Wash. Admin. Code § 51-11C-40333 - Section C403.3.3-Hot gas bypass
C403.3.3
Hot gas bypass
limitation. Cooling systems shall not use hot gas bypass or other
evaporator pressure control systems unless the system is designed with multiple
steps of unloading or continuous capacity modulation. The capacity of the hot
gas bypass shall be limited as indicated in Table C403.3.3, as limited by
Section C403.5.1.
Table C403.3.3
Maximum Hot Gas Bypass Capacity
Rated Capacity | Maximum Hot Gas BypassCapacity (% of totalcapacity) |
[LESS THAN EQUAL TO] 240,000 Btu/h | 50 |
[GREATER THAN] 240,000 Btu/h | 25 |
For SI: 1 British thermal unit per hour = 0.2931 W.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
C403.3.3 Hot gas bypass limitation. Cooling systems shall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table C403.3.3, as limited by Section C403.5.1.
Table C403.3.3
Maximum Hot Gas Bypass Capacity
Rated Capacity | Maximum Hot Gas BypassCapacity (% of totalcapacity) |
[LESS THAN EQUAL TO] 240,000 Btu/h | 50 |
[GREATER THAN] 240,000 Btu/h | 25 |
For SI: 1 British thermal unit per hour = 0.2931 W.