020-11 Wyo. Code R. §§ 11-10 - Pumping stations
(a) Design
conditions.
(i) Total dynamic head. The total
dynamic head rating of pumping units shall be based on pipe friction, pressure
losses from piping entrances, exits, appurtenances (bends, valves, etc.), and
static head at the rated flow.
(ii)
Grit. Where no grit removal is provided ahead of the pumping station, equipment
and piping design shall minimize the deleterious effects of grit in the
sewage.
(iii) Screening. Screens or
comminutors shall be provided ahead of pumps where the average daily flow is in
excess of 1.0 mgd (3,784 m3/d) to prevent solids
larger than 2 ½ inches (6.4 cm) from entering the pump.
(iv) Minimum pump opening. Except for grinder
pumps, raw sewage pumps shall be capable of passing spheres of at least three
(3) inches (7.6 cm) in diameter. Pump suction and discharge piping in all
sewage and sludge services shall be no smaller than four (4) inches in diameter
(10 cm).
(v) Pump cycle time.
Intermittently operated pumps shall be designed to start no more often than
once every ten (10) minutes at the minimum operating interval.
(vi) Removal of equipment. Pumping stations
shall be designed to permit removal of all items of equipment including pumps,
valves, electrical and control equipment. Equipment located in wetwells shall
be removable without entering the wetwell.
(vii) Surge control. Piping systems shall be
designed to withstand the maximum possible surge (water hammer) from the
pumping station, or adequate surge control provided to protect the piping.
Pressure relief valves are not acceptable surge control.
(viii) Net positive suction head. Pumps shall
be selected so that the net positive suction head required at maximum flow
(NPSHR) is less than the NPSH available minus four feet (1.2 m) based on the
hydraulic conditions and altitude of the pumping station.
(ix) Uplift. The pumping station chambers
shall resist hydrostatic uplift pressures. Siting requirements.
(b) Siting requirements.
(i) Access. Pumping stations shall be located
so that they are readily accessible to operating and maintenance personnel at
all times of day or night, and under all weather conditions. Pumping stations
shall be located off of traffic ways.
(ii) Flood protection. Pumping stations shall
be designed so there is no equipment or structural damage in the 100-year
flood, and so the pumping station's operation is uninterrupted by the 25-year
flood.
(iii) Security. The pumping
station shall be designed to discourage unauthorized entry.
(c) Pumping station types.
(i) Dry wells.
(A) Access. Pumping station dry wells and
equipment rooms shall be accessible for equipment inspection, operation and
maintenance. Ladder and stair dimensions, locations of landings, and structural
design shall comply with the Wyoming OHSA (1982). Equipment shall be removable
from pumping stations without making structural changes to the
station.
(B) Separation from
wetwell. Dry wells and equipment rooms shall be completely separated from
wetwells with no hatches, untrapped drains, or other connecting
accessways.
(C) Dewatering. Dry
pits and below-grade equipment rooms shall be provided with sump pumps sized to
remove infiltration of water during normal seepage and leakage.
(ii) Wetwell design. Wetwells
shall be designed to prevent vortexing and unstable pump operation. Pumps shall
be located below the minimum water level, except suction lift pumps. Suction
intakes shall be bell-mouthed. Provisions shall be made for isolating,
bypassing and/or dewatering portions of the wetwell for maintenance. Hopper
walls of wetwells shall be sloped at no less than 1.75 vertical to one (1)
horizontal.
(iii) Submersible
pumping stations. Submersible pumping stations shall be designed specifically
for totally submerged operation and so that pumps may be readily removed from
the wetwell without dewatering the wetwell or disconnecting piping in the
wetwell. Submersible pumps shall have an adequate means of indicating motor
seal failure. Electrical equipment shall be suitable for Class 1, Division 1,
Groups C and D hazardous environments, as defined in the National Electrical
Code (1982).
(iv) Suction lift.
Pumping stations utilizing suction lift pumps shall have adequate priming means
to prime the pumps quickly and shall be designed for priming the pumps when the
water level in the wetwell is one (1) foot (0.3 m) below the lead pump starting
elevation in the suction wetwell, and for maintaining prime when the wetwell
level is one (1) foot (0.3 m) below the lead pump stopping level. Valving shall
not be located in the wetwell.
(v)
Pneumatic ejectors. Pneumatic ejectors shall be limited to design flows
equivalent to 25 residential connections. One standby compressor shall be
provided.
(vi) Grinder pumps.
Grinder pumps shall be limited to design flows equivalent to 25 residential
connections.
(d) Piping
and valves.
(i) Suction.
(A) Suction intake. Suctions shall be located
so the pump is below the minimum water level. Suction intakes shall be
bell-mouthed. Suction intakes shall be located against the far wall from the
wetwell inlet.
(ii)
Piping.
(A) Size. Sewage and sludge piping
shall be no smaller than four (4) inches (10.2 cm) diameter, except as required
for metering, or where grinder pumps are provided.
(B) Velocity. Piping and pumping systems
shall be designed to maintain a minimum velocity of 2.5 fps (0.76 mps), and a
maximum velocity of 5 fps (1.52 mps) for suction piping.
(C) Design pressure. Piping shall be designed
for the maximum operating pressure and for the maximum value of any surges
(water hammer) that may occur, taking into account any surge protection
provided.
(D) Restraints. Piping
shall be blocked and otherwise restrained to prevent damaging movement under
the maximum anticipated pressure (including test pressure).
(E) Cleanouts. Cleanouts shall be provided in
pump suctions.
(iii)
Valves. Valves shall not be located in wetwells.
