Wash. Admin. Code § 51-11C-405053 - Table C405.4.2(1)-Interior lighting power allowances-Building area method
Table C405.4.2(1)
Interior Lighting Power Allowances-Building Area Method
Building Area Type |
LPD (w/ ft2) |
Automotive facility |
0.64 |
Convention center |
0.64 |
Court house |
0.79 |
Dining: Bar lounge/leisure |
0.79 |
Dining: Cafeteria/fast food |
0.72 |
Dining: Family |
0.71 |
Dormitory |
0.46 |
Exercise center |
0.67 |
Fire station |
0.54 |
Gymnasium |
0.75 |
Health care clinic |
0.70 |
Hospital |
0.84 |
Hotel/motel |
0.56 |
Library |
0.83 |
Manufacturing facility |
0.82 |
Motion picture theater |
0.44 |
Multiple family |
0.41 |
Museum |
0.55 |
Office |
0.64 |
Parking garage |
0.14 |
Penitentiary |
0.65 |
Performing arts theater |
0.84 |
Police station |
0.66 |
Post office |
0.65 |
Religious building |
0.67 |
Retail |
0.84 |
School/university |
0.70 |
Sports arena |
0.62 |
Town hall |
0.69 |
Transportation |
0.50 |
Warehouse |
0.40 |
Workshop |
0.91 |
Notes
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-405053, filed 2/1/13, effective 7/1/13.