Wash. Admin. Code § 51-11C-408012 - Figure C408.1.4.1-Commissioning compliance checklist
Figure C408.1.4.1 Commissioning Compliance Checklist
Project Information |
Project Name: |
Project Address: |
|
Certified Commissioning Professional: |
|
Type of ISO Certification and Number: |
|
Supporting Documents |
[SQUARE] Manuals, record documents and training have been completed or are scheduled (Section C103.6). * Building operations and maintenance information (C103.6.2) have been submitted to the owner or scheduled date: * Manuals (C103.6.2. 1) have been submitted to the owner or scheduled date: * Compliance documentation (C103.6.3) has been provided to the owner or scheduled date: * System operation training (C103.6.4) has been provided to the owner or scheduled date: |
Commissioning Plan |
[SQUARE] Commissioning Plan was used during construction (Section C408.1. 2) |
Commissioning Report |
[SQUARE] Commissioning Report has been submitted (Section C408.1. 3) |
Commissioned Systems |
[SQUARE] Mechanical Systems were included in the commissioning process(Section C408.2) [SQUARE] Testing, adjusting and balancing is complete (Section C408.2. 2). [SQUARE] There are unresolved deficiencies with the mechanical systems. These are described in the attached Commissioning Report submitted to the owner. |
[SQUARE] Service Water Heating Systems were included in the commissioning process (Section C408.3) [SQUARE] There are unresolved deficiencies with the service water heating systems. These are described in the attached Commissioning Report submitted to the owner. |
|
[SQUARE] Controlled receptacles and lighting control systems were included in the commissioning process (Section C408.4) [SQUARE] There are unresolved deficiencies with the electrical power and/or automatic lighting controls. These are described in the attached Commissioning Report submitted to the owner. |
|
[SQUARE] Additional Systems included in the commissioning process (Section C408.5) [SQUARE] There are unresolved deficiencies with systems required by Section C406 or Section C407. These are described in the attached Commissioning Report submitted to the owner. |
|
[SQUARE] Metering Systems were included in the commissioning process (Section C408.6) [SQUARE] There are unresolved deficiencies with the metering system. These are described in the attached Commissioning Report submitted to the owner. |
|
[SQUARE] Refrigeration Systems were included in the commissioning process (Section C408.7) [SQUARE] There are unresolved deficiencies with the systems required by Section C410. These are described in the attached Commissioning Report submitted to the owner. |
|
Certification |
[SQUARE] I hereby certify that all requirements for Section C408 System Commissioning have been completed in accordance with the Washington State Energy Code, including all items above. _____________________________________________ Certified Commissioning Professional Date |
[SQUARE] I hereby certify that all requirements for Section C408 System Commissioning have been completed in accordance with the Washington State Energy Code, including all items above. _____________________________________________ Building Owner or Owner's Authorized Agent Date |
Notes
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-408012, filed 2/1/13, effective 7/1/13.
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
Figure C408.1.4.1 Commissioning Compliance Checklist
Project Information | Project Name: |
Project Address: | |
Certified Commissioning Professional: | |
Type of ISO Certification and Number: | |
Supporting Documents | [SQUARE] Manuals, record documents and training have been completed or are scheduled (Section C103.6). * Building operations and maintenance information (C103.6.2) have been submitted to the owner or scheduled date: * Manuals (C103.6.2. 1) have been submitted to the owner or scheduled date: * Compliance documentation (C103.6.3) has been provided to the owner or scheduled date: * System operation training (C103.6.4) has been provided to the owner or scheduled date: |
Commissioning Plan | [SQUARE] Commissioning Plan was used during construction (Section C408.1. 2) |
Commissioning Report | [SQUARE] Commissioning Report has been submitted (Section C408.1. 3) |
Commissioned Systems | [SQUARE] Mechanical Systems were included in the commissioning process(Section C408.2) [SQUARE] Testing, adjusting and balancing is complete (Section C408.2. 2). [SQUARE] There are unresolved deficiencies with the mechanical systems. These are described in the attached Commissioning Report submitted to the owner. |
[SQUARE] Service Water Heating Systems were included in the commissioning process (Section C408.3) [SQUARE] There are unresolved deficiencies with the service water heating systems. These are described in the attached Commissioning Report submitted to the owner. | |
[SQUARE] Controlled receptacles and lighting control systems were included in the commissioning process (Section C408.4) [SQUARE] There are unresolved deficiencies with the electrical power and/or automatic lighting controls. These are described in the attached Commissioning Report submitted to the owner. | |
[SQUARE] Additional Systems included in the commissioning process (Section C408.5) [SQUARE] There are unresolved deficiencies with systems required by Section C406 or Section C407. These are described in the attached Commissioning Report submitted to the owner. | |
[SQUARE] Metering Systems were included in the commissioning process (Section C408.6) [SQUARE] There are unresolved deficiencies with the metering system. These are described in the attached Commissioning Report submitted to the owner. | |
[SQUARE] Refrigeration Systems were included in the commissioning process (Section C408.7) [SQUARE] There are unresolved deficiencies with the systems required by Section C410. These are described in the attached Commissioning Report submitted to the owner. | |
Certification | [SQUARE] I hereby certify that all requirements for Section C408 System Commissioning have been completed in accordance with the Washington State Energy Code, including all items above. _____________________________________________ Certified Commissioning Professional Date |
[SQUARE] I hereby certify that all requirements for Section C408 System Commissioning have been completed in accordance with the Washington State Energy Code, including all items above. _____________________________________________ Building Owner or Owner's Authorized Agent Date |
Notes
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-408012, filed 2/1/13, effective 7/1/13.