W. Va. Code R. § 36-9-4 - Electrical Provisions-Shaft and/or Slope
4.1. Power circuits and electric equipment
shall be deenergized before work is done on such circuits and equipment, except
when necessary for troubleshooting or testing.
4.2. No electrical work shall be performed on
electrical distribution circuits or equipment, except by a qualified person or
by a person trained to perform electrical work and to maintain electrical
equipment under the direct supervision of a qualified person. Disconnecting
devices shall be locked out and suitably tagged by the persons who perform such
work, except that in cases where locking out is not possible, such devices
shall be opened and suitably tagged by such persons who installed them, or, if
such persons are unavailable, by persons authorized by the operator or his
agent.
4.3. Electrical equipment
shall be examined weekly, tested monthly, and properly maintained by a
qualified person to assure safe operating conditions. When a potentially
dangerous condition is found on electric equipment, such equipment shall be
removed from service until such condition is corrected. A record of such
examination shall be kept and made available to an authorized representative of
the director of the department of energy and to the miners in such
mine.
4.4. Surface transformers
shall be elevated at least eight (8) feet above the ground or enclosed by a
fence six (6) feet high, grounded if metal; shall be properly grounded; shall
be installed so that they will not present a fire hazard; and shall be guarded
by sufficient danger signs. The gate or door to the enclosure shall be kept
locked at all times, unless authorized persons are present.
4.5. Electric conductors shall be sufficient
in size and have adequate carrying capacity and be of such construction that a
rise in temperatures resulting from normal operation will not damage the
insulating materials.
4.6.
Electrical connections or splices in electric conductors shall be mechanically
and electrically efficient, and suitable connectors shall be used. All
electrical connections or splices in electrical connections or splices in
insulated wire shall be reinsulated at least to the same degree of protection
as the remainder of the wire.
4.7.
Short circuit protection to protect all electric equipment and circuits against
short circuits and overloads, shall be provided by an automatic circuit breaker
or other no less effective device approved by the Director of the Department of
Energy. Three-phase motors on all electric equipment shall be provided with
overload protection that will deenergize all three phases in the event that any
phase is overloaded.
4.8. The booms
and masts of equipment operated on the surface of any shaft or slope shall not
be operated within ten (10) feet of an energized overhead powerline. Where the
voltage of overhead powerlines is sixty-nine thousand (69,000) volts or more
the minimum distance from the boom or mast shall be as follows:
|
Nominal power line |
Minimum distance (feet) |
|
voltage (in (1,000) volts) |
|
|
69-114............................................ |
12 |
|
115-229.......................................... |
15 |
|
230-344.......................................... |
20 |
|
345-499.......................................... |
25 |
|
500 or more................................... |
35 |
4.9.
During construction electrical equipment employed below the collar or within
twenty-five (25) feet of the return or exhaust of a slope or shaft during
excavation shall be approved or permissible and shall be maintained in a
permissible condition.
4.10. The
insulation of all electric conductors employed below the collar of any slope
and shaft during excavation shall be of the flame resistant type.
4.11. During the construction of shaft or
slope only lamps and portable flood lights approved by the Bureau of Mines
shall be permitted below the collar of the shaft or slope.
4.12. Metallic frames, casings, and other
enclosures of electric equipment that can become "alive" through failure of
insulation or by contact with energized parts shall be effectively
grounded.
4.13. All power wires
(except trailing cables on mobile equipment, specially designed cables
conducting high-voltage power to underground rectifying equipment or
transformers, or bare or insulated ground and return wires) shall be supported
on well-insulated insulators and shall not contact combustible material, roof,
or ribs.
4.14. Well-insulated
insulators is interpreted to mean well-installed insulators. Insulated J-hooks
may be used to suspend insulated power cables for temporary installation not
exceeding six (6) months and for permanent installation of control cables such
as may be used along belt conveyors.
4.15. Power wires and cables shall be
insulated adequately and fully protected.
4.16. Power wires and cables shall have
insulation with a dielectric strength at least equal to the voltage of the
circuit.
4.17. Each undergrounded,
exposed power conductor and each ungrounded exposed telephone wire that leads
underground shall be equipped with suitable lightning arresters of approved
type within one-hundred (100) feet of the point where the circuit enters the
mine. Lightning arresters shall be connected to a low resistance grounding
medium on the surface which shall be separated from neutral grounds by a
distance of not less than twenty-five (25) feet.
4.18. Short circuit protection for trailing
cables shall be provided by an automatic circuit breaker or other no less
effective device approved by the Director of the Department of Energy of
adequate current-interrupting capacity in each ungrounded conductor.
Disconnecting devices used to disconnect power from trailing cables shall be
plainly marked and identified and such devices shall be equipped or designed in
such a manner that it can be determined by visual observation that the power is
disconnected.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.