Cal. Code Regs. Tit. 19, § 573 - Fire Extinguisher Size and Placement for Commercial Cooking Operations
(a)
Fire extinguishers with a Class K rating shall be provided for hazards where
there is a potential for fires involving combustible cooking media (vegetable
or animal oils and fats).
(b)
Maximum travel distance shall not exceed 30 ft (9.15m) from the hazard to the
extinguishers.
(c) Additional fire
extinguishers, required for the control of other classes of fires, shall be
provided for commercial cooking areas as required by Section
567.
(d) A placard shall be conspicuously placed
near the extinguisher that states that the fire protection system shall be
activated prior to using the fire extinguisher.
(e) All solid fuel appliances with fire boxes
of 5 ft3 (0.14 m3) volume
or less shall have at least one 1.6 gal (6 L) wet chemical fire extinguisher
listed for Class K fires in the immediate vicinity of the appliance.
Notes
2. Amendment of section heading and new subsection (c) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9).
3. New subsections (d)-(e) filed 7-17-2013; operative 10-1-2013 (Register 2013, No. 29).
Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
2. Amendment of section heading and new subsection (c) filed 2-28-2007; operative 3-30-2007 (Register 2007, No. 9).
3. New subsections (d)-(e) filed 7-17-2013; operative 10-1-2013 (Register 2013, No. 29).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.