Wash. Admin. Code § 51-11C-40373 - Section C403.7.3-Ventilation air heating control

C403.7.3 Ventilation air heating control. For ventilation air units with supplemental heating capacity that operate in conjunction with zone heating and cooling systems, supplemental heating shall not warm ventilation supply air to a temperature greater than 55°F (13°C).