020-1 Wyo. Code R. §§ 1-8 - Repairs Allowed
(a) Owners and/or
operators of storage tank systems shall ensure that repairs will prevent
releases due to structural failure or corrosion as long as the storage tank
system is used to store regulated substances. The repairs shall meet the
following requirements:
(i) Repairs to UST
systems shall be properly conducted in accordance with one or more of the
following industry standards or practices:
(A)
NFPA Standard 30, as referenced in Section 2;
(B) API Recommended Practice 2200, as
referenced in Section 2;
(C) API
Standard 1631, as referenced in Section 2;
(D) NFPA Standard 326, as referenced in
Section 2;
(E) National Leak
Prevention Association Standard 631, as referenced in Section 2;
(F) STI Recommended Practice R972, as
referenced in Section 2;
(G) NACE
International Standard Practice SP0285, as referenced in Section 2;
or
(H) Fiberglass Tank and Pipe
Institute Recommended Practice T-95-02, as referenced in Section 2.
(ii) Repairs to aboveground
storage tank systems shall be properly conducted in accordance with one or more
of the following industry standards or practices:
(A) NFPA Standard 30, as referenced in
Section 2;
(B) API Standard 620, as
referenced in Section 2;
(C) API
Standard 650, as referenced in Section 2;
(D) API Standard 653, as referenced in
Section 2; or
(E) PEI RP200, as
referenced in Section 2.
(iii) Repairs to fiberglass-reinforced
plastic USTs may be made by the manufacturer's authorized representatives or in
accordance with a code of practice developed by a nationally recognized
association or an independent testing laboratory.
(iv) Metal pipe sections and fittings that
have released regulated substances as a result of corrosion or other damage
shall be replaced. Non-corrodible pipes and fittings may be repaired in
accordance with the manufacturer's specifications.
(v) Repairs to secondary containment areas of
tanks and piping used for interstitial monitoring and to containment sumps used
for interstitial monitoring of piping shall have the secondary containment
tested for tightness according to the manufacturer's instructions or a code of
practice developed by a nationally recognized association or independent
testing laboratory within 30 days following the date of completion of the
repair. All other repairs to storage tank systems shall be tightness tested in
accordance with Sections 14(g) and 16(b) within 30 days following the date of
the completion of the repair unless:
(A) The
repaired storage tank system is internally inspected in accordance with a code
of practice listed in this Section; or
(B) The repaired portion of any UST system is
monitored monthly for releases in accordance with a method specified in Section
16(c) through (j); or
(C) Another
test method is used that is determined by the department, pursuant to Section
33, to be no less protective of human health and the environment than those
listed above.
(D) The following
codes of practice may be used to comply with paragraph (a)(v) of this Section:
(I) STI Recommended Practice R012, as
referenced in Section 2; or
(II)
Fiberglass Tank and Pipe Institute Recommended Practice 2007-2, as referenced
in Section 2.
(III) PEI RP1200, as
referenced in Section 2.
(vi) Storage tank system owners and/or
operators shall maintain records of each repair until the UST system is
permanently closed or undergoes a change-in-service pursuant to Part G of this
Chapter.
(b) All owners
and/or operators of repaired UST systems shall ensure the modifications meet
the performance standards for design and repair as set forth in Section
6.
(c) Costs associated with
remediation of any release from a storage tank system during tank installation
or repair work by a tank installer, tester, owner and/or operator, etc., are
not eligible for the state's corrective action account funds.
(d) Any time steel connected piping is
repaired or modified by replacing the pipe with a non-corrodible pipe, all of
the connected piping on that run shall be replaced. Any time steel piping that
is not cathodically protected is repaired or replaced, the entire run of pipe
shall be replaced with a non-corrodible pipe.
(e) Whenever the integrity of the primary or
secondary wall of a double-wall tank has been compromised, repairs shall be
made immediately in accordance with the tank manufacturer's recommendations. If
the tank cannot be repaired, it shall be permanently closed in accordance with
Section 31.
(f) Within 30 days
following any repair to spill or overfill prevention equipment, the repaired
spill or overfill prevention equipment shall be tested or inspected, as
appropriate, in accordance with Section 10(d) to ensure it is operating
properly.
(g) Testing required
under this Section shall be conducted by a licensed installer as defined in
Section 45 or a licensed tester as defined in Section 48.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.