W. Va. Code R. § 36-48-3 - High Voltage Protection
3.1. The
nominal voltage of power circuits shall not exceed 2,400 volts.
3.2. The nominal voltage of the control
circuits shall not exceed 120 volts.
3.3. The ground-fault current shall be
limited by a neutral grounding resistor to not more than 0.5 ampere. Current
transformers used for the ground-fault protection shall be the single-window
type and shall be installed to encircle all three-phase conductors.
3.4. The trailing cable for the 2,400-volt
continuous miner circuit shall be provided with instantaneous ground-fault
protection set at not more than 0.125 ampere. The ground-fault protection
device shall be equipped with an impedance measuring feature, "Look-Ahead"
circuit, to guard against closing the circuit breaker on a circuit that has an
existing ground-fault condition.
3.5. The neutral grounding resistor shall be
provided with backup ground fault protection that will de-energize the primary
of the transformer if a ground fault occurs with the neutral grounding resistor
open. This protection shall be set at 40% of the maximum voltage that could
appear across the neutral grounding resistor during a ground fault. A time
delay set at the lowest practical value that permits reliable coordination
shall be permitted. The time delay shall not exceed 0.250 second.
3.6. The neutral grounding resistor for the
transformer supplying power to the 2,400-volt continuous miner shall be
provided with thermal protection that will de-energize the incoming
high-voltage circuit supplying power to the power center if the grounding
resistor is subjected to a sustained ground-fault. The thermal protection shall
operate at either 50 percent of the maximum temperature rise of the grounding
resistor, or 1500 C (3020
F), whichever is less. The thermal protection shall not be dependent upon
control power and may consist of a current transformer and overcurrent relay in
the grounding resistor circuit.
3.7. The trailing cable for the continuous
miner shall be provided with instantaneous short-circuit protection set at no
more than the setting specified in the continuous miner approval documentation
or 75 percent of the minimum phase-to-phase short-circuit current available at
the continuous miner, whichever is less.
3.8. The short-circuit protective device
shall contain no intentional time delay and shall be based on the maximum
asymmetrical starting current or have a time delay of no more than 0.05 seconds
and be based on the maximum symmetrical starting current. The time delay
settings shall not exceed the settings specified in the approval
documentation.
3.9. Guarding made
of grounded metal or nonconductive flame-resistant material shall be provided
to minimize the possibility of miners contacting the high-voltage trailing
cable and to protect the high-voltage trailing cable from damage. The
high-voltage trailing cable shall be installed on well insulated insulators or
guarded at the following locations:
3.9.a.
The high-voltage trailing cable shall be guarded at the power center cable
coupler for a distance of 10 feet.
3.9.b. The high-voltage trailing cable shall
be installed on well insulated insulators from the power center to the last
open crosscut and shall be guarded at any location on the working section where
it may be damaged by moving equipment. That portion of the trailing cable that
is located in or inby the last open crosscut shall be hung when other equipment
cables must cross the high-voltage trailing cable.
3.9.c. The high-voltage trailing cable shall
be provided with a guard that extends from the high-voltage miner cable
entrance gland for a distance of a minimum of 10 feet.