In order to prevent releases due to structural failure,
corrosion, or spills and overfills for as long as the UST system is used to
store regulated substances, all owners and/or operators of UST systems shall
meet the requirements in this Section. In addition, all tanks and piping
installed or replaced after December 1, 2005, shall be secondarily contained
and use interstitial monitoring in accordance with Part D Section 16(f).
Secondary containment shall be able to contain regulated substances leaked from
the primary containment until they are detected and removed and prevent the
release of regulated substances to the environment at any time during the
operational life of the tank system. Where the piping is considered to be
replaced, the entire piping run shall be secondarily contained.
(a)
Tanks. Tanks shall be
properly designed, constructed, and installed. Underground components that
routinely contain regulated substances shall be protected from corrosion in
accordance with a code of practice developed by a nationally recognized
association or independent testing laboratory as specified below:
(i) Fiberglass-reinforced plastic tanks shall
be manufactured and installed in accordance with UL Standard 1316 or UL of
Canada S615, both as referenced in Section 2.
(ii) Steel USTs shall be cathodically
protected or isolated from ground contact and manufactured and installed to
meet the following requirements:
(A) The
outside surface of all steel tanks installed after the date of these
regulations shall be coated with a suitable dielectric material;
(B) Field-installed CP systems shall be
designed by a corrosion expert;
(C)
Impressed current CP systems shall be designed to allow determination of
current operating status as required in Section 11, including a voltage meter,
an amperage meter, and an hour meter showing the hours that the rectifier
actually operated; and
(D) CP
systems shall be operated and maintained in accordance with Section 11. Once
installed, CP systems shall not be removed as long as the steel UST system
exists.
(E) In addition to the
above requirements, all cathodically protected steel USTs shall be manufactured
and installed in accordance with one or more of the following industry
standards or practices:
(I) STI-P3®
Specification and Manual for External Corrosion Protection of Underground Steel
Storage Tanks, as referenced in Section 2; or
(II) UL Standard 1746, as referenced in
Section 2; or
(III) UL of Canada
S603, S603.1, and S631, all three as referenced in Section 2; or
(IV) NACE Standard SP0285 and UL Standard 58,
both as referenced in Section 2; or
(V) STI Standard F841, as referenced in
Section 2.
(iii) Tanks constructed of steel and clad or
jacketed with a non-corrodible material shall be manufactured and installed in
accordance with one or more of the following industry standards or practices:
(A) UL Standard 1746, as referenced in
Section 2; or
(B) STI
ACT-100-U® Specification F894, as referenced in Section 2; or
(C) STI ACT-100-U® Specification F961, as
referenced in Section 2; or
(D) STI
Specification F922, as referenced in Section 2.
(iv) Owners and/or operators may continue to
operate tanks upgraded with an internal lining as long as CP is in place that
meets all requirements of this Chapter.
(v) New steel tanks shall not be installed
with a liner without the addition of CP. No existing steel tank with a liner
and added CP shall be modified to remove the CP.
(vi) After the effective date of these
regulations, no UST may be installed for any purpose regulated under this
Chapter with any penetration into the UST except in the top.
(vii) All USTs installed after the effective
date of these regulations shall be anchored using deadmen to prevent flotation.
No tank shall be installed without providing for the maximum possible buoyancy
force assuming that the tank is completely under the local groundwater table.
No tank shall be installed using a concrete slab above the tank as the primary
method of resisting buoyancy forces.
(b)
Piping. Piping that
routinely contains regulated substances and is in contact with the ground shall
be properly designed, constructed, installed, and protected from corrosion in
accordance with the following applicable industry standards or practices:
(i) Piping constructed of a non-corrodible
material shall be manufactured and installed in accordance with UL Standard 971
or UL of Canada S660, both as referenced in Section 2.
(ii) Steel piping shall be cathodically
protected in the following manner:
(A) The
piping shall be coated with a suitable dielectric material;
(B) Field-installed CP systems shall be
designed by a corrosion expert;
(C)
Impressed current CP systems shall be designed to allow determination of
current operating status as required in Section 11; and
(D) CP systems shall be operated and
maintained in accordance with Section 11.
(E) In addition to the above, cathodically
protected steel pipe shall be manufactured and installed in accordance with one
or more of the following industry standards or practices:
(I) UL Subject 971A, as referenced in Section
2;
(II) STI Recommended Practice
R892, as referenced in Section 2;
(III) NACE International Standard Practice
SP0169, as referenced in Section 2; or
(IV) NACE International Standard Practice
SP0285, as referenced in Section 2.
(iii) Other piping systems will be allowed if
they are determined by the department, pursuant to Section 33, to be designed
to prevent the release of any regulated substance in a manner that is no less
protective than the requirements in Section 6(b).
(c)
Spill and Overfill Prevention
Equipment.
