Wash. Admin. Code § 51-11C-403326 - Table C403.3.2(6)-Minimum efficiency requirements-Gas-fired and oil-fired boilers
Table C403.3.2(6)
Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements
Equipment Typea |
Subcategory or Rating Condition |
Size Category (Input) |
Minimum Efficiency |
Test Procedurea |
Boilers, hot water |
Gas-fired |
< 300,000 Btu/hg,h for applications outside the U.S. |
82% AFUE |
DOE 10 C.F.R. 430 Appendix N |
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/he |
84% Etd |
DOE 10 C.F.R. 431.86 |
||
< 2,500,000 Btu/h and [LESS THAN EQUAL TO] 10,000,000 Btu/hb |
85% Etd |
|||
10,000,000 Btu/hb |
82% Ecc |
|||
Oil-firedf |
< 300,000 Btu/hg,h |
84% AFUE |
DOE 10 C.F.R. 430 Appendix N |
|
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/he |
87% Etd |
DOE 10 C.F.R. 431.86 |
||
2,500,000 Btu/hb |
88% Ecc |
|||
10,000,000 Btu/hb |
84% Ecd |
|||
Boilers, steam |
Gas-fired |
< 300,000 Btu/hg |
81% AFUE |
DOE 10 C.F.R. 430 Appendix N |
Gas-fired - all, except natural draft |
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb |
82% Etd |
DOE 10 C.F.R. 431.86 |
|
2,500,000 Btu/ha |
79% Etd |
|||
10,000,000 Btu/hb |
79% Etd |
|||
Gas-fired - natural draft |
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb |
81% Etd |
||
2,500,000 Btu/hb |
82% Etd |
|||
10,000,000 Btu/hb |
79% Etd |
|||
Oil-firedf |
< 300,000 Btu/h |
82% AFUE |
DOE 10 C.F.R. 430 Appendix N |
|
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb |
84% Etd |
DOE 10 C.F.R. 431.86 |
||
2,500,000 Btu/hb |
85% Etd |
|||
10,000,000 Btu/hb |
81% Etd |
For SI: 1 British thermal unit per hour = 0.2931 W.
a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
b These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.
c Ec = Combustion efficiency (100 percent less flue losses).
d Et = Thermal efficiency.
e Maximum capacity - Minimum and maximum ratings as provided for and allowed by the unit's controls.
f Includes oil-fired (residual).
g Boilers shall not be equipped with a constant burning pilot light.
h A boiler not equipped with a tankless domestic water heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.
i This table is a replica of ASHRAE 90.1 Table 6.8.1-6 Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Table C403.3.2(6)
Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements
Equipment Typea | Subcategory or Rating Condition | Size Category (Input) | Minimum Efficiency | Test Procedurea |
Boilers, hot water | Gas-fired | < 300,000 Btu/hg,h for applications outside the U.S. | 82% AFUE | DOE 10 C.F.R. 430 Appendix N |
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/he | 84% Etd | DOE 10 C.F.R. 431.86 | ||
< 2,500,000 Btu/h and [LESS THAN EQUAL TO] 10,000,000 Btu/hb | 85% Etd | |||
10,000,000 Btu/hb | 82% Ecc | |||
Oil-firedf | < 300,000 Btu/hg,h | 84% AFUE | DOE 10 C.F.R. 430 Appendix N | |
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/he | 87% Etd | DOE 10 C.F.R. 431.86 | ||
2,500,000 Btu/hb | 88% Ecc | |||
10,000,000 Btu/hb | 84% Ecd | |||
Boilers, steam | Gas-fired | < 300,000 Btu/hg | 81% AFUE | DOE 10 C.F.R. 430 Appendix N |
Gas-fired - all, except natural draft | [GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb | 82% Etd | DOE 10 C.F.R. 431.86 | |
2,500,000 Btu/ha | 79% Etd | |||
10,000,000 Btu/hb | 79% Etd | |||
Gas-fired - natural draft | [GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb | 81% Etd | ||
2,500,000 Btu/hb | 82% Etd | |||
10,000,000 Btu/hb | 79% Etd | |||
Oil-firedf | < 300,000 Btu/h | 82% AFUE | DOE 10 C.F.R. 430 Appendix N | |
[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb | 84% Etd | DOE 10 C.F.R. 431.86 | ||
2,500,000 Btu/hb | 85% Etd | |||
10,000,000 Btu/hb | 81% Etd |
For SI: 1 British thermal unit per hour = 0.2931 W.
a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
b These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.
c Ec = Combustion efficiency (100 percent less flue losses).
d Et = Thermal efficiency.
e Maximum capacity - Minimum and maximum ratings as provided for and allowed by the unit's controls.
f Includes oil-fired (residual).
g Boilers shall not be equipped with a constant burning pilot light.
h A boiler not equipped with a tankless domestic water heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.
i This table is a replica of ASHRAE 90.1 Table 6.8.1-6 Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements.