C403.3.7 Hydronic system flow rate. Chilled water and condenser water piping shall be designed such that the design flow rate in each pipe segment shall not exceed the values listed in Table C403.3.7 for the appropriate total annual hours of operation. Pipe sizes for systems that operate under variable flow conditions (e.g., modulating 2-way control valves at coils) and that contain variable speed pump motors are permitted to be selected from the "Variable Flow/Variable Speed" columns. All others shall be selected from the "Other" columns.

EXCEPTION:

Design flow rates exceeding the values in Table C403.3.7 are permitted in specific sections of pipe if the pipe is not in the critical circuit at design conditions and is not predicted to be in the critical circuit during more than 30 percent of operating hours.

Table C403.3.7

Piping System Design Maximum Flow Rate in GPMa

Pipe Size

[LESS THAN EQUAL TO] 2000 hours/year

2000 and [LESS THAN EQUAL TO] 4400 hours/year

4400 hours/year

(in)

Other

Variable Flow/ Variable Speed

Other

Variable Flow/ Variable Speed

Other

Variable Flow/ Variable Speed

2 1/2

120

180

85

130

68

110

3

180

270

140

210

110

170

4

350

530

260

400

210

320

5

410

620

310

470

250

370

6

740

1100

570

860

440

680

8

1200

1800

900

1400

700

1100

10

1800

2700

1300

2000

1000

1600

12

2500

3800

1900

2900

1500

2300

Maximum velocity for pipes over 14 to 24 in. in size

8.5 ft/s

13.0 ft/s

6.5 ft/s

9.5 ft/s

5.0 ft/s

7.5 ft/s