(1)
Prohibited Venting.
(a)
Combination Waste and
Vent. A combination waste and vent system shall be prohibited
without Special-permission by the Board and shall comply with the following:
1. A combination waste-and-vent system is
limited to the installation of floor drains and sinks.
2. A combination waste-and-vent system
consists of a wet vented installation of waste piping in which fixture drains
are not individually vented.
3.
Every drainage pipe in a combination waste-and-vent system shall be not less
than two pipe sizes larger than the size required in
248
CMR
10.15.
(b)
Crown Venting.
No vent shall be installed within two pipe diameters of the trap weir.
See 10.16:
Example 1.
Example 1 - Crown Venting
Click to
view image
(c)
Extension of Horizontal Drain. The extension or
continuation of a horizontal soil or waste pipe shall not serve as a vent.
Exception:
1. When permitted under wet venting
248
CMR
10.16(5); and
2. When a fixture waste of not more than two
fixture units is connected to the vertical extension of the extended horizontal
piping.
See 10.16: Example 2.
Example 2 - Wet Vent Extension of a Horizontal
Drain
Click to
view image
(d)
Below Trap Weir.
The vent pipe opening from a soil or waste pipe, except for water closets and
similar fixtures shall not be below the weir of the trap.
(e)
Automatic Vent Fittings and
Air Admittance Valves: Automatic vents and air admittance valves
are not permitted without Special-Permission from the Board.
(2)
Vent Stacks and
Stack Vents.
(a) All building
drains within a structure shall, at minimum have at least one full size main
stack vent or a vent stack no less than three inches in diameter.
(
See
248
CMR
10.16 (11):
Table 2:
Size and Lengths of Vents for
fixture unit values to determine the appropriate stack vent or vent stack
size). Buildings with three or more branch intervals shall have at least one
main vent stack properly sized in accordance with 10.16:
Table
2 from the building drain through to the open air above the roof or
connect back to a main stack vent six inches above the flood level rim of the
highest fixture being served.
(b) A
vent stack or a main vent shall be installed with a soil or waste stack
whenever individual vents, relief vents, or other branch vents are
required.
(c)
Connections at Base and Top.
1. All main vents or vent stacks shall
connect full size at their base to the drainage of the building or to the main
soil or waste pipe, at or below the lowest fixture branch.
2. All vent pipes shall extend undiminished
in size above the roof, or shall be reconnected with the main soil or waste
stack a minimum of six inches above the flood level rim of the highest fixture
discharging into it.
(d)
Offsets in Buildings Five or More Stories in Height.
1. Except as provided in
248
CMR
10.15, offsets of more than 45 ° from
the vertical in a soil or waste stack may be vented:
a. as two separate soil or waste stacks;
i. installing a relief vent as a vertical
continuation of the lower section of the stack; or
ii. as a yoke vent connected to the lower
section between the offset and the next lower fixture or horizontal
branch.
iii. The upper section of
the offset shall be provided with a yoke vent.
iv. The diameter of the vents shall not be
less than the diameter of the main vent or of the soil and waste stack,
whichever is the smaller.
See 10.16: Example 3
10.16: Example 3 - Offsets of More Than
45°
Click to
view image
(e)
Vent Headers.
1. Where vent stacks and stack vents connect
to a vent header, the connections shall be made at the top of the
stacks.
2. The vent header shall
connect to a vent extension through the roof.
3. When more than two four-inch soil or waste
stacks are connected, the vent header extension through the roof shall be five
inches in diameter.
4. When more
than four four-inch stacks are connected, the diameter shall be six inches in
diameter.
(f)
Relief Vents for Vents in Buildings with More than Ten Branch
Intervals.
1. Soil and waste
stacks in buildings having more than ten branch intervals shall be provided
with a relief vent at each tenth interval installed, beginning from the top
floor down.
2. The size of the
relief vent shall be equal to the size of the vent stack to which it
connects.
3. The lower end of each
relief vent shall connect to the soil or waste stack through a wye below the
horizontal branch serving the floor and the upper end shall connect to the vent
stack through a wye not less than three feet above the floor level.
(3)
Vent
Terminals.
(a)
Extension Above Roof.
