W. Va. Code R. § 47-63-9 - Corrosion and Deterioration Prevention
9.1 General corrosion requirements. - The
owner or operator shall ensure that all regulated ASTs are maintained with
those corrosion prevention measures that are necessary to prevent releases.
9.1.a. The owner or operator shall ensure
that regulated AST systems are maintained with corrosion and deterioration
prevention measures until the AST system has undergone permanent
closure.
9.1.b. Acceptable
corrosion and deterioration protection methods may include any one or a
combination of various methods, such as cathodic protection systems (galvanic
or impressed current), external and internal coatings, internal tank liners,
storage in a manner that prevents metal contact with an electrolyte,
construction out of noncorrodible material or metal construction with a
noncorrodible material coating.
9.2 Cathodic Protection Systems.-To the
extent that a cathodic protection system is used as corrosion prevention, the
owner or operator shall ensure that cathodic protection systems are designed by
a National Association of Corrosion Engineers (NACE) certified (or equivalent)
corrosion expert and maintained to provide protection against external
corrosion for the operational life of the regulated tank system (tank, tank
bottoms, piping) or have provisions to allow for the periodic rehabilitation of
the cathodic protection system as needed to affect repairs of failing or
defective systems.
9.2.a. For new,
reconstructed or relocated regulated tanks, the owner or operator shall ensure
that special consideration for monitoring the cathodic protection status of the
underside of the AST bottom shall be provided for in the cathodic protection
system designed by the corrosion expert.
9.2.b. Regulated metallic AST systems with
tank bottoms in direct contact with soil or other electrolytes shall be
protected from corrosion, unless the tank is installed at a site that is
determined by a NACE certified or equivalent corrosion expert not to be
corrosive enough to cause it to have a release due to corrosion during its
operating life.
9.2.c. The cathodic
protection system for the external bottom of a new or existing regulated
metallic AST must be designed, installed, inspected, and maintained to meet or
exceed the requirements for cathodic protection required by NACE Standards
RP01-93, RP0169 or API 651.
9.2.d.
Each cathodic protection system shall have an access point that enables the
owner or operator to check on the adequacy of cathodic protection. The cathodic
protection systems shall be monitored in accordance with subsection 9.3 of this
Rule.
9.2.e. After installation of
a sacrificial anode system, measurements of AST-to-soil potential must be made
no sooner than 60 days and no later than 180 days after installation of the
cathodic protection system by a person who, at a minimum, is NACE certified as
a cathodic protection tester. If inadequate cathodic protection is indicated,
the cause shall be determined, and the owner or operator shall ensure that
necessary repairs are made within 90 days or another time period approved by
the Secretary upon request of the owner or operator and for good cause
shown.
9.2.f. AST and piping
connections of two dissimilar metals which create a galvanic cell are
prohibited.
9.2.g. For existing
regulated AST systems certified as Fit for Service but having cathodic
protection deficiencies, the cathodic protection system shall be upgraded to
meet the minimum requirements of this Rule and industry standards on the
schedule provided by the certifying person, but in no case later than the
following:
9.2.g.1. For Level 1 ASTs, the AST
system component not meeting cathodic protection standards must be upgraded or
repaired and tested by June 30, 2017.
9.2.g.2. For Level 2 ASTs, the AST system
component not meeting cathodic protection standards must be upgraded or
repaired and tested by December 31, 2017.
9.2.g.3. An existing regulated tank system
that is taken out of service for internal inspection or major modification of
the tank or that has been temporarily out of service and being returned to
service shall have the cathodic protection upgraded or repaired and tested
prior to placing the AST back into service.
9.3 Operation and Maintenance of Cathodic
Protection Systems. - The owner or operator of a regulated AST system with
cathodic protection shall ensure compliance with the following requirements to
ensure that releases due to corrosion are prevented for as long as the AST
system is used to store fluids.
9.3.a. All
cathodic protection systems must be operated and maintained to continuously
provide corrosion protection to the metal components of that portion of the
regulated tank and piping that routinely contain fluid substances and are in
contact with soil or an electrolyte.
