Wash. Admin. Code § 51-11C-61061 - Section A106.1 - General

A106.1 General. Table A106.1 lists heat loss coefficients for heated on-grade slab floors, in units of Btu/h . °F per lineal foot of perimeter.

Table A106.1 Default F -factors for On-Grade Slabs

Insulation Type

R-0

R-5

R-10

R-15

R-20

R-30

Unheated Slab

Uninsulated slab

0.73

--

--

--

--

--

2 ft. Horizontal (No thermal break)

--

0.70

0.70

0.69

--

--

4 ft. Horizontal (No thermal break)

--

0.67

0.64

0.63

--

--

2 ft. Vertical

--

0.58

0.54

0.52

--

--

4 ft. Vertical

--

0.54

0.48

0.45

--

--

Fully insulated slab*

--

--

0.36

0.31

0.26

0.21

Heated Slab

Uninsulated slab

0.84

--

--

--

--

--

Fully insulated slab*

--

0.74

0.55

0.44

0.39

0.32

R-5 Center (With perimeter insulation)

--

--

0.66

0.62

--

--

R-10 Center (With perimeter insulation)

--

--

--

0.51

--

--

3 ft. Vertical

--

--

0.78

--

--

--

*Edge insulation R-10 regardless of the below slab insulation level.

Notes

Wash. Admin. Code § 51-11C-61061

Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-61061, filed 2/1/13, effective 7/1/13.