Wash. Admin. Code § 51-11C-403322 - Table C403.3.2(2)-Electrically operated air-cooled unitary heat pumps-Minimum efficiency requirements

Table C403.3.2(2)

Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements

Equipment Type

Size Category

Heating Section Type

Subcategory or Rating Condition

Minimum Efficiency

Test Procedurea

Air cooled (cooling mode)

< 65,000 Btu/h

All

Split System, three phase and applications outside U.S. single phaseb

14.3 SEER2

AHRI 201/240-2023

Single Package, three phase and applications outside U.S. single phaseb

13.4 SEER2

Space constrained, air cooled

[LESS THAN EQUAL TO] 30,000 Btu/h

All

Split System, three phase and applications outside U.S. single phaseb

11.7 SEER2

Single Package, three phase and applications outside U.S. single phaseb

11.7 SEER2

Single duct high velocity, air cooled (cooling mode)

[LESS THAN EQUAL TO] 65,000 Btu/h

All

Split System, three phase and applications outside U.S. single phaseb

12.0 SEER2

Air cooled (cooling mode)

[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h

Electric Resistance (or None)

Split System and Single Package

11.0 EER

14.1 IEER

AHRI 340/360

All other

Split System and Single Package

10.8 EER

13.9 IEER

[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h

Electric Resistance (or None)

Split System and Single Package

10.6 EER

13.5 IEER

All other

Split System and Single Package

10.4 EER

13.3 IEER

[GREATER THAN EQUAL TO] 240,000 Btu/h

Electric Resistance (or None)

Split System and Single Package

9.5 EER

12.5 IEER

All other

Split System and Single Package

9.3 EER

12.3 IEER

Air cooled (heating mode)

< 65,000 Btu/hb

-

Split System, three phase and applications outside U.S. single phaseb

7.5 HSPF

AHRI 201/240-2023

-

Single Package, three phase and applications outside U.S. single phaseb

6.7 HSPF

Space constrained, air cooled (heating mode)

[LESS THAN EQUAL TO] 30,000 Btu/h

-

Split System, three phase and applications outside U.S. single phaseb

6.3 HSPF

-

Single Package, three phase and applications outside U.S. single phaseb

6.3 HSPF

Small-duct high velocity air cooled (heating mode)

< 65,000 Btu/h

-

Split System, three phase and applications outside U.S. single phaseb

6.1 HSPF

Air cooled (heating mode)

[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h (cooling capacity)

-

47F db/43ºF wb

Outdoor Air

3.40 COPH

AHRI 340/360

17F db/15ºF wb

Outdoor Air

2.25 COPH

[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h (cooling capacity)

-

47F db/43ºF wb

Outdoor Air

3.30 COPH

17F db/15ºF wb

Outdoor Air

2.05 COPH

[GREATER THAN EQUAL TO] 240,000 Btu/h (cooling capacity)

47F db/43ºF wb

Outdoor Air

3.20 COPH

17F db/15ºF wb

Outdoor Air

2.05 COPH

For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.

a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.

b Single-phase, U.S. air-cooled heat pumps less than 65,000 Btu/h are regulated as consumer products by the U.S. Department of Energy Code of Federal Regulations DOE 10 C.F.R. 430 . SEER, SEER2, and HSPF values for single-phase products are set by the U.S. Department of Energy.

c DOE 10 C.F.R. 430 Subpart B Appendix MI includes the test procedure updates effective 1/1/2023 that will be incorporated into AHRI 210/240-2023.

d This table is a replica of ASHRAE 90.1 Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements.

Notes

Wash. Admin. Code § 51-11C-403322
Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023