020-1 Wyo. Code R. § 1-15 - Petroleum USTs with a Capacity of 2,000 Gallons or Less
Tanks installed on or after December 1, 2005, shall be double-wall systems and interstitially monitored. Tanks installed on or before November 30, 2005, shall be monitored for releases at least every 30 days using one of the methods listed in Section 16. Tanks with a capacity of 550 gallons or less and tanks with a capacity of 551 to 1,000 gallons that meet the tank diameter criteria in Table 1 may use manual tank gauging as the sole method of release detection in accordance with Section 15(a). All other tanks with a nominal capacity of 551 to 2,000 gallons may use manual tank gauging in place of inventory control.
TABLE 1 MANUAL TANK GAUGING VARIATION STANDARDS | ||||
Nominal Tank Capacity | Weekly Standard (one test) | Monthly Standard (average of four tests) | Minimum Test Duration Hours* | |
550 gallons or less | 10 gallons | 5 gallons | 36 | |
551-1,000 gallons (when the tank diameter is 64") | 9 gallons | 4 gallons | 44 | |
551-1,000 gallons (when the tank diameter is 48") | 12 gallons | 6 gallons | 58 | |
551-1,000 gallons | 13 gallons | 7 gallons | 36 | |
1,001-2,000 gallons | 26 gallons | 13 gallons | 36 |
* Nothing can be added to or removed from the UST for the duration of the test.