1. The vent extension through a roof shall be
no less than two inches in diameter and shall extend to a point between 18 and
24 inches above the penetration through the roof. See 10.16:
Example 4.
2. If
the roof area is used for gardening, a parking deck, observation deck or
similar purposes, the vent shall extend no less than eight feet above the roof
and be increased one pipe diameter. See 10.16: Example
5.
3.
Increaser. The change in the diameter of a vent
terminal shall be made using an increaser; and occur no less than one foot
below the roof surface.
See 10.16: Example 4.
Example 4 - Vent Extension Through Roof
Click to
view image
Example 5 - Vent Extension Through Observation Deck or
Similar
Click to
view image
(b)
Waterproof
Flashings. Each vent terminal shall be made watertight with the
roof by proper flashing.
(c)
Location of Vent Terminal.
1. No vent terminal shall be located directly
beneath any building opening or within ten feet horizontally of the opening
unless it is at least two feet above the top of said opening.
See
248
CMR
10.16:
Example
6.
2. Plumbing vent
terminals shall be located no less than 25 feet horizontally from forced air
intakes. Vents terminating no less than two feet above the top of the forced
air intake may be located as close as ten feet from the forced air intake.
248
CMR
10.16(3)(a) does not
apply in this case.
See
248
CMR
10.16:
Example 7.
Example 6 - Location of Vent Terminal
Click to
view image
Example 7 - Vent Terminal from Forced Air
Inlet
Click to
view image
(d)
Vent Extensions Outside of
the Building. All soil, waste or vent pipe extensions shall be
installed inside the building.
Exception: For remodeling and
alteration work only, vents may be installed outside the building when all
other means of venting have been eliminated or are not practical and with prior
permission of the Inspector.
(e)
Frost Closure.
Where frost closure is likely to occur, each vent extension through a roof
shall be at least three inches in diameter.
(4)
Vent Grades and
Connections.
(a)
Vent
Grade. All vents shall be uniformly graded in accordance with
248
CMR
10.05(2) and connected
as to drain back to a soil or waste pipe by gravity.
(b)
Vertical Rise.
1. Where vent pipes connect to a horizontal
soil or waste pipe:
a. The vent shall be
taken off above the center line of the soil or waste pipe drain.
b. For other than floor mounted fixtures, the
vent pipe shall rise vertically, or at an angle of 45 ° from the vertical,
to a point at least six inches above the flood-level rim of the fixture it is
venting, before it may offset horizontally.
c. For floor mounted fixtures, the vent may
be extended horizontally above the centerline of the drain of the fixture to
the nearest practical location where it can rise vertically. The vent shall
come off the soil or waste pipe above the centerline of the drain not less than
45° from the horizontal before running in a horizontal
position.
(c)
Height Above Fixtures.
1. All connection between a vent pipe and a
vent stack or stack-vent shall be made at least six inches above the
flood-level rim of the highest fixture served by the vent.
2. Horizontal vent pipes forming branch
vents, relief vents, or loop vents shall be installed at least six inches above
the flood-level rim of the highest fixture served.
(5)
Wet
Venting.
(a)
Bathroom
Wet Vent. In a bathroom having a two-inch horizontal waste, a
two-inch extension of the horizontal drain connecting to a lavatory may serve
as a wet vent for the fixtures it serves.
See 10.16:
Example 2. This would also apply to double or back-to-back
bathrooms.
The lowest portion of the pipe serving as a wet vent shall
break the centerline of the horizontal drain it serves. See
10.16: Example 11.
(b)
Piping Not to Serve as Wet
Vents. Waste and vent piping that serves:
1. Kitchen sink;
2. Garbage disposal;
3. Dishwasher;
4. Washing machine; and
5. Any fixture for culinary use.
Example 10 - Miscellaneous Wet Venting
Click to
view image
Example 11 - Wet Venting Breaking the
Centerline
Click to
view image
(6)
Stack Venting.
(a)
Plumbing Fixtures at the Top
Branch Interval of a Stack.
1.
Plumbing fixtures at the highest level may enter a three-inch soil or waste
stack.