9.3.b. All regulated AST systems equipped
with galvanic or impressed current cathodic protection systems must be
inspected for proper operation by a qualified cathodic protection tester in
accordance with the following requirements:
9.3.b.1. Cathodic protection systems must be
tested within six months of installation and every three years thereafter by a
person who, at a minimum, is NACE certified as a cathodic protection tester.
However cathodic protection systems on tank bottoms in direct contact with soil
or other electrolytes shall be tested within six months of installation and
annually thereafter; and
9.3.b.2.
The owner or operator must maintain the results of the last two (2) cathodic
protection tests and provide those to the Secretary upon request.
9.3.c. The owner or operator of a
regulated AST system with impressed current cathodic protection systems must
have the rectifier inspected every sixty (60) days to ensure the equipment is
operating properly. The owner or operator must maintain the results of the last
six (6) rectifier readings from the impressed current system and make those
available to the Secretary for inspection upon request.
9.3.d. All impressed current systems shall be
checked by the owner or operator and tested by a NACE certified cathodic
protection tester every twelve (12) months as part of a preventative
maintenance program to minimize in-service failure. The check and tests shall
include a check for electrical shorts, ground connections, meter accuracy, and
circuit resistance. The effectiveness of isolating devices, continuity bonds,
and insulators shall be evaluated during this inspection.
9.3.e. The impressed current source shall not
be de-energized at any time, including periods when the facility is closed
(except during power failures or during service work on the regulated AST,
underground piping or impressed current system). The impressed current source
shall be equipped with a continuously operating meter or meters that display
voltage, amperage, and run time to show that the system is working.
9.3.f. If any inspection, monitoring or
testing indicates that the cathodic protection system is not functioning
properly, the owner or operator shall determine the cause and immediately
initiate the necessary repairs.
9.3.f.1. If a
cathodic protection system on a Level 1 AST system is found to be defective and
the cathodic protection system is not repairable within ninety (90) days, the
owner or operator shall take immediate action to remove substances from the
affected AST or underground piping, as applicable, in order to protect human
health or the environment.
9.3.f.2.
Substances shall not be returned to any affected part of the regulated AST
system until the defective cathodic protection system has been repaired and
passed a cathodic protection test.
9.3.g. The criteria for determining the
effectiveness of cathodic protection shall be a negative (cathodic) potential
of at least 850 millivolts (mV) with the cathodic protection current applied.
Alternatively, a negative potential of at least 850 millivolts from instant off
reading or a 100mV shift from the instant off position is acceptable for
impressed current systems. This potential shall be measured with respect to a
saturated copper/copper sulfate reference electrode contacting the
electrolyte.
9.3.h. Corrosion
protection testing required by this section shall be performed by a person
having, at a minimum, NACE certification (or equivalent) to perform corrosion
testing.
9.4 Exterior
Coatings. - For regulated metallic ASTs and piping, corrosion
protection may consist of an appropriate external coating as specified in a
nationally recognized standard or practice of a nationally recognized
association, such as the Society for Protective coatings, or an independent
testing laboratory.
9.4.a. When exterior
coatings are used as a means of corrosion protection, the owner or operator
shall ensure that the exterior surfaces of all regulated aboveground tanks and
piping are protected by a suitable coating that prevents corrosion and
deterioration in accordance with the requirements of this section.
9.4.a.1. The owner or operator shall ensure
that the coating is able to permanently bond to the regulated AST or piping and
be of sufficient thickness, density, and strength to resist corrosion,
deterioration, and degradation of the exterior of the AST or piping.
9.4.a.2. The owner or operator shall ensure
that the exterior tank and piping surfaces are properly prepared prior to the
application of a coating, so that visible rust, moisture or foreign matter is
not present immediately prior to the application of the coating.
9.4.a.3. The owner or operator shall ensure
that the exterior coating system is maintained in good condition to prevent
corrosion throughout the entire operational life of the tank or
piping.
