Kan. Admin. Regs. § 49-50-19 - Combustion safeguards and waterside control appurtenances
(a) Each
automatically fired boiler shall be protected against the perils of low water,
furnace explosion, overpressure, and overtemperature by equipping the boiler
with controls and safety devices in accordance with the requirements of ASME
CSD-1. ASME CSD-1 and the national board inspection code, which are adopted by
reference in K.A.R. 49-45-27 and K.A.R. 49-45-20, shall apply to new
installations, used or secondhand boilers, boilers moved and relocated,
retrofitting of any boiler system having experienced incidental failure of its
control equipment, major alterations of existing installations, and any boiler
that could lack controls and safety devices.
(b) To implement the provisions of ASME CSD-1
and the national board inspection code, manufacturers of new boilers shall
provide documentation to installing contractors verifying that the boiler was
constructed in compliance with CSD-1, Part CG-510. The testing and maintenance
instructions obtained by the installing contractor and presented to the boiler
owner or user shall be filed with the installation report and made available to
the inspector upon request.
(c)
Combustion and waterside controls and safety devices for boilers with burner
inputs that exceed the 12,500,000 BTUH input limit of CSD-1 shall meet the
requirements of all applicable ASME and NFPA standards and the national board
inspection code, as adopted by reference in these regulations. Applicable flame
safeguard requirements for the prevention of furnace explosions shall be those
set forth in the national fire code, sections 85, 85A, 85F, and 86, which are
adopted by reference in K.A.R. 49-45-37, K.A.R. 49-45-38, K.A.R. 45-49-39, and
K.A.R. 49-45-40. Combustion and waterside controls and safety devices for
existing boiler installations with burner inputs that exceed the 12,500,000
BTUH limit of CSD-1 shall meet the applicable provisions of the edition of the
ASME and NFPA standards in effect when they were constructed and installed.
Whenever existing installations are considered unsafe, undergo extension repair
due to accidental damage, major alteration due to accidental damage, or lack a
qualified 24-hour attendant, flame safeguard and other pertinent controls and
safety devices shall be brought up to the current code requirements.
(d) Each owner, user, or installer of boilers
using flame safeguard equipment shall document the results of combustion safety
testing. The frequency of testing shall be in accordance with the equipment
manufacturer's recommendations but shall be conducted at least upon the initial
start-up and shutdown of the boiler. An inspection and maintenance schedule
shall be established and performed to comply with the boiler and combustion
system manufacturer's recommendations. Documentation relative to the combustion
safety testing shall be kept on permanent file at the boiler location and shall
be made available to the authorized inspector upon request. The use of rebuilt
or remanufactured flame safeguard equipment shall not be allowed. Each boiler
control shall be listed as UL (underwriters laboratories), FM (factory mutual),
or AGA (American gas association).
(e) Each boiler that operates continuously
for more than 24 hours shall have a self-checking scanner that is compatible
with the type of fuel being burned.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.