2. The continuation of a
three-inch soil or waste stack vented through the roof or reconnected to the
venting system above the highest fixture shall be accepted, provided:
a. all such fixtures shall enter said stack
independently;
b. the waste pipe
from all fixtures shall have a pitch of not more than one quarter inch pitch
per foot;
c. the toilet and bathtub
or shower drain connect to the stack at the same floor level; and
d. the traps from all fixtures shall be
placed in compliance with
248
CMR
10.16(10):
Table
1: Distance of Fixture Trap from Vent.
See 10.16:
Example 12 for Miscellaneous Stack Venting.
Example 12 - Miscellaneous Stack Venting
Stack Venting Top Floor
Click to
view image
Stack Venting Top Floor with Estabrook
Click to
view image
Stack Venting Lower Floors
Click to
view image
(b)
Stack Venting.
Provided there is a soil and/or waste stack in a building as required under
248
CMR
10.16(2)(a), the
continuation in an upwards direction of the vertical waste for a toilet may be
reduced to two inch and serve as the vent for the toilet and the waste for a
lavatory, bathtub, or shower stall, and a kitchen sink.
See
10.16:
Example 12, Stack Venting on Lower Floors.
(c)
Back to Back Installation
(Stack Vented). Bathroom groups installed back-to-back shall be
permissible provided they comply with the provisions of
248
CMR
10.16(6)(a).
(7)
Common
Vents.
(a)
Individual Vent as Common Vent. An individual vent,
installed vertically, may be used as a common vent for two fixture traps when
both fixture drains connect with a vertical drain at the same level.
(b)
Side by Side. If
two bathtubs or similar flat bottom fixtures are installed back to back or side
by side, a common vent may be used in a vertical position to serve as the vent
for both fixtures.
(c)
Different Levels. A vertical vent may be used for two
fixtures that are in the same branch interval but connected to the stack at
different levels, not exceeding ten inches center to center, provided:
1. The vertical drain is one pipe diameter
larger than the upper fixture drain but is not smaller than the lower fixture
drain, whichever is the larger.
2.
That both wastes for said fixtures conform to
248
CMR
10.16(10):
Table
1:
Distance of Fixture Trap from Vent.
See 10.16:
Example 13, Drawing 3.
(d)
Back-to-back
Fixtures. Two fixtures installed back-to-back within the distance
allowed between the trap and vent as stated in
248
CMR
10.16(10):
Table
1, may have one continuous vent provided each fixture wastes
separately into a double sanitary drainage tee fitting having inlet openings at
the same level.
See
248
CMR
10.15(8)(b).
(e)
Horizontal Waste
Branch.
1. Two lavatories or
similar fixtures installed adjacent or back-to-back within six feet of a main
vented stack, proper wet vent, or continuous waste and vent, may be installed
on a two-inch horizontal waste branch without installation of an independent
vent, provided:
a. the horizontal waste
branch is not less than two inches throughout its entire length; and
b. the fixture wastes are connected into the
side center of the branch.
See 10.16:
Example 13,
Drawing 1.
Example 13 - Miscellaneous Types Venting
Drawing 1.
Click to
view image
Drawing 2.
Relief Vent Necessary Per 10.16 Table 1
Click to
view image
Drawing 3.
See
248
CMR 10.16(7)(c)
Click to
view image
(8)
Venting of a Battery Drainage
System.
(a) A horizontal branch
drain may be vented by either a circuit or loop vent installed downstream of
the last fixture connection of the battery provided the branch drain has two,
but not more than eight floor outlet fixtures that are connected in a battery
and discharged into the side center of the horizontal battery branch drain.
1. A circuit vent shall be connected to a
proper vent upstream of the horizontal battery drainage system.
2. A loop vent shall be connected to a proper
vent downstream of the horizontal battery drainage system.
(b) In addition, lower floor branches serving
fixtures as described above shall be provided with a relief vent installed
vertically downstream of the first fixture in the battery and shall connect
back to the circuit or loop vent.
See 10:16:
Example
14.
1. Where only two fixtures that
are battery waste and vented are installed on the same branch, a relief vent as
described above shall not be required.
2. Batteries of more than eight fixtures may
be installed providing an additional vent is installed for each eight or less
of the fixtures connected.
(c) Fixtures other than the floor outlet type
may also connect to the battery drainage system but shall be either individual
or common vented.
(d)
Dual Branches. When parallel branches are installed,
all the provisions and requirements of
248
CMR
10.16(8) shall prevail.
