
constructed as to prevent the individual from harming himself. Light controls
shall be located outside the seclusion room.
F. Doors to the seclusion room shall be at
least 32 inches wide, shall open outward and shall contain observation view
panels of transparent wire glass or its approved equivalent, not exceeding 120
square inches but of sufficient size for someone outside the door to see into
all corners of the room.
G. The
seclusion room shall contain only a mattress with a washable mattress covering
designed to avoid damage by tearing.
H. The seclusion room shall maintain
temperatures appropriate for the season.
I. All space in the seclusion room shall be
visible through the locked door, either directly or by mirrors.
Notes
Statutory Authority
§ 37.2-203 of the Code of Virginia.