(i) Except as provided in
Sections 6(c)(ii) and 6(c)(iii), to prevent spilling and overfilling associated
with regulated substance transfer to the UST system, owners and/or operators
shall use the following spill and overfill prevention equipment:
(A) Spill prevention equipment that will
prevent release of regulated substances to the environment when the transfer
hose is detached from the fill pipe; and
(B) Overfill prevention equipment that will:
(I) Automatically shut off flow into the tank
when the tank is no more than 95% full; or
(II) Alert the transfer operator when the
tank is no more than 90% full by restricting the flow into the tank or
triggering a high-level alarm. The high-level alarm shall be audible and
visible to the transfer operator; or
(III) Restrict flow 30 minutes prior to
overfilling, alert the transfer operator with a high-level alarm (audible and
visible to the transfer operator) 1 minute before overfilling, or automatically
shut off flow into the tank so that none of the fittings located on top of the
tank are exposed to product due to overfilling.
(ii) Owners and/or operators are not required
to use the spill and overfill prevention equipment specified in Section 6(c)(i)
if the UST system is filled by transfers of no more than 25 gallons at one
time.
(iii) Flow restrictors (ball
valves) used in vent lines may not be used to comply with Section 6(c)(i)(B)
when overfill prevention is installed or replaced after April 11, 2016. Flow
restrictors may continue to be used for reasons other than meeting the overfill
prevention requirement so long as the flow restrictor does not interfere with
the operation of the overfill prevention equipment being used.
(iv) Spill and overfill prevention equipment
shall be periodically tested or inspected in accordance with Section
10(d).
(d)
Installation. The tank system shall be properly installed in
accordance with one of the following industry standards or practices (as long
as the standard or practice does not conflict with the manufacturer's
instructions and recommendations) and in accordance with the manufacturer's
instructions and recommendations:
(i) API
Publication 1615, as referenced in Section 2; or
(ii) PEI RP100, as referenced in Section 2;
or
(iii) NFPA Standard 30 and
Standard 30A, both as referenced in Section 2.
(e)
Installation
Certification. No storage tank system shall be operated until the
department determines the installation or substantial modification meets the
applicable standards of this Part. The department shall not issue any such
determination until all construction on the site of the storage tank system is
complete. Owners and/or operators shall:
(i)
Notify the department by telephone or in writing at least 30 days prior to the
installation, repair or substantial modification of any storage tank system.
Installations, repairs, or substantial modifications shall be scheduled at
mutually acceptable times so the department can ensure a representative is on
site at various phases of installation or substantial modification. Inspections
shall be completed within 10 days of the date the department is notified that
the installation, repair or substantial modification is complete; and
(ii) Pay the department a fee for each
storage tank system or multiple storage tank systems installed, repaired or
substantially modified at the same time and at the same site pursuant to
W.S.
35-11-1420(c). The
department will invoice the owner and/or operator upon completion of the final
installation, repair or substantial modification inspection. The owner and/or
operator shall remit payment to the department within 30 days of receipt of the
department's invoice; and
(iii)
Ensure that the installation, repair, or substantial modification of all USTs
meets the performance standards of this Chapter; and
(iv) Obtain a certification from the licensed
installer certifying that the tank system was installed or modified to meet the
requirements of this Chapter. Such certification shall be provided on the UST
notification form required under Section 9; and
(v) In the case of an emergency where the
owner and/or operator cannot comply with the notification requirement of
Section 6(e)(i), notify the department by telephone as soon as the emergency is
found. Before proceeding with any substantial modification or installation:
(A) The department shall determine if an
inspection can be made within the owner and/or operator's work schedule;
or
(B) If the department cannot
make the inspection, the owner and/or operator shall provide by mail, the
specifications of materials and industry standards or practices used to
accomplish the installation or substantial modification and documentation of
any tests required within 5 days of completion.
(f)
Compatibility. In
accordance with Section 12, owners and/or operators shall demonstrate that all
components of a new UST system are compatible with the substance to be stored
in the UST system.
(g)
Dispenser Systems. Any new dispenser system installed after
April 11, 2016, shall be equipped with under-dispenser containment.
(i) A dispenser system is considered new when
both the dispenser and the equipment needed to connect the dispenser to the
storage tank system are installed. The equipment necessary to connect the
dispenser to the tank system includes check valves, shear valves, unburied
risers or flexible connectors, or other transitional components that are
underneath the dispenser and connect the dispenser to the underground piping.
Sensors are not required for monitoring under-dispenser containment. However,
sensors may need to be added to meet the periodic monitoring requirement for
sumps that cannot be visually inspected or to meet the piping interstitial
monitoring requirement.
(ii)
Under-dispenser containment shall be liquid-tight on its sides, bottom, and at
all penetrations. Under-dispenser containment shall allow for visual inspection
and access to the components in the containment system or be periodically
monitored for leaks from the dispenser system.
(h) Owners and/or operators shall install a
UST system listed in Section 4(b)(i), (iii), or (iv) storing regulated
substances (whether single- or double-wall construction) that meets the
following:
(i) Will prevent releases due to
corrosion or structural failure for the operational life of the UST
system;
(ii) Is cathodically
protected against corrosion, constructed of non-corrodible material, steel clad
with a non-corrodible material, or designed in a manner to prevent the release
or threatened release of any stored substance; and
(iii) Is constructed or lined with material
that is compatible with the stored substance.