Wash. Admin. Code § 296-800-31053 - Provide adequate lighting for exit routes and signs
(1) You must illuminate each exit route
adequately and reliably.
(2) You
must have at least five foot-candles illumination from a reliable light
source.
(3) You must make sure any
exit signs illuminated by artificial lights and made of translucent material
(other than internally illuminated types).
(a) Have screens, discs or lens of at least
twenty-five square inches in size; and
(b) Show red or other designated color on the
approach side of the exit.
(4) You must make sure brightly lit signs,
displays, or objects in or near the line of vision do not distract attention
from the exit sign.
(5) You must
make sure exit signs that are self-lighting have a minimum luminance surface
value of .06 footlamberts.