Wash. Admin. Code § 51-11C-405021 - Section C405.2.1-Occupant sensor controls
EXCEPTIONS: |
1. Corridors in manufacturing facilities. 2. General lighting and task lighting in shop and laboratory classrooms. 3. Luminaires that are required to have specific application controls in accordance with Section C405.2.6 unless specifically required to comply with this section by Section C405.2.6. |
Table C405.4.2(1) Interior Lighting Power Allowances-Building Area Method
Space Type |
Comply with Section |
Classrooms/lecture/training rooms |
C405.2.1.1 |
Conference/meeting/multipurpose rooms |
C405.2.1.1 |
Copy/print rooms |
C405.2.1.1 |
Lounge/breakrooms |
C405.2.1.1 |
Enclosed offices |
C405.2.1.1 |
Open plan office areas |
C405.2.1.3 |
Restrooms |
C405.2.1.1 |
Storage rooms |
C405.2.1.1 |
Locker rooms |
C405.2.1.1 |
Other spaces 300 square feet (28 m2) or less that are enclosed by |
C405.2.1.1 |
Warehouse storage areas |
C405.2.1.2 |
Library stacks |
C405.2.1.2 |
Enclosed fire rated stairways |
C405.2.1.5 |
Corridors |
C405.2.1.6 |
EXCEPTION: |
Full automatic-on controls with no manual control shall be permitted in corridors, interior parking areas, stairways, restrooms, locker rooms, library stacks, lobbies, and areas where manual operation would endanger occupant safety or security. |
EXCEPTION: |
Corridors provided with less than two foot-candles of illumination on the floor at the darkest point with all lights on |
Notes
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-405021, filed 2/1/13, effective 7/1/13.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
EXCEPTIONS: | 1. Corridors in manufacturing facilities. 2. General lighting and task lighting in shop and laboratory classrooms. 3. Luminaires that are required to have specific application controls in accordance with Section C405.2.6 unless specifically required to comply with this section by Section C405.2.6. |
Table C405.4.2(1) Interior Lighting Power Allowances-Building Area Method
Space Type | Comply with Section |
Classrooms/lecture/training rooms | C405.2.1.1 |
Conference/meeting/multipurpose rooms | C405.2.1.1 |
Copy/print rooms | C405.2.1.1 |
Lounge/breakrooms | C405.2.1.1 |
Enclosed offices | C405.2.1.1 |
Open plan office areas | C405.2.1.3 |
Restrooms | C405.2.1.1 |
Storage rooms | C405.2.1.1 |
Locker rooms | C405.2.1.1 |
Other spaces 300 square feet (28 m2) or less that are enclosed by | C405.2.1.1 |
Warehouse storage areas | C405.2.1.2 |
Library stacks | C405.2.1.2 |
Enclosed fire rated stairways | C405.2.1.5 |
Corridors | C405.2.1.6 |
EXCEPTION: | Full automatic-on controls with no manual control shall be permitted in corridors, interior parking areas, stairways, restrooms, locker rooms, library stacks, lobbies, and areas where manual operation would endanger occupant safety or security. |
EXCEPTION: | Corridors provided with less than two foot-candles of illumination on the floor at the darkest point with all lights on |
Notes
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-405021, filed 2/1/13, effective 7/1/13.