(1) Distribution box - where distribution
boxes are used for distributing sewage from the septic tank or other onsite
sewage tank to the drainfield lines, the following requirements must be adhered
to:
(a) Distribution boxes must be watertight,
constructed of durable materials, have adequate structural strength, and be of
sufficient size to accommodate the required number of drainfield
lines.
(b) Each drainfield line
must be connected individually to the box.
(c) The invert of inlets to the box must be
at least 1'' inch above the invert of the outlets. The invert of all outlets
must be level with respect to each other.
(d) The distribution box must be built as a
separate unit from the septic tank and must be set level on solid ground or in
mineral aggregate.
(2)
Header pipe - header pipe, when used, must be installed in compliance with the
following requirements:
(a) Header pipe must
meet one or more of the following requirements:
1. ASTM D-3034-21, Standard Specification for
Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings (2021), herein
adopted and incorporated by reference. This standard has been deemed copyright
protected and is available from the publisher at ASTM International, P.O. Box
C700, West Conshohocken, Pennsylvania 19428-2959, or at publisher's website at
www.astm.org/, and is available for
inspection as provided in subsection (6) below.
2. ASTM D-2729-21 Standard Specification for
Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings (2021), herein adopted and
incorporated by reference. This standard has been deemed copyright protected
and is available from the publisher at ASTM International, P.O. Box C700, West
Conshohocken, Pennsylvania 19428-2959, or at publisher's website at
www.astm.org/, and is available for
inspection as provided in subsection (6) below.
3. AASHTO M252-18 Standard Specification for
Corrugated Polyethylene Drainage Pipe (2018), herein adopted and incorporated
by reference. This standard has been deemed copyright protected and is
available from the publisher at American Association of State Highway and
Transportation Officials, 444 North Capitol Street N.W., Suite 249, Washington
D.C. 20001, and is available for inspection as provided in subsection (6)
below.
4. ASTM F-667/667M-16R21,
Standard Specification for 3 through 24 in. Corrugated Polyethylene Pipe and
Fittings (2021), herein adopted and incorporated by reference. This standard
has been deemed copyright protected and is available from the publisher at ASTM
International, P.O. Box C700, West Conshohocken, Pennsylvania 19428-2959, or at
publisher's website at
www.astm.org/, and is
available for inspection as provided in subsection (6) below.
5. ASTM F-810-12R18, Standard Specification
for Smoothwall Polyethylene (PE) Pipe for Use in Drainage and Waste Disposal
Absorption Fields (2018), herein adopted and incorporated by reference. This
standard has been deemed copyright protected and is available from the
publisher at ASTM International, P.O. Box C700, West Conshohocken, Pennsylvania
19428-2959, or at publisher's website at
www.astm.org/, and is available for inspection as
provided in subsection (6) below.
(b) Corrugated or smooth wall fittings
(elbows, tees and crosses) shall be acceptable for gravity flow headers. Header
pipe interior must be smooth. Header pipe must have a minimum inside diameter
of 4'' inches for gravity flow applications. Header pipe must not be
perforated.
(c) The header pipe
must be laid level with direct, connections to each drainfield line and the
septic tank outlet pipe. When installed in a drainfield which uses mineral
aggregate, the header pipe must be encased in mineral aggregate, and must be
included as part of the drainfield area. Gravity flow header pipes, when
installed within the mineral aggregate drainfield, may be non-watertight but
must be soil tight. Snap connections are acceptable. On non-mineral aggregate
systems, header pipe must be supported by soil. All connections must be such
that all joints or fittings are firmly connected to pipes. When a drainfield
system is a pumped system, the header pipe and fittings must be smooth-walled
and watertight. Where the header pipe is not within the absorption surface area
it must not be included in drainfield size calculations, but must be considered
part of the system. The header pipe must be designed to distribute effluent as
equally as practical to each individual drain line and must be supported so
that the header is laid level.
(d)
Pipe which connects the septic tank outlet to the header pipe or a distribution
box must comply with the strength and material standards for header pipe as
specified in this subsection.
(3) Low-Pressure dosing - where the total
required area of drainfield is greater than 1, 000 square feet or where the
applicant proposes to use low-pressure dosing, an automatic dosing device
discharging into a low pressure distribution network consisting of 2'' inch or
smaller diameter schedule 40 PVC or equal pipe with 1/2'' inch or smaller
diameter drilled holes must be used. All piping must use solvent welded
connections or equal throughout to prevent dislocation of connections under
pressure. The network must be designed for equal distribution of effluent. For
the purposes of this section, equal distribution means that the flow from the
least effective hole in the network must deliver no less than 75% of the flow
from the most effective hole. The selected pump capacity (as measured in
Gallons Per Minute) versus total dynamic head must be indicated on a pump curve
and must be shown by calculation to achieve an effluent velocity through the
network of at least 2' ft. per second to the first exit hole on each lateral.
