020-21 Wyo. Code R. §§ 21-13 - Monitoring
(a) Sampling. Representative samples of the
treated wastewater that is to be reused shall be collected and analyzed by the
person who prepares the wastewater.
(b) Methods. Waste constituents shall be
analyzed in accordance with 40 CFR Part 136, Guidelines Establishing Test
Procedures for the Analysis of Pollutants.
(c) Parameters. The treated wastewater shall
be analyzed for the following:
(i) Fecal
coliform;
(ii) Nitrate as
N;
(iii) Ammonia as N;
(iv) pH;
(v) Parameters identified in 40 CFR Part 122,
Appendix D, Table III, when required by the NPDES permit; and
(vi) Other parameters identified in the
permit.
(d) Frequency
for monitoring for these pollutants shall be:
(i) For lagoon systems, once per month or the
frequency specified in the NPDES discharge permit whichever is more
frequent;
(ii) For mechanical
plants, once per week or the monitoring frequency specified in the NPDES
discharge permit whichever is more frequent; and
(iii) For monitoring of parameters identified
in Section
13(c)
(v), shall be conducted at the frequency
specified in the NPDES discharge permit.