9.4.b. In order
to prevent AST system deterioration, the owner or operator shall ensure that
the regulated AST system is repaired when the following types of painting or
coating failures are detected. Repairs may be made at the next scheduled
maintenance activity, but in no case shall the time for repairs exceed twelve
(12) months from the date of discovery for Level 1 ASTs and twenty-four (24)
months for Level 2 ASTs.
9.4.b1. Rust
spots;
9.4.b.2. Blisters;
9.4.b.3. Peeling;
9.4.b.4. Cracking;
9.4.b.5. Coating bond
failure.
9.4.c. For
existing regulated AST systems certified as Fit for Service but having
corrosion deficiencies of their coating, the corrosion protection shall be
repaired or upgraded to meet minimum requirements of this Rule and industry
standards on the schedule provided by the certifying person, but in no case
later than the following:
9.4.c.1. For Level
1 ASTs, the AST system component not meeting corrosion protection standards for
coatings must be repaired or upgraded by June 30, 2017.
9.4.c.2. For Level 2 ASTs, the AST system
component not meeting corrosion protection standards for coatings must be
repaired or upgraded by December 31, 2017.
9.4.c.3. An existing regulated tank system
that is taken out of service for internal inspection or major modification to
the tank or that has been temporarily out of service and is being returned to
service shall have deficiencies in the coatings upgraded or repaired prior to
placing the regulated AST back into service.
9.5 Interior Linings and Coatings. - Coating
or lining systems may be used, as applicable, to protect tank interiors from
corrosion and to meet requirements of compatibility of the AST with substances
stored within the regulated AST.
9.5.a. The
owner or operator shall ensure that coating or lining systems that are used in
the regulated ASTs are designed in accordance with current codes of practices
such as API 652 or associations such as NACE. Any appropriate coating that is
bonded firmly to the interior surfaces may be used to protect a tank from
corrosion. Specific requirements are as follows:
9.5.a.1. Coatings and linings shall be
chemically compatible with the substance to be stored. No owner or operator
shall allow storage of any liquid that is not compatible with the AST
system.
9.5.a.2. Coating material
shall be applied and cured in strict accordance with the manufacturer's
specifications.
9.5.a.3. Surfaces
shall be prepared and inspected in accordance with applicable
nationally-recognized codes and standards.
9.5.a.4. Coatings used to protect the bottom
of a tank shall extend up the side of the tank a minimum of 18 inches, while
some forms of lining may cover the entire tank interior.
9.5.a.5. Coatings shall be examined for
blisters and air pockets and tested for pinholes. The coating thickness shall
be checked to assure compliance with the manufacturer's specifications and
industry standards.
9.5.a.6.
Defects in coating or lining systems shall be repaired or corrected prior to
putting the tank or system into service.
9.5.b. The owner or operator shall ensure
that interior linings or coatings are inspected by an API or STI certified
aboveground storage tank inspector, NACE certified corrosion technician or
other qualified individual:
9.5.b.1. At
installation;
9.5.b.2. When the
regulated AST undergoes a major modification;
9.5.b.3. As warranted or recommended by the
manufacturer or design engineer;
9.5.b.4. At a minimum, at least every ten
years after installation of the internal lining.
9.5.c. For existing regulated systems
certified as Fit for Service but having known corrosion deficiencies of their
internal lining noted during inspections performed to meet requirements of
subdivision 9.5.b of this Rule, the corrosion protection shall be repaired or
upgraded, as applicable, to meet the minimum requirements of this Rule and
industry standards on the schedule provided by the certifying person, but in no
case later than the following:
9.5.c.1. For
Level 1 ASTs, the AST system component not meeting corrosion protection
standards for internal lining must be repaired or upgraded by June 30,
2017.
9.5.c.2. For Level 2 ASTs,
the AST system component not meeting corrosion protection standards for
internal lining must be repaired or upgraded by December 31, 2017.
9.5.c.3. A regulated existing tank system
that is taken out of service for internal inspection or major modification to
the tank or that has been temporarily out of service and is being returned to
service shall have deficiencies in the internal lining upgraded or repaired
prior to placing the AST back into service.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.