13 Va. Admin. Code § 5-52-380 - IFC Chapter 33 Fire Safety during Construction and Demolition
Make the following changes to Chapter 33:
1. Change Section 3303.3.1 to read:
3303.3.1 Violations. Failure to properly
conduct, document, and maintain documentation required by this section shall
constitute an unlawful act in accordance with Section 111, and the fire code
official may request a stop work order be issued by the building
official.
2. Change
Section 3303.5 to read:
3303.5 Fire safety for
buildings of Types IV-A, IV-B, and IV-C construction. Buildings of Types IV-A,
IV-B, and IV-C construction designed to be greater than six stories above grade
plane shall comply with the following requirements during construction unless
otherwise approved by the fire code official:
1. Standpipes shall be provided in accordance
with Section 3313.
2. A water
supply for fire department operations, as approved by the fire code official
and the fire chief.
3. Fire safety
construction features as required by the building official in accordance with
the applicable building code.
3. Change Section 3305.9 to read:
3305.9 Separations between construction
areas. Separations used in Type I and Type II construction to separate
construction areas from occupied portions of the building shall be maintained
in accordance with the applicable building code.
4. Change Exception 2 to Section 3307.2.1 to
read (Exceptions 1 and 3 remain):
2. Piping
systems regulated by the Virginia Fuel Gas Code.
5. Change Section 3311.1 to read:
3311.1 Required access. Approved vehicle
access for firefighting shall be provided to all construction or demolition
sites. Vehicle access shall be provided to within 100 feet (30 480 mm) of
buildings and temporary or permanent fire department connections. Vehicle
access shall be provided by either temporary or permanent roads capable of
supporting vehicle loading under all weather conditions. Vehicle access shall
be maintained until permanent fire apparatus access roads are
available.
6. Change
Section 3312.1 to read:
3312.1 Stairways.
Where building construction exceeds 40 feet (12,192 mm) in height above the
lowest level of fire department vehicle access, a temporary or permanent
stairway shall be maintained in accordance with the applicable building code.
As construction progresses, such stairway shall be maintained in accordance
with the applicable building code.
7. Change Section 3314.1 to read:
3314.1 Where required. Where required by the
applicable building code, a temporary or permanent standpipe shall be
maintained and remain in an operable condition so as to be available for use by
the fire department.
8.
Delete Sections 3314.2 and 3314.3.
9. Change Section 3315.1 to read:
3315.1 Completion before occupancy. In
buildings where an automatic sprinkler system is required by this code or the
applicable building code, the building or portion thereof shall not be occupied
until the automatic sprinkler system has been tested and approved, except where
approved by the building official.