Each line of the pressure network must individually connect to a pressure
manifold and be sealed on their distal ends and must not be looped with other
lines regardless of whether the drainfield is a bed or a trench or whether it
is in a mound, filled subsurface installation. Plans and equipment
specifications for low-pressure dosing systems must be approved by the
Department prior to construction or installation.
(a) Where the total drainfield area is
greater than 1, 000' square feet but not more than 2, 000' square feet, the
applicant may, in lieu of low-pressure dosing, choose to split the drainfield
into two drainfields, equal in size, each having no more than 1, 000' square
feet, with each drainfield being lift-dosed alternately.
(b) Dosing systems with 2, 000' square feet
of drainfield or less must consist of a pump tank that receives the flow from a
septic tank or other onsite sewage tank. Two pumps must be required for
commercial use where dosing is required due to drainfield size or where gravity
flow into the drainfield is not possible, and estimated establishment sewage
flows exceed 500 gallons per day. Where more than one pump is used, the pumps
must dose alternately. Where dosing is required for a commercial system for
flows of 500 gallons or less per day, only one pump is required if the
drainfield does not exceed 2, 000' square feet.
(c) Systems having more than 2, 000' square
feet of drainfield must have a minimum of two dosing pumps, with each pump
serving a proportionate amount of the total required absorption area. The pumps
must dose alternately.
(d) The
volume dosed between the pump operating levels must be adequate to assure that
the entire drain pipe network is filled at least four times each
cycle.
(e) When a drainfield is
installed in slightly limited soil, operating levels must be adjusted to dose
the drainfield a maximum of six times in a 24 hour period. For moderately
limited soils the drainfield must be dosed no more than four times in a 24 hour
period. More frequent dosing may be allowed with systems designed by engineers
licensed in the state of Florida.
(f) The distribution network for drainfields
having an absorption area less than 1, 500' square feet must be designed by a
Florida licensed professional engineer or a master septic tank contractor. The
network for drainfields having an absorption area of 1, 500' square feet or
larger must be designed by a Florida licensed professional engineer.
(g) Drip emitter systems must be designed in
accordance with subsection
62-6.009(5),
F.A.C.
(4) Lift dosing -
Where a septic tank or sewage waste receptacle is placed too low to permit
gravity flow into a properly designed, constructed and located drainfield, a
pump tank with a pump or similar type device must be used to lift the effluent
to a properly constructed header pipe or distribution box for effluent
distribution by gravity to the drainfield. This provision must apply only to
drainfields of 1, 000 square feet or less of total absorption area. Tank size
and pumps with effluent level controls and alarms must be set in accordance
with the requirements set forth in subsection
62-6.013(9),
F.A.C.
(5) Drain trenches and
absorption beds - drain trenches and absorption beds are the standard
subsurface drainfield systems used for disposing of effluent from septic tanks
or other sewage tanks. When used, these systems must be constructed as
specified below.
(a) When utilizing the
standard drain trench method, the width of the trench at the bottom must not
exceed 36'' inches. For trenches of 12'' inches or less, there must be a
minimum separation distance of 12'' inches between the sidewalls of adjacent
trenches; trenches greater than 12 inches require a minimum 24'' inch
separation between the sidewalls of adjacent trenches.
(b) The trench method must be the preferred
method. Absorption beds may be used in lieu of the standard drain trench
method. An absorption bed consists of an area in which the entire earth content
of the required absorption area is removed and replaced with aggregate and
distribution pipe or other approved alternative drainfield components. The
distance between the centers of distribution lines in standard beds must be a
maximum of 36'' inches. The distance between the sidewall of the bed and the
center of the outside drain line must be no more than 18 inches, but must not
be less than six inches. Where header pipe is used in lieu of a distribution
box, the header must extend to within 18 inches of the bed sidewalls. In no
case must the bottom surface of an absorption bed exceed a total of 1, 500'
square feet. Where two or more beds are used to obtain the necessary absorption
area, there must be a minimum 10 foot separation between the sidewalls of
adjacent absorption beds. Absorption beds must be designed to achieve the
maximum length to width ratio practical.
(c) When installing a drainfield system that
uses mineral aggregate, all portions of the header pipe and perforated drain
pipe must be installed in aggregate conforming to ASTM C33/C33M-18, Standard
Specification for Concrete Aggregates (2018) or lightweight aggregate
conforming to ASTM C330/C330M-17a Standard Specification for Lightweight
Aggregates for Structural Concrete (2017), herein adopted and incorporated by
reference. These standards have been deemed copyright protected and are
available from the publisher at ASTM International, P.O. Box C700, West
Conshohocken, Pennsylvania 19428-2959, or at publisher's website at
www.astm.org/, and are available for
inspection as provided in subsection (6) below. Aggregate must meet State of
Florida Department of Transportation (FDOT) specifications under Section 901,
"Standard Specifications for Road and Bridge Construction, January 2019" herein
adopted and incorporated by reference. Copies of this document are available as
provided in subsection (6) below and at
http://www.flrules.org/Gateway/reference.asp?No=Ref-14369.
