Kan. Admin. Regs. § 4-4-908 - Liquid-level-gauging device
(a) Except as
provided in paragraph (b) of this regulation, each storage container shall be
equipped with a liquid-level-gauging device by which the level of fluid in the
storage container can be readily and reliably measured.
(b) A liquid-level-gauging device shall not
be required if the level of fluid in a storage container can be readily and
reliably measured by other means approved by the secretary.
(c) Liquid-level-gauging devices shall be
locked or secured, in a safe manner, to protect against breakage or vandalism
which could result in a discharge.
(d) External sight gauges shall be prohibited
unless:
(1) the gauge has a positive shut-off
valve constructed from stainless steel;
(2) all pipes or other plumbing components
which connect the shut-off valve to the storage container shall be constructed
from stainless steel;
(3) the
sight gauge's shut-off valve remains closed except when the amount of material
stored in the storage container is being determined; and
(4) the shut-off valve is located on the
storage container in a location which is readily accessible and which conforms
to the storage container manufacturer's specifications.