W. Va. Code R. § 36-1-31 - Electrical Provisions - Shaft and/or Slope
31.1. Power circuits and electric equipment
shall be deenergized before work is done on such circuits and equipment, except
when necessary for troubleshooting or testing.
31.2. No electrical work shall be performed
on electrical distribution circuits or equipment, except by a qualified person
or by a person trained to perform electrical work and to maintain electrical
equipment under the direct supervision of a qualified person. Disconnecting
devices shall be locked out and suitably tagged by each person who performs
such work, except that in cases where locking out is not possible, such devices
shall be opened and suitably tagged by each person who installed them, or, if
such persons are unavailable, by qualified persons authorized by the operator
or his/her agent.
31.3. Electrical
equipment shall be examined weekly, tested, and properly maintained by a
qualified person to assure safe operating conditions. When a potentially
dangerous condition is found on electric equipment, such equipment shall be
removed from service until such condition is corrected. A record of such
examination shall be kept and made available to an authorized representative of
the Director and to the miners in such mine.
31.4. Surface transformers shall be elevated
at least eight (8) feet above the ground or enclosed by a fence six (6) feet
high, grounded if metal; shall be properly grounded; shall be installed so that
they will not present a fire hazard; and shall be guarded by sufficient danger
signs. The gate or door to the enclosure shall be kept locked at all times
unless authorized persons are present.
31.5. Electric conductors shall be sufficient
in size and have adequate carrying capacity and be of such construction that a
rise in temperature resulting from normal operation will not damage the
insulating material.
31.6.
Electrical connections or splices in electric conductors shall be mechanically
and electrically efficient, and suitable connectors shall be used. All
electrical connections or splices in electrical connections or splices in
insulated wire shall be reinsulated at least to the same degree of protection
as the remainder of the wire.
31.7.
Short circuit protection to protect all electric equipment and circuits against
short circuits and overloads shall be provided by an automatic circuit breaker
or other no less effective device approved by the Director. Three-phase motors
on all electric equipment shall be provided with overload protection that will
deenergize all three phases in the event that any phase is overloaded.
31.8. The booms and masts of
equipment operated on the surface of any shaft or slope shall not be operated
within ten (10) feet of an energized overhead powerline. Where the voltage of
overhead powerlines is sixty-nine thousand (69,000) volts or more, the minimum
distance from the boom or mast shall be as follows:
|
Nominal power line voltage (in (1,000) volts) |
Minimum distance (feet) |
|
69-114 |
12 |
|
115-229 |
15 |
|
230-344 |
20 |
|
345-499 |
25 |
|
500 or more |
35 |
31.9.
During construction, electrical equipment employed below the collar or within
twenty-five (25) feet of the return or exhaust of a slope or shaft during
excavation shall be approved or permissible and shall be maintained in a
permissible condition.
31.10. The
insulation of all electric conductors employed below the collar of any slope
and shaft during excavation shall be of the flame resistant type.
31.11. During the construction of shaft or
slope only lamps and portable flood lights approved by MSHA shall be permitted
below the collar of the shaft or slope.
31.12. Metallic frames, casings, and other
enclosures of electric equipment that can become "alive" through failure of
insulation or by contact with energized parts shall be effectively grounded.
31.13. All power wires (except
trailing cables on mobile equipment, specially designed cables conducting
high-voltage power to underground rectifying equipment or transformers, or bare
or insulated ground and return wires) shall be supported on well-insulated
insulators and shall not contact combustible material, roof, or ribs.
31.14. Well-insulated insulators
is interpreted to mean well-installed insulators. Insulated J-hooks may be used
to suspend insulated power cables for temporary installation not exceeding six
(6) months and for permanent installation of control cables such as may be used
along belt conveyors.
31.15. Power
wires and cables shall be insulated adequately and fully protected.
31.16. Power wires and cables shall have
insulation with a dielectric strength at least equal to the voltage of the
circuit.
31.17. Each ungrounded,
exposed power conductor that leads underground shall be equipped with suitable
lightning arresters of approved type within one-hundred (100) feet of the point
where the circuit enters the mine. Lightning arresters shall be connected to a
low resistance grounding medium on the surface which shall be separated from
neutral grounds by a distance of not less than twenty-five (25) feet.
31.18. Short circuit protection for trailing
cables shall be provided by an automatic circuit breaker or other no less
effective device approved by the Director of adequate current-interrupting
capacity in each ungrounded conductor. Disconnecting devices used to disconnect
power from trailing cables shall be plainly marked and identified and such
devices shall be equipped or designed in such a manner that it can be
determined by visual observation that the power is disconnected and a suitable
means to provide the ability to lock and tag.
31.19. Dry insulating platforms of rubber or
other suitable nonconductive material shall be kept in place at each
switchboard and at stationary machinery where shock hazards exist.