Aggregate must also meet the following gradation requirements.
|
Sieve size
|
2 IN.
|
1 1/2 IN.
|
1 IN.
|
3/4 IN.
|
1/2 IN.
|
3/8 IN.
|
No. 4
|
|
Percent passing
|
90-100
|
35-100
|
15-100
|
0-70
|
0-50
|
0-30
|
0-5
|
In addition, not more than 3.75% by weight of the aggregate
material at the point of use must pass a #200 sieve.
1. Approved materials for drainfield mineral
aggregate must be limestone, slag, quartz rock, granite, river gravel, recycled
crushed concrete, lightweight aggregate and other equally durable
materials.
2. The aggregate must be
labeled as drainfield aggregate on the freight bill-of-lading. Effective March
1, 1995, a copy of the freight bill-of-lading must be part of the documentation
of aggregate size and quality and records must be available for Department
review for a period of two years from the date of purchase. This bill-of-lading
must clearly certify that the material meets the requirements for drainfield
use.
(d) Mineral
aggregate material must have a total depth of at least 12'' inches extending
throughout the width of the trench or absorption bed. The distribution pipe
must have a minimum of six inches of aggregate under the pipe, but must not
exceed 10'' inches under the pipe when the total depth of aggregate is 12''
inches.
(e) The drainfield in place
must be protected from infiltration of earth backfill by a barrier of polyester
bonded filament. The barrier must be placed on top of the drainfield only. For
alternative drainfield systems any required earth backfill barrier must be as
specified by the alternative system manufacturer, which must be approved by the
Department at the time of the initial alternative drainfield
approval.
(f) Providing the
requirements of subsections
62-6.006(1), (2) and
(6), F.A.C., are met, the maximum depth from
the bottom of the drainfield to the finished ground surface must not exceed 30
inches after natural settling. The minimum earth cover over the top of the
drainfield, distribution box or header pipe in standard subsurface drainfields
must be 6 inches after natural settling.
(g) The inside diameter of the drain pipe
used in drainfields must be determined based on the type and design of the
proposed absorption system. However, for standard gravity aggregate drainfield
systems, inside pipe diameter must not be less than 4 inches. Perforated pipe
must have two rows of holes, and a minimum perforated area of 1 1/2'' square
inches per linear foot. Perforations must be located not less than 30º or
more than 60º from the vertical on either side of the center line of the
bottom of the pipe. However, for drainfield systems designed by an engineer,
drain pipe perforation area and hole configuration must assure that effluent is
distributed as equally as possible throughout the drainfield area. All plastic
pipe must conform to the standards of ASTM D-3034-21, Standard Specification
for Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings (2021),
incorporated by reference in subparagraph
62-6.014(2)(a)
1., F.A.C. ASTM F 667/667M-16R21, Standard Specification for 3 through 24 in.
Corrugated Polyethylene Pipe and Fittings (2021), incorporated in subparagraph
62-6.014(2)(a)
4., F.A.C., or ASTM F-810-12R18, Standard Specification for Smoothwall
Polyethylene (PE) Pipe for Use in Drainage and Waste Disposal Absorption Fields
as incorporated by reference in subparagraph
62-6.014(2)(a)
5., F.A.C.
(h) Depending on the
type of drainfield system being utilized, the drainfield absorption surface
must be constructed level or with a downward slope not exceeding one inch per
10' feet. Drain lines must be placed at the same slope as the drainfield
absorption surface.
(i) The maximum
length of drain lines must not exceed 100' feet for all gravity-fed and
lift-dosed drainfields, and where two or more drain lines are used, they must
be, as near as practical, the same length. The ends of two or more drain lines
in bed and mound systems must be connected to produce a continuous circuit. A
continuous circuit arrangement is also recommended but not required for
standard drain trench systems. However, when a continuous circuit arrangement
is not used, the distal ends of the drain lines must be capped or
sealed.
(j) No part of a drainfield
must be placed within 18'' inches of the treatment or pump tank.
(k) If lots are encountered whereby a
standard drainfield system cannot meet drainfield slope or soil cover
requirements, a drop box configuration for sloping lots as per Section 7.2.8.1,
Chapter 7, EPA 625/1-80-012, Design Manual for Onsite Wastewater Treatment and
Disposal Systems, such section hereby incorporated by reference, may be used at
the installer's discretion for drainfield construction.
(6) All materials incorporated herein may be
obtained from the Department of Environmental Protection, Onsite Sewage Program
at
www.floridadep.gov or 2600 Blair
Stone Road, MS #3596, Tallahassee, Florida 32399-2400 or Florida Department of
State, Florida Administrative Code and Register, R.A. Gray Building, 500 South
Bronough Street, Tallahassee, Florida 32399-0250. Reference materials deemed
copyright protected are available for inspection at the same
address.