048-5 Wyo. Code R. §§ 5-8 - Physical Environment
(a) The ambulatory
surgical center shall be constructed, arranged, and maintained to ensure health
and safety of the patient.
(i) The building
interior and exterior shall be clean, orderly, sanitary, and free of
odors.
(b) Ambulatory
surgical centers, certified prior to the effective date of these regulations
and were lawfully constructed and in compliance with the regulations at the
time of initial certification and found to be in continuing compliance during
any subsequent surveys may continue to utilize existing, approved life safety
systems provided that they present no hazard to life, health, or property and
that there are no changes in the scope of services and utilization patterns in
the ambulatory surgical center.
(i) Any
renovations of the certified ambulatory surgical centers shall, after the
effective date of these regulations, comply with the requirements as outlined
in Section
9.
(c) All new ambulatory
surgical centers shall meet the 1994 edition of the Life Safety Code of the
National Fire Protection Association that is applicable to health care
facilities.
(d) Medical gas and
vacuum piped systems shall not be shared with non-licensed health care
facilities.
(e) The critical branch
of the emergency system powered by the generator shall not be shared with
non-licensed health care facilities.
(f) The ventilation system shall not be share
with non-licensed health care facilities.