(A) Shutoff. Except on submersible pumps and
suction lift pumps, a shutoff valve shall be provided on the suction of all
pumps. A shutoff valve shall be provided on the discharge of all pumps,
regardless of type or service.
(B)
Check. All pumps shall be provided with a check valve located between the pump
and the discharge shutoff valve, except where arranged so that backflow is not
possible under normal operating conditions.
(C) Air release. Air release valves shall be
provided at the high points in piping whenever the pipe crown elevation falls
below the pipe invert elevation. On sewage lines, air or air and vacuum release
valves shall be specifically designed for sewage
service.
(e)
Reliability.
(i) Multiple units. Every
pumping station shall have not less than two (2) pumping units. The number of
units and their size shall be sufficient to permit pumping the maximum design
flow with the largest pumping unit out of service.
(ii) One of the following shall be provided:
(A) Alternative power source. Where the
pumping station serves more than fifty (50) residential units, alternative
power shall be provided. Alternative power shall be permanently installed or
portable engine generator sets, permanently installed or portable engine driven
pumps or a separate, independent utility source provided. Where manual starting
is required, sufficient storage shall be provided to allow notifying the
operator and performing whatever tasks are necessary to get the pumping station
in service. Where permanently installed engine driven equipment is provided,
sufficient fuel shall be provided for at least eight hours operation under the
maximum flow condition. Where more than one (1) pumping station is affected by
a power outage and portable equipment is planned for alternative power source,
sufficient portable equipment shall be provided to provide alternative power to
all pumping stations under maximum flow conditions.
(B) Generators. Generators shall be sized to
permit starting the largest pump in the pumping station with all other pumps
except one running. If the generator is not capable of starting all pumps
simultaneously, suitable controls shall be provided to stagger the pump starts
to remain within the capabilities of the equipment. Generators shall be
diesel-fired, natural gas-fired or bottled gas-fired. The use of gasoline or
digester gas-fired generators for permanently installed standby service is
unacceptable. Gasoline-fired portable generators are accept able.
(C) Engine driving pumps. Engine driven pumps
shall be sized for maximum design flow. Diesel, natural gas and bottled gas are
acceptable fuels for portable engines only. Digester gas is unacceptable for
standby fuel. Quick connecting couplings shall be provided for portable engine
driven pumps.
(D) Storage.
Wastewater storage may be provided in the form of underground storage or
surface ponds or tanks in lieu of alternative power supplies. Storage shall be
sized for the maximum anticipated power outage, but not less than twenty-four
(24) hours at average design flow. Storage shall be water tight and arranged to
drain back to the pumping station wetwell.
(f) Electrical.
(i) Equipment location. All electrical
equipment, including motors, motor starters and controls shall be located so as
to be undamaged by the 100-year flood.
(ii) Controls. Controls shall include a
separate start/stop device for each pump or for each pumping position in the
control sequence. Controls shall be arranged so that the failure of any one
control system component will affect only the operation of one pumping unit.
Manual override shall be provided for normal pump operating control.
(iii) Code requirements. All electrical work
shall comply with the National Electrical Code as adopted and amended by the
Wyoming Department of Fire Prevention and Electrical Safety. Electrical
equipment in enclosed wetwells, which may be subject to explosive concentration
of hazardous gases or flammable fluids, including all raw sewage wetwells,
shall comply with the NEC requirements for Class 1, Division 1, Groups C and D
areas.
(iv) Alarms. An alarm system
shall be provided for each pumping station. As a minimum, alarms shall include
high wetwell level and high water level in the dry well. For pumping stations
having a capacity of 0.5 mgd (1890 m3/d) or more,
the alarm shall be telemetered to a facility that is manned twenty-four (24)
hours a day. For pumping stations having a capacity of 0.5 mgd (1890
m3/d) or less, an audio and visual alarm shall be
provided in a conspicuous location.
(g) Safety.
(i) Ventilation. All accessible pumping
station areas shall be ventilated. Ventilation may be continuous or
intermittent. If intermittent, ventilation in areas normally visited by
operating personnel shall be started automatically at not greater than
30-minute intervals. Permanently installed dry well ventilation shall provide
at least six air changes per hour if continuous, and twelve (12) air changes
per hour if intermittent. Permanently installed wetwell ventilation shall
provide twelve (12) complete air changes per hour if continuous, and thirty
(30) complete air changes per hour if intermittent. Wetwell ventilation shall
be positive pressure, forcing air into the wetwell rather than exhaustion from
it. All ventilation equipment shall be of a non-sparking design. Intermittent
ventilating equipment shall insure starting upon entry of operating personnel.
Wetwells may be ventilated by gravity means if normal access by operating
personnel is unnecessary. Wetwells that are accessed infrequently shall be
designed to permit the use of portable blowers that will exhaust the space and
continue to supply fresh air during access periods.
(ii) Hoists. Where required for removing
equipment, hoists shall be rated for not less than 50 percent more than the
weight of the heaviest single item to be lifted by the hoist.
(iii) Lighting. Lighting levels shall be
sufficient to permit safe operation and maintenance of all equipment within the
pumping station, but not less than 30 foot-candles. All areas shall be lit in
such a manner that the failure of one lighting fixture or lamp will not cause
the area to be completely dark.
(iv) Equipment guards. Provide shields to
protect from rotating or moving machinery.
(v) Warning signs. Provide warning signs for
nonpotable water, electrical hazards, chemical hazards, or other unsafe
features. Warning signs shall be permanently attached to the structure or
appropriate equipment.
(vi) Safety.
Comply with the Wyoming Occupational Health and Safety Rules and
Regulations.