Wash. Admin. Code § 51-11C-403323 - Table C403.3. 2(3)-Water chilling packages-Minimum efficiency requirements
Table C403.3.2(3)
Water Chilling Packages-Minimum Efficiency Requirementsa,b,e,f
Equipment Type |
Size Category |
Units |
Path A |
Path B |
Test Procedurec |
||
FL |
IPLV,IP |
FL |
IPLV,IP |
||||
Air-cooled chillers |
< 150 tons |
EER(Btu/Wh) |
[GREATER THAN EQUAL TO] 10.100 |
[GREATER THAN EQUAL TO] 13.700 |
[GREATER THAN EQUAL TO] 9.700 |
[GREATER THAN EQUAL TO] 15.800 |
AHRI 550/590 |
[GREATER THAN EQUAL TO] 150 tons |
EER(Btu/Wh) |
[GREATER THAN EQUAL TO] 10.100 |
[GREATER THAN EQUAL TO] 14.000 |
[GREATER THAN EQUAL TO] 9.700 |
[GREATER THAN EQUAL TO] 16.100 |
||
Air cooled without condenser, electrically operated |
All capacities |
EER(Btu/Wh) |
Air-cooled chillers without condensers shall be rated with matching condensers and comply with the air-cooled chiller efficiency requirements |
||||
Water cooled, electrically operated, positive displacement |
< 75 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.750 |
[LESS THAN EQUAL TO] 0.600 |
[LESS THAN EQUAL TO] 0.780 |
[LESS THAN EQUAL TO] 0.500 |
|
[GREATER THAN EQUAL TO] 75 tons and < 150 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.720 |
[LESS THAN EQUAL TO] 0.560 |
[LESS THAN EQUAL TO] 0.750 |
[LESS THAN EQUAL TO] 0.490 |
||
[GREATER THAN EQUAL TO] 150 tons and < 300 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.660 |
[LESS THAN EQUAL TO] 0.540 |
[LESS THAN EQUAL TO] 0.680 |
[LESS THAN EQUAL TO] 0.440 |
||
[GREATER THAN EQUAL TO] 300 tons and < 600 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.610 |
[LESS THAN EQUAL TO] 0.520 |
[LESS THAN EQUAL TO] 0.625 |
[LESS THAN EQUAL TO] 0.410 |
||
[GREATER THAN EQUAL TO] 600 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.560 |
[LESS THAN EQUAL TO] 0.500 |
[LESS THAN EQUAL TO] 0.585 |
[LESS THAN EQUAL TO] 0.380 |
||
Water cooled, electrically operated, centrifugal |
< 150 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.610 |
[LESS THAN EQUAL TO] 0.550 |
[LESS THAN EQUAL TO] 0.695 |
[LESS THAN EQUAL TO] 0.440 |
|
[GREATER THAN EQUAL TO] 150 tons and < 300 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.610 |
[LESS THAN EQUAL TO] 0.550 |
[LESS THAN EQUAL TO] 0.695 |
[LESS THAN EQUAL TO] 0.400 |
||
[GREATER THAN EQUAL TO] 150 tons and < 300 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.560 |
[LESS THAN EQUAL TO] 0.520 |
[LESS THAN EQUAL TO] 0.595 |
[LESS THAN EQUAL TO] 0.390 |
||
[GREATER THAN EQUAL TO] 150 tons and < 300 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.560 |
[LESS THAN EQUAL TO] 0.500 |
[LESS THAN EQUAL TO] 0.585 |
[LESS THAN EQUAL TO] 0.380 |
||
[GREATER THAN EQUAL TO] 600 tons |
kW/ton |
[LESS THAN EQUAL TO] 0.560 |
[LESS THAN EQUAL TO] 0.500 |
[LESS THAN EQUAL TO] 0.585 |
[LESS THAN EQUAL TO] 0.380 |
||
Air cooled absorption, single effect |
All capacities |
COP(W/W) |
[GREATER THAN EQUAL TO] 0.600 |
NR |
NAd |
NAd |
AHRI 560 |
Water cooled absorption, single effect |
All capacities |
COP(W/W) |
[GREATER THAN EQUAL TO] 0.700 |
NR |
NAd |
NAd |
|
Absorption double effect, indirect fired |
All capacities |
COP(W/W) |
[GREATER THAN EQUAL TO] 1.000 |
[GREATER THAN EQUAL TO] 1.050 |
NAd |
NAd |
|
Absorption double effect, direct fired |
All capacities |
COP(W/W) |
[GREATER THAN EQUAL TO] 1.000 |
[GREATER THAN EQUAL TO] 1.000 |
NAd |
NAd |
For SI: 1 ton = 3517 W, 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.
