020-1 Wyo. Code R. § 1-17 - Hazardous Substance UST Systems
Owners and/or operators of hazardous substance UST systems shall provide containment that meets the following requirements and monitor these systems every 30 days using Section 16(f):
(a)
Release Detection.
Hazardous substance UST systems shall have a secondary containment system, be
constructed with double-wall tanks, or be constructed with an external liner or
vault surrounding the entire tank system. These systems shall meet the
following requirements:
(i) Secondary
containment systems shall:
(A) Be designed,
constructed, and installed to contain regulated substances leaked from the
primary containment until those substances are detected and removed;
(B) Be designed, constructed, and installed
to prevent the release of regulated substances to the environment at any time
during the operational life of the UST system; and
(C) Be inspected for evidence of a release at
least once every 30 days.
(ii) Double-wall tanks shall:
(A) Be designed, constructed, and installed
to contain a leak from any portion of the inner tank within the outer
wall;
(B) Be designed, constructed,
and installed to detect the failure of the inner wall; and
(C) Be inspected for evidence of a release at
least once every 30 days.
(iii) External liners (including vaults)
shall:
(A) Be designed, constructed, and
installed to contain 100% of the capacity of the largest tank within its
boundary;
(B) Be designed,
constructed, and installed to prevent the interference of precipitation or
groundwater intrusion with the ability to contain or detect a release of
regulated substances;
(C) Be
designed, constructed, and installed to surround the tank completely (i.e.,
capable of preventing lateral and vertical migration of regulated substances);
and
(D) Be inspected for evidence
of a release at least once every 30 days.
(b)
Connected Piping.
Connected piping shall be equipped with secondary containment that satisfies
the requirements of this Section. Trench liners and double-wall pipe are
examples of secondary containment systems. Connected piping that conveys
regulated substances under pressure shall be equipped with an automatic line
leak detector in accordance with Section 14(g)(i).
(c)
Other Methods. Other
methods of release detection may be used for hazardous substance UST systems
installed on or before October 13, 2015, if owners and/or operators:
(i) Demonstrate to the department that an
alternate method can detect a release of the stored regulated substance as
effectively as any of the methods allowed in Section 16(b) through (h) can
detect a release of petroleum;
(ii)
Provide information to the department on effective corrective action
technologies, health risks, and chemical and physical properties of the stored
substance, and the characteristics of the UST site; and
(iii) Obtain authorization from the
department to use the alternate release detection method before the
installation and operation of the new or modified UST system.