Wash. Admin. Code § 51-11C-403323 - Table C403.3. 2(3)-Water chilling packages-Minimum efficiency requirements

Table C403.3.2(3)

Water Chilling Packages-Minimum Efficiency Requirementsa,b,e,f

Equipment Type

Size Category

Units

Path A

Path B

Test Procedurec

FL

IPLV,IP

FL

IPLV,IP

Air-cooled chillers

< 150 tons

EER(Btu/Wh)

[GREATER THAN EQUAL TO] 10.100

[GREATER THAN EQUAL TO] 13.700

[GREATER THAN EQUAL TO] 9.700

[GREATER THAN EQUAL TO] 15.800

AHRI 550/590

[GREATER THAN EQUAL TO] 150 tons

EER(Btu/Wh)

[GREATER THAN EQUAL TO] 10.100

[GREATER THAN EQUAL TO] 14.000

[GREATER THAN EQUAL TO] 9.700

[GREATER THAN EQUAL TO] 16.100

Air cooled without condenser, electrically operated

All capacities

EER(Btu/Wh)

Air-cooled chillers without condensers shall be rated with matching condensers and comply with the air-cooled chiller efficiency requirements

Water cooled, electrically operated, positive displacement

< 75 tons

kW/ton

[LESS THAN EQUAL TO] 0.750

[LESS THAN EQUAL TO] 0.600

[LESS THAN EQUAL TO] 0.780

[LESS THAN EQUAL TO] 0.500

[GREATER THAN EQUAL TO] 75 tons and < 150 tons

kW/ton

[LESS THAN EQUAL TO] 0.720

[LESS THAN EQUAL TO] 0.560

[LESS THAN EQUAL TO] 0.750

[LESS THAN EQUAL TO] 0.490

[GREATER THAN EQUAL TO] 150 tons and < 300 tons

kW/ton

[LESS THAN EQUAL TO] 0.660

[LESS THAN EQUAL TO] 0.540

[LESS THAN EQUAL TO] 0.680

[LESS THAN EQUAL TO] 0.440

[GREATER THAN EQUAL TO] 300 tons and < 600 tons

kW/ton

[LESS THAN EQUAL TO] 0.610

[LESS THAN EQUAL TO] 0.520

[LESS THAN EQUAL TO] 0.625

[LESS THAN EQUAL TO] 0.410

[GREATER THAN EQUAL TO] 600 tons

kW/ton

[LESS THAN EQUAL TO] 0.560

[LESS THAN EQUAL TO] 0.500

[LESS THAN EQUAL TO] 0.585

[LESS THAN EQUAL TO] 0.380

Water cooled, electrically operated, centrifugal

< 150 tons

kW/ton

[LESS THAN EQUAL TO] 0.610

[LESS THAN EQUAL TO] 0.550

[LESS THAN EQUAL TO] 0.695

[LESS THAN EQUAL TO] 0.440

[GREATER THAN EQUAL TO] 150 tons and < 300 tons

kW/ton

[LESS THAN EQUAL TO] 0.610

[LESS THAN EQUAL TO] 0.550

[LESS THAN EQUAL TO] 0.695

[LESS THAN EQUAL TO] 0.400

[GREATER THAN EQUAL TO] 150 tons and < 300 tons

kW/ton

[LESS THAN EQUAL TO] 0.560

[LESS THAN EQUAL TO] 0.520

[LESS THAN EQUAL TO] 0.595

[LESS THAN EQUAL TO] 0.390

[GREATER THAN EQUAL TO] 150 tons and < 300 tons

kW/ton

[LESS THAN EQUAL TO] 0.560

[LESS THAN EQUAL TO] 0.500

[LESS THAN EQUAL TO] 0.585

[LESS THAN EQUAL TO] 0.380

[GREATER THAN EQUAL TO] 600 tons

kW/ton

[LESS THAN EQUAL TO] 0.560

[LESS THAN EQUAL TO] 0.500

[LESS THAN EQUAL TO] 0.585

[LESS THAN EQUAL TO] 0.380

Air cooled absorption, single effect

All capacities

COP(W/W)

[GREATER THAN EQUAL TO] 0.600

NR

NAd

NAd

AHRI 560

Water cooled absorption, single effect

All capacities

COP(W/W)

[GREATER THAN EQUAL TO] 0.700

NR

NAd

NAd

Absorption double effect, indirect fired

All capacities

COP(W/W)

[GREATER THAN EQUAL TO] 1.000

[GREATER THAN EQUAL TO] 1.050

NAd

NAd

Absorption double effect, direct fired

All capacities

COP(W/W)

[GREATER THAN EQUAL TO] 1.000

[GREATER THAN EQUAL TO] 1.000

NAd

NAd

For SI: 1 ton = 3517 W, 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.

NR = No requirement.

a Chapter 6 contains a complete specification of the referenced standards, which includes test procedures, including the referenced year version of the test procedure.

b The requirements for centrifugal chiller shall be adjusted for nonstandard rating conditions per Section C403.3.2.4 and are applicable only for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the referenced test procedure.

c Both the full load and IPLV.IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for any application.

d NA means the requirements are not applicable for Path B and only Path A can be used for compliance.

e FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.

f This table is a replica of ASHRAE 90.1 Table 6.8.1-3 Water-Chilling Packages-Minimum Efficiency Requirements.

Notes

Wash. Admin. Code § 51-11C-403323
Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023