Exception: Fixtures connecting to each
parallel horizontal branch shall be sized based on 50% of the fixture units
permitted on a horizontal branch for a battery drainage system.
(c)
Vent
Connections. Vents installed in a battery drainage system shall be
taken off at a vertical angle above the centerline of the drain or from the top
of the horizontal branch.
Example 14 - Battery Venting Installations
Click to
view image
Example 15 - Circuit and Loop VentingSee
10.03: Definition of Circuit Vent and Loop Vent
Click to
view image
(9)
Bow Vents.
(a) Bow vents are permitted when a vent for
an individual sink or lavatory cannot rise six inches above the flood level rim
of the fixture before turning horizontal.
(b) The bow vent shall be sized in accordance
with 248 CMR
10.16(11):
Table
2:
Size and Lengths of Vents.
Example 16 - Typical Bow Vent Installations
Click to
view image
(10)
Fixture Vents.
(a)
Distance of Trap from
Vent. Each fixture trap shall have a vent with a developed length
in the fixture drain from the trap weir to the vent fitting are within the
requirements set forth in
248
CMR
10.16(12):
Table
1:
Distance of Fixture Trap from Vent.
Click to
view image
Table 1
Distance of Fixture Trap from Vent
|
Diameter of Pipe
|
Maximum Developed Length of the Pipe
|
|
11/2
|
5"
|
|
2
|
6'
|
|
3
|
8'
|
|
4
|
10'
|
|
Slope not to exceed 1/4" per foot
|
Click to
view image
(b)
Venting of Fixture Drain Below Trap.
1. The vent pipe openings from a soil or
waste pipe, except for toilets and similar fixtures, shall not be below the top
weir of the trap.
2. An exception
to 248 CMR
10.16(10)(b)
shall be permitted if the following
requirements are satisfied:
a. The fixture has
a flat bottom with a minimum area of 144 square inches.
b. The horizontal section of the fixture
waste must comply with
248
CMR
10.16(10):
Table
1:
Distance of Fixture Trap from Vent and the
vertical section shall be at least one pipe size larger than the fixture trap
and waste arm.
c. The vent opening
shall be as high and close to the fixture as possible.
(c)
Floor-mounted
Fixture Outlet.
1. When
installing the piping for a floor outlet type toilet or similar fixture, the
vertical piping distance shall not exceed 20 inches from the finish floor of
the fixture served to the center line of the horizontal drain serving such
fixture.
2. If the vertical
distance exceeds 20 inches the fixture shall be individually vented.
(11)
Size
and Length of Vents.
(a)
Size of Individual Vents. The minimum diameter of an
individual vent shall be not less than 11/4 inch or less than 1/2 the
diameter of the drain to which it connects.
(b)
Size of Circuit, Loop and
Relief Vents. The diameter of a relief vent shall be not less than
1/2 the diameter of the soil or waste branch to which it connects when
fixtures are battery connected.
(c)
Length and Size of Vent Stacks. The length and size of
the vent stack or main vent shall be determined by the developed length from
the lowest connect of the vent to the sanitary drainage system to the open air.
See
248
CMR
10.16(11):
Table
2.
(d)
Size of
Vents. The vent pipe sizes shall be determined from their
developed length and the total number of fixture units connected thereto, as
listed in
248
CMR
10.16(11):
Table
2:
Size and Lengths of Vents. This table shall be
used to size all vents, except for those vents that are specifically sized
elsewhere in
248 CMR
3.00 through
10.00.
(e)
Size of Underground Vent
Piping. No portion of the venting system installed underground or
below a basement floor, shall be less than two inches in diameter.
