1. Systems using surface water or ground
water under the direct influence of surface water and using conventional
filtration treatment must operate with enhanced coagulation or enhanced
softening to achieve the TOC percent removal levels specified in this rule
unless the system meets at least one (1) of the alternative compliance criteria
listed here. These systems must still comply with monitoring and compliance
requirements of this rule. The alternative compliance criteria for enhanced
coagulation and enhanced softening are:
A. The
system's source water TOC level, measured according to 10 CSR 605.010, is less
than 2.0 mg/L, calculated quarterly as a running annual average;
B. The system's treated water TOC level,
measured according to 10 CSR 605.010, is less than 2.0 mg/L, calculated
quarterly as a running annual average;
C. The system's source water TOC level,
measured according to 10 CSR 605.010, is less than 4.0 mg/L, calculated
quarterly as a running annual average; the source water alkalinity, measured
according to
10 CSR 60-5.010, is greater than
sixty (60) mg/L (as CaCO
3), calculated quarterly as a
running annual average; and either the TTHM and HAA5 running annual averages
are no greater than 0.040 mg/L and 0.030 mg/L, respectively; or prior to the
effective date for compliance with this rule, the system has made a clear and
irrevocable financial commitment not later than the effective date for
compliance with this rule to use technologies that will limit the levels of
TTHMs and HAA5 to no more than 0.040 mg/L and 0.030 mg/L, respectively. Systems
must submit evidence of a clear and irrevocable financial commitment, in
addition to a schedule containing milestones and periodic progress reports for
installation and operation of appropriate technologies, to the department for
approval not later than the effective date for compliance with this rule. These
technologies must be installed and operating not later than June 30, 2005.
Failure to install and operate these technologies by the date in the approved
schedule will constitute a violation;
D. The TTHM and HAA5 running annual averages
are no greater than 0.040 mg/L and 0.030 mg/L, respectively, and the system
uses only chlorine for primary disinfection and maintenance of a residual in
the distribution system;
E. The
system's source water SUVA, prior to any treatment and measured monthly
according to
10 CSR 60-5.010, is less than or
equal to 2.0 L/mg-m, calculated quarterly as a running annual average. SUVA
refers to Specific Ultraviolet Absorption at two hundred fifty-four nanometers
(254 nm), an indicator of the humic content of water. It is a calculated
parameter obtained by dividing a sample's ultraviolet absorption at a
wavelength of 254 nm (UV
254) (in
m
=1) by its concentration of dissolved organic
carbon (DOC) (in mg/L); and
F. The
system's finished water SUVA, measured monthly according to 10 CSR 605.010, is
less than or equal to 2.0 L/mg-m, calculated quarterly as a running annual
average.
2. Additional
alternative compliance criteria for softening systems. Systems practicing
enhanced softening that cannot achieve the Step 1 TOC removals may use the
alternative compliance criteria listed here in lieu of complying with paragraph
(3)(C)3. of this rule. Systems must still comply with monitoring and compliance
requirements of this rule.
A. Softening that
results in lowering the treated water alkalinity to less than sixty (60) mg/L
(as CaCO
3), measured monthly according to
10 CSR
60-5.010 and calculated quarterly as a running annual
average.
B. Softening that results
in removing at least ten (10) mg/L of magnesium hardness (as
CaCO
3), measured monthly according to
10 CSR
60-5.010 and calculated quarterly as an annual running
average.
3. Enhanced
coagulation and enhanced softening performance requirements.
A. Systems must achieve the percent reduction
of TOC specified in Table 1 between the source water and the combined filter
effluent, unless the department approves a system's request for alternate
minimum TOC removal (Step 2) requirements. Systems may begin monitoring to
determine whether Step 1 TOC removals can be met twelve (12) months prior to
the compliance date for the system. This monitoring is not required and failure
to monitor during this period is not a violation. However, any system that does
not monitor during this period, and then determines in the first twelve (12)
months after the compliance date that it is not able to meet the Step 1
requirements and must therefore apply for alternate minimum TOC removal (Step
2) requirements, is not eligible for retroactive approval of alternate minimum
TOC removal (Step 2) requirements and is in violation. Systems may apply for
alternate minimum TOC removal (Step 2) requirements any time after the
compliance date. For systems required to meet Step 1 TOC removals, if the value
calculated under part (3)(C)4.A.(IV) of this rule is less than 1.00, the system
is in violation of the treatment technique requirements and must notify the
public pursuant to
10 CSR 60-8.010 in addition to
reporting to the department pursuant to
10 CSR
60-7.010.
