Wash. Admin. Code § 51-11C-403324 - Table C403.3.2(4)-Minimum efficiency requirements-Electrically operated PTAC, PTHP, SPVAC, SPVHP, room air conditioners

Table C403.3.2(4)

Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners and Room Air-Conditioner Heat Pumps-Minimum Efficiency Requirementse

Equipment Type

Size Category (Input)

Subcategory or Rating Condition

Minimum Efficiency

Test Procedurea

PTAC (cooling mode) Standard size

< 7,000 Btu/h

95°F db/75°F wb outdoor airc

11.9 EER

AHRI 310/380

[GREATER THAN EQUAL TO] 7,000 Btu/h and [LESS THAN EQUAL TO] 15,000 Btu/h

14.0 - (0.300 × Cap/1000) EERd

> 15,000 Btu/h

9.5 EER

PTAC (cooling mode) Nonstandard sizea

< 7,000 Btu/h

95°F db/75°F wb outdoor airc

9.4 EER

AHRI 310/380

[GREATER THAN EQUAL TO] 7,000 Btu/h and LESS THAN EQUAL TO] 15,000 Btu/h

10.9 - (0.213 × Cap/1000) EERd

15,000 Btu/h

7.7 EER

PTHP (cooling mode) Standard size

< 7,000 Btu/h

95°F db/75°F wb outdoor airc

11.9 EER

AHRI 310/380

[GREATER THAN EQUAL TO] 7,000 Btu/h and LESS THAN EQUAL TO] 15,000 Btu/h

14.0 - (0.300 × Cap/1000) EERd

15,000 Btu/h

9.5 EER

PTHP (cooling mode) Nonstandard sizeb

< 7,000 Btu/h

95°F db/75°F wb outdoor airc

9.3 EER

AHRI 310/380

[GREATER THAN EQUAL TO] 7,000 Btu/h and LESS THAN EQUAL TO] 15,000 Btu/h

10.8 - (0.213 × Cap/1000) EERd

15,000 Btu/h

7.6 EER

PTHP (heating mode) Standard size

< 7,000 Btu/h

47°F db/43°F wb outdoor air

3.3 COPH

AHRI 310/380

[GREATER THAN EQUAL TO] 7,000 Btu/h and LESS THAN EQUAL TO] 15,000 Btu/h

3.7 - (0.052 × Cap/1000) COPHd

15,000 Btu/h

2.90 COPH

PTHP (heating mode) Nonstandard sizeb

< 7,000 Btu/h

47°F db/43°F wb outdoor air

2.7 COPH

AHRI 310/380

[GREATER THAN EQUAL TO] 7,000 Btu/h and LESS THAN EQUAL TO] 15,000 Btu/h

2.9 - (0.026 × Cap/1000) COPHd

15,000 Btu/h

2.5 COPH

SPVAC (cooling mode)

< 65,000 Btu/h

95°F db/75°F wb outdoor airc

11.0 EER

AHRI 390

[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h

10.0 EER

[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h

10.0 EER

SPVHP (cooling mode)

< 65,000 Btu/h

95°F db/75°F wb outdoor airc

11.0 EER

AHRI 390

[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h

10.0 EER

[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h

10.0 EER

SPVHP (heating mode)

<65,000 Btu/h

47°F db/43°F wb outdoor air

3.3 COP

AHRI 390

[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h

3.0 COP

[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h

3.0 COP

Room air conditioners without reverse cycle with louvered sides for applications outside U.S.

< 6,000 Btu/h

-

11.0 CEER

ANSI/ AHAMRAC-1

[GREATER THAN EQUAL TO] 6,000 Btu/h and < 8,000 Btu/h

-

11.0 CEER

[GREATER THAN EQUAL TO] 8,000 Btu/h and < 14,000 Btu/h

-

10.9 CEER

[GREATER THAN EQUAL TO] 14,000 Btu/h and < 20,000 Btu/h

-

10.7 CEER

[GREATER THAN EQUAL TO] 20,000 Btu/h and < 28,000 Btu/h

-

9.4 CEER

[GREATER THAN EQUAL TO] 28,000 Btu/h

-

9.0 CEER

Room air conditioners without louvered sides

< 6,000 Btu/h

-

10.0 CEER

ANSI/ AHAMRAC-1

[GREATER THAN EQUAL TO] 6,000 Btu/h and < 8,000 Btu/h

-

10.0 CEER

[GREATER THAN EQUAL TO] 8,000 Btu/h and < 11,000 Btu/h

-

9.6 CEER

[GREATER THAN EQUAL TO] 11,000 Btu/h and < 14,000 Btu/h

-

9.5 CEER

[GREATER THAN EQUAL TO] 14,000 Btu/h and < 20,000 Btu/h

-

9.3 CEER

[GREATER THAN EQUAL TO] 20,000 Btu/h

-

9.4 CEER

Room air conditioners with reverse cycle, with louvered sides for applications outside U.S.

< 20,000 Btu/h

-

9.8 CEER

ANSI/ AHAMRAC-1

[GREATER THAN EQUAL TO] 20,000 Btu/h

-

9.3 CEER

Room air conditioners with reverse cycle without louvered sides for applications outside U.S.

< 14,000 Btu/h

-

9.3 CEER

ANSI/ AHAMRAC-1

[GREATER THAN EQUAL TO] 14,000 Btu/h

-

8.7 CEER

Room air conditioners, casement only for applications outside U.S.

All capacities

-

9.5 CEER

ANSI/ AHAMRAC-1

Room air conditioners, casement-slider for application outside U.S.

All capacities

-

10.4 CEER

ANSI/ AHAMRAC-1

For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) - 32]/1.8.

"Cap" = The rated cooling capacity of the product in Btu/h. If the unit's capacity is less than 7,000 Btu/h, use 7,000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculations.

a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the referenced year version of the test procedure.

b Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY: NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 inches (406 mm) high or less than 42 inches (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.43 m2).

c The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil.

d "Cap" in EER and COPH equations for PTACs and PTHPs means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.

e This table is a replica of ASHRAE 90.1 Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat Pumps-Minimum Efficiency Requirements.

Notes

Wash. Admin. Code § 51-11C-403324
Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023