Wash. Admin. Code § 51-11C-403322 - Table C403.3.2(2)-Electrically operated air-cooled unitary heat pumps-Minimum efficiency requirements
Table C403.3.2(2)
Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements
Equipment Type |
Size Category |
Heating Section Type |
Subcategory or Rating Condition |
Minimum Efficiency |
Test Procedurea |
Air cooled (cooling mode) |
< 65,000 Btu/h |
All |
Split System, three phase and applications outside U.S. single phaseb |
14.3 SEER2 |
AHRI 201/240-2023 |
Single Package, three phase and applications outside U.S. single phaseb |
13.4 SEER2 |
||||
Space constrained, air cooled |
[LESS THAN EQUAL TO] 30,000 Btu/h |
All |
Split System, three phase and applications outside U.S. single phaseb |
11.7 SEER2 |
|
Single Package, three phase and applications outside U.S. single phaseb |
11.7 SEER2 |
||||
Single duct high velocity, air cooled (cooling mode) |
[LESS THAN EQUAL TO] 65,000 Btu/h |
All |
Split System, three phase and applications outside U.S. single phaseb |
12.0 SEER2 |
|
Air cooled (cooling mode) |
[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h |
Electric Resistance (or None) |
Split System and Single Package |
11.0 EER 14.1 IEER |
AHRI 340/360 |
All other |
Split System and Single Package |
10.8 EER 13.9 IEER |
|||
[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h |
Electric Resistance (or None) |
Split System and Single Package |
10.6 EER 13.5 IEER |
||
All other |
Split System and Single Package |
10.4 EER 13.3 IEER |
|||
[GREATER THAN EQUAL TO] 240,000 Btu/h |
Electric Resistance (or None) |
Split System and Single Package |
9.5 EER 12.5 IEER |
||
All other |
Split System and Single Package |
9.3 EER 12.3 IEER |
|||
Air cooled (heating mode) |
< 65,000 Btu/hb |
- |
Split System, three phase and applications outside U.S. single phaseb |
7.5 HSPF |
AHRI 201/240-2023 |
- |
Single Package, three phase and applications outside U.S. single phaseb |
6.7 HSPF |
|||
Space constrained, air cooled (heating mode) |
[LESS THAN EQUAL TO] 30,000 Btu/h |
- |
Split System, three phase and applications outside U.S. single phaseb |
6.3 HSPF |
|
- |
Single Package, three phase and applications outside U.S. single phaseb |
6.3 HSPF |
|||
Small-duct high velocity air cooled (heating mode) |
< 65,000 Btu/h |
- |
Split System, three phase and applications outside U.S. single phaseb |
6.1 HSPF |
|
Air cooled (heating mode) |
[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
- |
47F db/43ºF wb Outdoor Air |
3.40 COPH |
AHRI 340/360 |
17F db/15ºF wb Outdoor Air |
2.25 COPH |
||||
[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) |
- |
47F db/43ºF wb Outdoor Air |
3.30 COPH |
||
17F db/15ºF wb Outdoor Air |
2.05 COPH |
||||
[GREATER THAN EQUAL TO] 240,000 Btu/h (cooling capacity) |
47F db/43ºF wb Outdoor Air |
3.20 COPH |
|||
17F db/15ºF wb Outdoor Air |
2.05 COPH |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.
a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
b Single-phase, U.S. air-cooled heat pumps less than 65,000 Btu/h are regulated as consumer products by the U.S. Department of Energy Code of Federal Regulations DOE 10 C.F.R. 430 . SEER, SEER2, and HSPF values for single-phase products are set by the U.S. Department of Energy.
c DOE 10 C.F.R. 430 Subpart B Appendix MI includes the test procedure updates effective 1/1/2023 that will be incorporated into AHRI 210/240-2023.
d This table is a replica of ASHRAE 90.1 Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Table C403.3.2(2)
Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements
Equipment Type | Size Category | Heating Section Type | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
Air cooled (cooling mode) | < 65,000 Btu/h | All | Split System, three phase and applications outside U.S. single phaseb | 14.3 SEER2 | AHRI 201/240-2023 |
Single Package, three phase and applications outside U.S. single phaseb | 13.4 SEER2 | ||||
Space constrained, air cooled | [LESS THAN EQUAL TO] 30,000 Btu/h | All | Split System, three phase and applications outside U.S. single phaseb | 11.7 SEER2 | |
Single Package, three phase and applications outside U.S. single phaseb | 11.7 SEER2 | ||||
Single duct high velocity, air cooled (cooling mode) | [LESS THAN EQUAL TO] 65,000 Btu/h | All | Split System, three phase and applications outside U.S. single phaseb | 12.0 SEER2 | |
Air cooled (cooling mode) | [GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 11.0 EER 14.1 IEER | AHRI 340/360 |
All other | Split System and Single Package | 10.8 EER 13.9 IEER | |||
[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 10.6 EER 13.5 IEER | ||
All other | Split System and Single Package | 10.4 EER 13.3 IEER | |||
[GREATER THAN EQUAL TO] 240,000 Btu/h | Electric Resistance (or None) | Split System and Single Package | 9.5 EER 12.5 IEER | ||
All other | Split System and Single Package | 9.3 EER 12.3 IEER | |||
Air cooled (heating mode) | < 65,000 Btu/hb | - | Split System, three phase and applications outside U.S. single phaseb | 7.5 HSPF | AHRI 201/240-2023 |
- | Single Package, three phase and applications outside U.S. single phaseb | 6.7 HSPF | |||
Space constrained, air cooled (heating mode) | [LESS THAN EQUAL TO] 30,000 Btu/h | - | Split System, three phase and applications outside U.S. single phaseb | 6.3 HSPF | |
- | Single Package, three phase and applications outside U.S. single phaseb | 6.3 HSPF | |||
Small-duct high velocity air cooled (heating mode) | < 65,000 Btu/h | - | Split System, three phase and applications outside U.S. single phaseb | 6.1 HSPF | |
Air cooled (heating mode) | [GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) | - | 47F db/43ºF wb Outdoor Air | 3.40 COPH | AHRI 340/360 |
17F db/15ºF wb Outdoor Air | 2.25 COPH | ||||
[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) | - | 47F db/43ºF wb Outdoor Air | 3.30 COPH | ||
17F db/15ºF wb Outdoor Air | 2.05 COPH | ||||
[GREATER THAN EQUAL TO] 240,000 Btu/h (cooling capacity) | 47F db/43ºF wb Outdoor Air | 3.20 COPH | |||
17F db/15ºF wb Outdoor Air | 2.05 COPH |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.
a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
b Single-phase, U.S. air-cooled heat pumps less than 65,000 Btu/h are regulated as consumer products by the U.S. Department of Energy Code of Federal Regulations DOE 10 C.F.R. 430. SEER, SEER2, and HSPF values for single-phase products are set by the U.S. Department of Energy.
c DOE 10 C.F.R. 430 Subpart B Appendix MI includes the test procedure updates effective 1/1/2023 that will be incorporated into AHRI 210/240-2023.
d This table is a replica of ASHRAE 90.1 Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps-Minimum Efficiency Requirements.