Wyoming Design and
Construction Minimum Standards for Healthcare Facilities.
(iv)
Requirements in addition to the "Guidelines for Design and Construction of
Health Care Facilities - 2006 Edition" are as follows:
(A) In hospitals and nursing care facilities,
the laundry shall have a soiled linen holding room equipped with handwashing
facilities and a sink for soaking soiled items.
(B) In ambulatory surgical centers, birthing
centers, hospices providing inpatient care, hospitals, and nursing care
facilities, continuous mechanical exhaust ventilation shall be provided in all
bathing rooms, toilet rooms, and soiled and wet areas.
(C) In hospitals and nursing care facilities,
nurse call systems and equipment shall be tested against the provisions of IHS
UL Standard 1069.
(D) In ambulatory
surgical centers, birthing centers, hospices providing inpatient care,
hospitals, and nursing care facilities, the air ducts that penetrate floors
shall be provided with fire-rated dampers which are activated by smoke and
heat.
(E) In ambulatory surgical
centers, birthing centers, freestanding diagnostic testing centers, hospices
providing inpatient care, hospitals, medical assistance facilities, nursing
care facilities, rehabilitation facilities, and renal dialysis centers, all
sinks shall be provided with spray heads or equivalent. Aerators shall not be
used.
(F) In ambulatory surgical
centers, birthing centers, freestanding diagnostic testing centers, hospices
providing inpatient care, hospitals, medical assistance facilities, nursing
care facilities, rehabilitation facilities, and renal dialysis centers, all
handwash sinks shall have faucets which discharge at least five (5) inches
above the spill level of the sink. Soap dispensers and hand drying apparatus
shall be provided at each handwash sink.
(G) In nursing care facilities, bathing
facilities shall include one (1) circulating type fixture for each nurses'
station.
(H) In nursing care
facilities, each resident shall have within his or her bedroom, minimum storage
space to include a wardrobe, locker or closet, separated from other
resident-shared spaces by a solid divider with a minimum dimension of 2' 4" x
1' 8", with a shelf and rod to permit hanging of full-length garments. In
addition, a built-in or freestanding drawer unit which contains at least three
(3) drawers, with a minimum inside drawer width of
24", shall be provided for each resident. Nightstand furniture is not
considered storage space.
(I)
Engineering Services and Equipment.
(I) In
ambulatory surgical centers, birthing centers, freestanding diagnostic testing
centers, hospices providing inpatient care, hospitals, medical assistance
facilities, nursing care facilities, rehabilitation facilities, and renal
dialysis centers, the boiler room or other rooms containing storage of
combustible material shall not contain ventilation equipment, the main
electrical switch board, or emergency electrical equipment.
(II) In ambulatory surgical centers, birthing
centers, freestanding diagnostic testing centers, hospices providing inpatient
care, hospitals, medical assistance facilities, nursing care facilities,
rehabilitation facilities, and renal dialysis centers, building water system
designs shall be in accordance with "Guideline 12-2000 - Minimizing the Risk of
Legionellosis Associated with Building Water Systems," published by the
American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE).
(III) In ambulatory
surgical centers, birthing centers, freestanding diagnostic testing centers,
hospices providing inpatient care, hospitals, medical assistance facilities,
nursing care facilities, rehabilitation facilities, and renal dialysis centers,
all electrical receptacles located adjacent to sinks or other potentially wet
areas shall be provided with ground fault circuit interrupter
protection.
(IV) In ambulatory
surgical centers, birthing centers, hospitals, medical assistance facilities,
and nursing care facilities, a standby electrical generator shall be installed
in all facilities to provide emergency lighting and power per the 2008 Edition
of "NFPA 70: National Electrical Code," the 2005 Edition of "NFPA 99: Standard
for Health Care Facilities," and the 2005 Edition of "NFPA 110: Standard for
Emergency and Standby Power Systems."
(V) In ambulatory surgical centers, birthing
centers, freestanding diagnostic testing centers, hospices providing inpatient
care, hospitals, medical assistance facilities, nursing care facilities,
rehabilitation facilities, and renal dialysis centers, exposed light bulb
fixtures and heat lamps shall not be allowed. Globes, guards, lenses, and
speciality coated bulbs shall be provided.
(VI) In ambulatory surgical centers, birthing
centers, hospitals, medical assistance facilities, and nursing care facilities,
supply and return air systems for patient and resident care areas shall be
within a duct. Common returns using corridor, ceiling cavities, and attic
spaces as return plenums are prohibited.
(1.)
Exception: Remodeling of existing buildings where the remodeling causes no
change of space use that previously existed and where the ventilation of the
existing building complies with Section
7(b) of these
Rules.
(VII) In assisted
living facilities where there are sleeping accommodations for more than sixteen
(16) residents, the automatic sprinkler system shall be installed in accordance
with "NFPA 13: Standard for the Installation of Sprinkler Systems."