Wash. Admin. Code § 51-11C-40502 - Section C405.2-Electrical power and lighting systems

C405.2 Lighting controls. Lighting systems shall be provided with controls that comply with one of the following:
1. Lighting controls as specified in Sections C405.2.1 through C405.2.10.
2. Luminaire-level lighting controls (LLLC) as specified in Section C405.2.8.1.

EXCEPTION:

Except for specific application controls required by Section C405.2.6, lighting controls are not required for the following:

1. Areas designated as security or emergency areas that are required to beously lighted.

2. Means of egress illumination serving the exit access that does not exceed 0.01 watts per square foot of building area.

3. Emergency egress lighting that is normally off.

4. Industrial or manufacturing process areas, as may be required for production and safety.