Ala. Admin. Code r. 535-X-11-.10 - Electrical Plan Drawing Requirements
The electrical plans submitted pursuant to Rule 535-X-11-.07 of this chapter must:
(a) Provide plan
and detail of service equipment, including service entrance, conductors,
service raceway and clearances above ground and above structures.
(b) Indicate method and detail for ground
service equipment.
(c) Provide a
single line diagram of the entire electrical installation.
(d) Provide complete load calculations for
service and feeders.
(e) Identify
and show sizes of all feeders and branch circuits.
(f) Show size, rating, and location of main
disconnect/over-current protective devices.
(g) Detail method of interconnection between
modules or units and location of connections.
(h) Show location of all outlets and junction
boxes.
(i) Indicate how
nonmetallic-sheathed cable in locations subject to mechanical damage is to be
protected.
(j) Indicate method of
backing mounting and stapling of fixtures and wiring.
(k) Provide details showing mounting of
nontypical fixtures, if any.
(l)
Provide name plate rating of all appliances and equipment.
(m) Indicate method of testing.
(n) Indicate that all wiring, fixtures, and
equipment are listed or labeled.