Wash. Admin. Code § 51-11C-405054 - Table C405.4.2(2)-Interior lighting power allowances-Space-by-space method

Table C405.4.2(2)

Interior Lighting Power Allowances-Space-by-Space Method

Common Space-by-Space Typesa

LPD (w/ft2)

Atrium - Less than 20 feet in height

0.39

Atrium - 20 to 40 feet in height

0.48

Atrium - Above 40 feet in height

0.60

Audience/seating area - Permanenti

In an auditorium

0.61

In a gymnasium

0.23

In a motion picture theater

0.27

In a penitentiary

0.67

In a performing arts theater

1.16

In a religious building

0.72

In a sports arena

0.33

Otherwise

0.23

Banking activity areai

0.61

Breakroom (see lounge/breakroom)

Classroom/lecture hall/training room

In a penitentiary

0.89

Otherwiseh

0.71

Computer room, data center

0.94

Conference/meeting/multipurpose

0.97

Confinement cell

0.70

Copy/print room

0.31

Corridor

In a facility for the visually

impaired (and not used

primarily by the staff)b

0.71

In a hospital

0.71

In a manufacturing facility

0.41

Otherwisec,i

0.41

Courtroomc

1.20

Dining area

In a penitentiary

0.42

In a facility for the visually

impaired (and not used

primarily by the staff)b

1.27

In a bar/lounge or leisure

diningi

0.86

In cafeteria or fast food

dining

0.40

In a family dining areai

0.60

Otherwise

0.43

Electrical/mechanical

0.43

Emergency vehicle garage

0.52

Food preparation

1.09

Guest rooma,b

0.41

Laboratory

In or as a classroom

1.11

Otherwise

1.33

Laundry/washing area

0.53

Loading dock, interior

0.88

Lobbyc

In a facility for the visually

impaired (and not used

primarily by the staff)b

1.69

For an elevator

0.65

In a hotel

0.51

In a motion picture theater

0.23

In a performing arts theater

1.25

Otherwise

0.84

Locker room

0.52

Lounge/breakroomi

In a health care facilityc,i

0.42

Otherwisei

0.59

Office

Enclosed [LESS THAN EQUAL TO] 250

0.74

Enclosed [GREATER THAN] 250

0.66

Open plan

0.61

Parking area, interior

0.15

Pharmacy area

1.66

Restroom

In a facility for the visually

impaired (and not used

primarily by the staff)b

1.26

Otherwisei

0.63

Sales area

1.05

Seating area, general

0.23

Stairway (see space containing stairway)

Stairwellc,i

0.49

Storage room

< 50 ft2

0.51

50-100 ft2

0.38

All other storage

0.38

Vehicular maintenance

0.60

Workshop

1.26

Automotive (see vehicular

maintenance)

Convention center - Exhibit spacei

0.61

Dormitory living quartersa,b

0.50

Facility for the visually impairedb

In a chapel (and not used

primarily by the staff)b

0.70

In a recreation room (and not

used primarily by the staff)b

1.77

Fire stations

Sleeping quarters

0.23

Gymnasium/fitness center

In an exercise area

0.90

In a playing area

0.85

Health care facilityc,i

In an exam/treatment room

1.40

In an imaging room

0.94

In a medical supply room

0.62

In a nursery

0.92

In a nurse's station

1.17

In an operating room

2.26

In a patient room

0.68

In a physical therapy room

0.91

In a recovery room

1.25

Library

In a reading areai

0.96

In the stacks

1.10

Manufacturing facility

In a detailed manufacturing

area

0.80

In an equipment room

0.76

In an extra high bay area

(greater than 50-foot floor-

to-ceiling height)

1.42

In a high bay area (25 - 50-

foot floor-to-ceiling height)

1.24

In a low bay (< 25-foot

floor-to-ceiling height)

0.86

Museum

In a general exhibition areai

0.31

In a restoration room

1.10

Performing arts theater dressing/

fitting room

0.41

Post office - Sorting area

0.76

Religious buildings

In a fellowship halli

0.54

In a worship/pulpit/choir

area i

0.85

Retail facilities

In a dressing/fitting room

0.51

In a mall concourse

0.82

Sports arena - Playing area

For a Class 1 facilityd

2.94

For a Class 2 facilitye

2.01

For a Class 3 facilityf

1.30

For a Class 4 facility g

0.86

Transportation

In a baggage/carousel area

0.39

In an airport concourse

0.25

At a terminal ticket

counteri

0.51

Warehouse - Storage area

For medium to bulky

palletized items

0.33

For smaller, hand-carried items

0.69

For SI: 1 foot = 304.8 mm, 1 watt per square foot = 10.76 W/m2.

a In cases where both a common space type and a bng area specific space type are listed, the building area specific space type shall apply.

b A facility for the visually impaired is a facility that is licensed or will be licensed by local or state authorities for senior long-term care, adult daycare, senior support or people with special visual needs.

c Additional lighting power allowance of 0.2 watts per square foot for the purpose of highlighting art or exhibits. This additional power shall be permitted only where the specified lighting is installed in addition to and controlled separately from general lighting in accordance with Section C405.2.6. This additional power shall be used only for the specified luminaires and shall not be used for any other purpose and it shall not be added to any other space or the interior power allowance.

d Class I facilities consist of professional facilities; and semiprofessional, collegiate or club facilities with seating for 5,000 or more spectators.

e Class II facilities consist of collegiate and semiprofessional facilities with seating for fewer than 5,000 spectators; club facilities with seating between 2,000 and 5,000 spectators; and amateur league and high school facilities with seating for more than 2,000 spectators.

f Class III facilities consist of club, amateur league and high school facilities with seating for 2,000 or fewer spectators.

g Class IV facilities consist of elementary school and recreational facilities; and amateur league and high school facilities without provisions for spectators.

h For classrooms, additional lighting power allowance of 4.50 W/lineal foot of white or chalk boards for directional lighting dedicated to white or chalk boards.

i Additional lighting power allowance of 0.15 W/ft2 for ornamental lighting. Qualifying ornamental lighting includes luminaires that are specifically used in a decorative manner This additional power shall be permitted only where the specified lighting is installed in addition to and controlled separately from display or general lighting in accordance with Section C405.2.6. This additional power shall be used only for the specified luminaires and it shall not be added to any other space or the interior power allowance.

j Where a space is designated as unfinished, neither the area nor the lighting power in the space shall be calculated as part of the LPA.

Notes

Wash. Admin. Code § 51-11C-405054
Amended by WSR 16-03-072, Filed 1/19/2016, effective 7/1/2016 Amended by WSR 19-24-040, Filed 11/26/2019, effective 7/1/2020 Amended by WSR 20-21-080, Filed 10/19/2020, effective 2/1/2021 Amended by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023