Table 2
Size and Lengths of Vents
|
Diameter of Soil or Waste Stack or Branch in
Inches
|
Total Fixture Units Connected to Stack or Branch in
Fixture Units
|
|
|
11/4
|
11/2
|
2
|
21/2
|
3
|
4
|
5
|
6
|
8
|
10
|
|
11/2
|
4
|
50
|
150
|
|
2
|
10
|
25
|
50
|
150
|
|
21/2
|
28
|
30
|
100
|
300
|
|
3
|
7
|
42
|
150
|
360
|
1040
|
|
3
|
21
|
32
|
110
|
270
|
810
|
|
3
|
53
|
27
|
94
|
230
|
680
|
|
3
|
102
|
25
|
86
|
210
|
620
|
|
4
|
43
|
35
|
85
|
250
|
980
|
|
4
|
140
|
27
|
65
|
200
|
750
|
|
4
|
320
|
23
|
55
|
170
|
640
|
|
4
|
530
|
21
|
50
|
150
|
580
|
|
5
|
190
|
28
|
82
|
320
|
990
|
|
5
|
490
|
21
|
63
|
250
|
760
|
|
5
|
940
|
18
|
53
|
210
|
640
|
|
5
|
1,400
|
16
|
49
|
190
|
590
|
|
6
|
500
|
33
|
130
|
400
|
1,000
|
|
6
|
1,100
|
26
|
100
|
310
|
780
|
|
6
|
2,000
|
22
|
84
|
260
|
660
|
|
6
|
2,900
|
20
|
77
|
240
|
600
|
|
8
|
1,800
|
31
|
95
|
240
|
940
|
|
8
|
3,400
|
24
|
73
|
190
|
720
|
|
8
|
5,600
|
20
|
62
|
160
|
610
|
|
8
|
7,600
|
18
|
56
|
140
|
560
|
|
10
|
4,000
|
31
|
78
|
310
|
960
|
|
10
|
7,200
|
24
|
60
|
240
|
740
|
|
10
|
11,000
|
20
|
51
|
200
|
630
|
|
10
|
15,000
|
18
|
46
|
180
|
570
|
Note 1: Table 2 shall also apply to
the sizing of vents for branch soil and waste lines.
To determine size of vent, use the following procedure:
a. Compute total number of fixture units,
using
248
CMR
10.15(7):
Table
1:
Fixture Unit Values for Various Plumbing Fixtures
and 248 CMR
10.15(2)(b).
b. Knowing total fixture unit load, refer to
248
CMR
10.15(7):
Table
3:
Maximum Loads in Fixture Units for Soil and Waste Stacks
Having One or Two Branch Intervals or
248
CMR
10.15(7):
Table
4:
Maximum Loads in Fixture Units for any One Branch Interval
on Multistory Soil and Waste Stacks depending on number of intervals,
to determine size of stack.
c. With
selected stack size and total fixture unit load refer to
248
CMR
10.16 (11):
Table 2:
Size and Lengths of Vents and
determine size of vent. Follow same procedure to determine size of vents for
branch soil and waste lines.
(12)
Future Venting.
(a) In the lowest level of any building there
shall be an accessible future vent connection.
(b) Buildings that require a main vent stack
shall have a future vent connection full size of the vent stack. In all other
buildings (including residential) there shall be a minimum of a two-inch future
vent connection.
(c) All future
vent connections shall be drip connected identified and labeled "Future
Vent".
(13)
Venting of Ejector Sumps.
(a)
Size of Vents.
The size and length of all vent pipes serving building sanitary ejector sumps
shall be determined from, and in accordance with
248
CMR
10.16 (14)
Table 3:
Size and Lengths of Sump
Vents.
(b)
Pneumatic Ejector. The air pressure relief pipe from a
pneumatic ejector shall not be connected to the regular venting system but
shall be vented independently to the atmosphere through the roof.
Table 3
Size and Lengths of Sump
Vents2
|
Diameter of Drain to
Sump1
|
Diameter of Vent (inches)
|
|
1A
|
1A
|
2
|
2A
|
3
|
4
|
5
|
6
|
8
|
10
|
12
|
|
2
|
23
|
52
|
290
|
|
2A
|
5
|
13
|
89
|
290
|
|
3
|
2
|
30
|
110
|
290
|
|
4
|
1
|
17
|
57
|
280
|
|
5
|
10
|
80
|
280
|
|
6
|
20
|
97
|
280
|
|
8
|
3
|
41
|
270
|
|
10
|
1
|
53
|
250
|
|
12
|
61
|
230
|
Note 1: Where more than one drain
connects to the sump, size vent on the basis of a drain diameter having a cross
sectional area equal to the sum of the areas of the multiple drains.
Note 2: The above values provide for a
maximum of one-inch pressure drop in the system.
Example 17
Individual Venting - Wet Venting - Stack
venting
Click to
view image