Wash. Admin. Code § 51-11C-405027 - Section C405.2.7-Area controls
C405.2.7
Area
controls. The maximum lighting power that may be controlled from a
single switch or automatic control device shall not exceed that which is
provided by a 20 ampere circuit loaded to not more than 80 percent. A master
control may be installed provided the individual switches retain their
capability to function independently. Circuit breakers may not be used as the
sole means of switching.
EXCEPTION: |
Areas less than 5 percent of the building footprint for footprints over 100,000 ft2. |
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
C405.2.7 Area controls. The maximum lighting power that may be controlled from a single switch or automatic control device shall not exceed that which is provided by a 20 ampere circuit loaded to not more than 80 percent. A master control may be installed provided the individual switches retain their capability to function independently. Circuit breakers may not be used as the sole means of switching.