NR = No requirement.
a Chapter 6 contains a complete specification of the referenced standards, which includes test procedures, including the referenced year version of the test procedure.
b The requirements for centrifugal chiller shall be adjusted for nonstandard rating conditions per Section C403.3.2.4 and are applicable only for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the referenced test procedure.
c Both the full load and IPLV.IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for any application.
d NA means the requirements are not applicable for Path B and only Path A can be used for compliance.
e FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.
f This table is a replica of ASHRAE 90.1 Table 6.8.1-3 Water-Chilling Packages-Minimum Efficiency Requirements.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Table C403.3.2(3)
Water Chilling Packages-Minimum Efficiency Requirementsa,b,e,f
Equipment Type | Size Category | Units | Path A | Path B | Test Procedurec | ||
FL | IPLV,IP | FL | IPLV,IP | ||||
Air-cooled chillers | < 150 tons | EER(Btu/Wh) | [GREATER THAN EQUAL TO] 10.100 | [GREATER THAN EQUAL TO] 13.700 | [GREATER THAN EQUAL TO] 9.700 | [GREATER THAN EQUAL TO] 15.800 | AHRI 550/590 |
[GREATER THAN EQUAL TO] 150 tons | EER(Btu/Wh) | [GREATER THAN EQUAL TO] 10.100 | [GREATER THAN EQUAL TO] 14.000 | [GREATER THAN EQUAL TO] 9.700 | [GREATER THAN EQUAL TO] 16.100 | ||
Air cooled without condenser, electrically operated | All capacities | EER(Btu/Wh) | Air-cooled chillers without condensers shall be rated with matching condensers and comply with the air-cooled chiller efficiency requirements | ||||
Water cooled, electrically operated, positive displacement | < 75 tons | kW/ton | [LESS THAN EQUAL TO] 0.750 | [LESS THAN EQUAL TO] 0.600 | [LESS THAN EQUAL TO] 0.780 | [LESS THAN EQUAL TO] 0.500 | |
[GREATER THAN EQUAL TO] 75 tons and < 150 tons | kW/ton | [LESS THAN EQUAL TO] 0.720 | [LESS THAN EQUAL TO] 0.560 | [LESS THAN EQUAL TO] 0.750 | [LESS THAN EQUAL TO] 0.490 | ||
[GREATER THAN EQUAL TO] 150 tons and < 300 tons | kW/ton | [LESS THAN EQUAL TO] 0.660 | [LESS THAN EQUAL TO] 0.540 | [LESS THAN EQUAL TO] 0.680 | [LESS THAN EQUAL TO] 0.440 | ||
[GREATER THAN EQUAL TO] 300 tons and < 600 tons | kW/ton | [LESS THAN EQUAL TO] 0.610 | [LESS THAN EQUAL TO] 0.520 | [LESS THAN EQUAL TO] 0.625 | [LESS THAN EQUAL TO] 0.410 | ||
[GREATER THAN EQUAL TO] 600 tons | kW/ton | [LESS THAN EQUAL TO] 0.560 | [LESS THAN EQUAL TO] 0.500 | [LESS THAN EQUAL TO] 0.585 | [LESS THAN EQUAL TO] 0.380 | ||
Water cooled, electrically operated, centrifugal | < 150 tons | kW/ton | [LESS THAN EQUAL TO] 0.610 | [LESS THAN EQUAL TO] 0.550 | [LESS THAN EQUAL TO] 0.695 | [LESS THAN EQUAL TO] 0.440 | |
[GREATER THAN EQUAL TO] 150 tons and < 300 tons | kW/ton | [LESS THAN EQUAL TO] 0.610 | [LESS THAN EQUAL TO] 0.550 | [LESS THAN EQUAL TO] 0.695 | [LESS THAN EQUAL TO] 0.400 | ||
[GREATER THAN EQUAL TO] 150 tons and < 300 tons | kW/ton | [LESS THAN EQUAL TO] 0.560 | [LESS THAN EQUAL TO] 0.520 | [LESS THAN EQUAL TO] 0.595 | [LESS THAN EQUAL TO] 0.390 | ||
[GREATER THAN EQUAL TO] 150 tons and < 300 tons | kW/ton | [LESS THAN EQUAL TO] 0.560 | [LESS THAN EQUAL TO] 0.500 | [LESS THAN EQUAL TO] 0.585 | [LESS THAN EQUAL TO] 0.380 | ||
[GREATER THAN EQUAL TO] 600 tons | kW/ton | [LESS THAN EQUAL TO] 0.560 | [LESS THAN EQUAL TO] 0.500 | [LESS THAN EQUAL TO] 0.585 | [LESS THAN EQUAL TO] 0.380 | ||
Air cooled absorption, single effect | All capacities | COP(W/W) | [GREATER THAN EQUAL TO] 0.600 | NR | NAd | NAd | AHRI 560 |
Water cooled absorption, single effect | All capacities | COP(W/W) | [GREATER THAN EQUAL TO] 0.700 | NR | NAd | NAd | |
Absorption double effect, indirect fired | All capacities | COP(W/W) | [GREATER THAN EQUAL TO] 1.000 | [GREATER THAN EQUAL TO] 1.050 | NAd | NAd | |
Absorption double effect, direct fired | All capacities | COP(W/W) | [GREATER THAN EQUAL TO] 1.000 | [GREATER THAN EQUAL TO] 1.000 | NAd | NAd |
For SI: 1 ton = 3517 W, 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.
NR = No requirement.
a Chapter 6 contains a complete specification of the referenced standards, which includes test procedures, including the referenced year version of the test procedure.
b The requirements for centrifugal chiller shall be adjusted for nonstandard rating conditions per Section C403.3.2.4 and are applicable only for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the referenced test procedure.
c Both the full load and IPLV.IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for any application.
d NA means the requirements are not applicable for Path B and only Path A can be used for compliance.
e FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.
f This table is a replica of ASHRAE 90.1 Table 6.8.1-3 Water-Chilling Packages-Minimum Efficiency Requirements.