Wash. Admin. Code § 51-11C-403326 - Table C403.3.2(6)-Minimum efficiency requirements-Gas-fired and oil-fired boilers

Table C403.3.2(6)

Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements

Equipment Typea

Subcategory or Rating Condition

Size Category (Input)

Minimum Efficiency

Test Procedurea

Boilers, hot water

Gas-fired

< 300,000 Btu/hg,h for applications outside the U.S.

82% AFUE

DOE 10 C.F.R. 430 Appendix N

[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/he

84% Etd

DOE 10 C.F.R. 431.86

< 2,500,000 Btu/h and [LESS THAN EQUAL TO] 10,000,000 Btu/hb

85% Etd

10,000,000 Btu/hb

82% Ecc

Oil-firedf

< 300,000 Btu/hg,h

84% AFUE

DOE 10 C.F.R. 430 Appendix N

[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/he

87% Etd

DOE 10 C.F.R. 431.86

2,500,000 Btu/hb

88% Ecc

10,000,000 Btu/hb

84% Ecd

Boilers, steam

Gas-fired

< 300,000 Btu/hg

81% AFUE

DOE 10 C.F.R. 430 Appendix N

Gas-fired - all, except natural draft

[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb

82% Etd

DOE 10 C.F.R. 431.86

2,500,000 Btu/ha

79% Etd

10,000,000 Btu/hb

79% Etd

Gas-fired - natural draft

[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb

81% Etd

2,500,000 Btu/hb

82% Etd

10,000,000 Btu/hb

79% Etd

Oil-firedf

< 300,000 Btu/h

82% AFUE

DOE 10 C.F.R. 430 Appendix N

[GREATER THAN EQUAL TO] 300,000 Btu/h and [LESS THAN EQUAL TO] 2,500,000 Btu/hb

84% Etd

DOE 10 C.F.R. 431.86

2,500,000 Btu/hb

85% Etd

10,000,000 Btu/hb

81% Etd

For SI: 1 British thermal unit per hour = 0.2931 W.

a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.

b These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.

c Ec = Combustion efficiency (100 percent less flue losses).

d Et = Thermal efficiency.

e Maximum capacity - Minimum and maximum ratings as provided for and allowed by the unit's controls.

f Includes oil-fired (residual).

g Boilers shall not be equipped with a constant burning pilot light.

h A boiler not equipped with a tankless domestic water heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.

i This table is a replica of ASHRAE 90.1 Table 6.8.1-6 Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements.

Notes

Wash. Admin. Code § 51-11C-403326
Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023