Wash. Admin. Code § 51-11C-403325 - Table C403.3.2(5)-Minimum efficiency requirements-Warm air furnaces and unit heaters

Table C403.3.2(5)

Warm Air Furnaces and Combination Warm Air Furnaces/Air-Conditioning Units, Warm Air Duct Furnaces and Unit Heaters-Minimum Efficiency Requirements

Equipment Type

Size Category (Input)

Subcategory or Rating Condition

Minimum Efficiencyd,c

Test Procedurea

Warm-air furnace, gas fired for application outside the U.S.

< 225,000 Btu/h

Maximum capacityc

80% AFUE (nonweatherized)

or

1% AFUE (weatherized) or

80% Etb,d

DOE 10 C.F.R. 430 Appendix N or Section 2.39, Thermal Efficiency, ANSI Z21.47

Warm-air furnace, gas fired

< 225,000 Btu/h

Maximum capacityc

80% Etb,d before 1/1/2023 81% Etd after 1/1/2023

Section 2.39, Thermal Efficiency, ANSI Z21.47

Warm-air furnace, oil fired

< 225,000 Btu/h

Maximum capacityc

83% AFUE (nonweatherized)

or

78% AFUE (weatherized) or

80% Etb,d

DOE 10 C.F.R. 430 Appendix N or Section 42, Combustion UL 727

Warm-air furnace, oil fired

< 225,000 Btu/h

Maximum capacityc

80% Et before 1/1/2023 82% Etd after 1/1/2023

Section 42, Combustion UL 727

Electric furnaces for applications outside the U.S.

< 225,000 Btu/h

All

96% AFUE

DOE 10 C.F.R. 430 Appendix N

Warm air duct furnaces, gas fired

All capacities

Maximum capacityc

80% Ece

Section 2.10, Efficiency, ANSI Z83.8

Warm air unit heaters, gas fired

All capacities

Maximum capacityc

80% Ece,f

Section 2.10, Efficiency, ANSI Z83.8

Warm air unit heaters, oil fired

All capacities

Maximum capacityc

80% Ece,f

Section 40, Combustion, UL 731

For SI: 1 British thermal unit per hour = 0.2931 W.

a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the referenced year version of the test procedure.

b Combination units (i.e., furnaces contained within the same cabinet as an air conditioner) not covered by DOE 10 C.F.R. 430 (i.e., 3-phase power or with cooling capacity greater than or equal to 65,000 Btu/h) may comply with either rating. All other units greater than 225,000 Btu/h sold in the U.S. must meet the AFUE standards for consumer products and testing using U.S. DOE's AFUE test procedure at DOE 10 C.F.R. 430 Subpart B, Appendix N.

c Compliance of multiple firing rate units shall be at the maximum firing rate.

d Et = Thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75 percent of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.

e Ec = Combustion efficiency (100% less flue losses). See test procedure for detailed discussion.

f Units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.

g This table is a replica of ASHRAE 90.1 Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters-Minimum Efficiency Requirements.

Notes

Wash. Admin. Code § 51-11C-403325
Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.