049-9 Wyo. Code R. §§ 9-5 - Exits
The building or fire official, in accordance with the adopted building and fire codes, shall determine number of exits, placement and adequacy. General requirements are:
(a) A minimum of two (2) exits;
(i) A second exit may consist of a sliding
glass patio door with approved landing, guardrails and handrails.
(ii) Windows and garages shall not be
considered as an exit for this purpose;
(iii) An exit door is a side-hinged door and
shall be at least 32" of clear width by 80" in height in new construction or as
approved by the authority having jurisdiction in existing
construction.
(b)
Required exit access, exits or exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire
or other emergency.
(c) An exit
shall be free from obstructions that would prevent its use, including the
accumulation of snow and ice.
(d)
Egress doors shall be readily openable from the inside without the use of a key
or any special knowledge or effort, the door knob system shall be an "emergency
exit feature type, no unlocking required". Use of dead bolts, chains, night
latches, manually operated flush bolts or surface bolts are not permitted
during child care hours.
(e) The
means of egress, including the exit discharge, shall be illuminated at all
times the building is occupied.
(f)
Porches, steps, stairs, landings and walkways shall be maintained in good
repair and safe condition, and in compliance with the adopted code or as
approved by the authority having jurisdiction.
(g) Guardrails shall be located along
open-sided walking surfaces, mezzanines, stairways, ramps and landings and
along glazed sides of stairways, ramps and landings which are located more than
thirty (30) inches above the floor or grade below.
(h) Guardrails shall form a protective
barrier not less than forty-two (42) inches high.
(i) Open guardrails shall have intermediate
rails or balusters or ornamental patterns such that a three and a half (3 1/2)
inch diameter sphere cannot pass through any opening.
(j) Landings shall have a width not less than
the width of the stairway or the width of the door, whichever is the greater.
Landings shall have a length measured in the direction of travel of not less
than thirty-six (36) inches.
(k)
Basements must have two (2) approved exits with one leading directly to the
outside.