B. Required Step 1 TOC reductions, indicated
in the following table, are based upon specified source water parameters
measured in accordance with
10 CSR
60-5.010. Systems practicing softening are required to
meet the Step 1 TOC reductions in the far right column (Source water alkalinity
>120 mg/L) for the specified source water TOC.
Table 1: Required Step 1 TOC Reduction
|
Step 1 Required Removal of TOC by Enhanced
Coagulation and Enhanced Softening for Surface Water and GWUDISW Systems Using
Conventional Treatment1,2
|
|
Source water TOC, mg/L
|
Source water alkalinity, mg/L as
CaCO3
|
|
0-60
|
>60-120
|
>1203
|
|
>2.0-4.0
|
35.0%
|
25.0%
|
15.0%
|
|
>4.0-8.0
|
45.0%
|
35.0%
|
25.0%
|
|
>8.0
|
50.0%
|
40.0%
|
30.0%
|
1Systems meeting at least one (1)
of the conditions in paragraph (3)(C)1. of this rule are not required to
operate with enhanced coagulation.
2Softening systems meeting one (1)
of the alternative compliance criteria in paragraph (3)(C)1. of this rule are
not required to operate with enhanced softening.
3Systems practicing softening must
meet the TOC removal requirements in this column.
C. Conventional treatment systems using
surface water or ground water under the direct influence of surface water that
cannot achieve the Step 1 TOC removals due to water quality parameters or
operational constraints must apply to the department, within three (3) months
of failure to achieve the Step 1 TOC removals, for approval of alternative
minimum TOC removal (Step 2) requirements submitted by the system. If the
department approves the alternative minimum TOC removal (Step 2) requirements,
the department may make those requirements retroactive for the purposes of
determining compliance. Until the department approves the alternate minimum TOC
removal (Step 2) requirements, the system must meet the Step 1 TOC removals.
D. Alternate minimum TOC removal
(Step 2) requirements. Applications made to the department by enhanced
coagulation systems for approval of alternative minimum TOC removal (Step 2)
requirements under subparagraph (3)(C)3.C. of this rule must include, as a
minimum, results of bench- or pilot-scale testing conducted under this
subparagraph (3)(C)3.D. and used to determine the alternate enhanced
coagulation level.
(I) Alternate enhanced
coagulation level is defined as coagulation at a coagulant dose and pH as
determined by the method described here such that an incremental addition of
ten (10) mg/L of alum (or equivalent amount of ferric salt) results in a TOC
removal of less than or equal to 0.3 mg/L. The percent removal of TOC at this
point on the "TOC removal versus coagulant dose" curve is then defined as the
minimum TOC removal required for the system. Once approved by the department,
this minimum requirement supersedes the minimum TOC removal required by Table 1
of this rule. This requirement will be effective until such time as the
department approves a new value based on the results of a new bench- and
pilot-scale test. Failure to achieve department-set alternative minimum TOC
removal levels is a violation.
(II)
Bench- or pilot-scale testing of enhanced coagulation must be conducted by
using representative water samples and adding 10 mg/L increments of alum (or
equivalent amounts of ferric salt) until the pH is reduced to a level less than
or equal to the enhanced coagulation Step 2 target pH shown in Table 2.
Table 2: Enhanced Coagulation
Step 2 Target pH
|
Alkalinity (mg/L as
CaCO3)
|
Target pH
|
|
0-60
|
5.5
|
|
>60-120
|
6.3
|
|
>120-240
|
7.0
|
|
>240
|
7.5
|
(III)
For waters with alkalinities of less than sixty (60) mg/L for which addition of
small amounts of alum or equivalent addition of iron coagulant drives the pH
below 5.5 before significant TOC removal occurs, the system must add necessary
chemicals to maintain the pH between 5.3 and 5.7 in samples until the TOC
removal of 0.3 mg/L per 10 mg/L alum added (or equivalent addition of iron
coagulant) is reached.
(IV) The
system may operate at any coagulant dose or pH necessary (consistent with other
regulatory requirements) to achieve the minimum TOC percent removal approved
under subparagraph (3)(C)3.C. of this rule.
(V) If the TOC removal is consistently less
than 0.3 mg/L of TOC per 10 mg/L of incremental alum dose at all dosages of
alum (or equivalent addition of iron coagulant), the water is deemed to contain
TOC not amenable to enhanced coagulation. The system may then apply to the
department for a waiver of enhanced coagulation
requirements.
4. Compliance calculations.
A. Systems using surface water or ground
water under the direct influence of surface water, other than those identified
in paragraphs (3)(C)1. or (3)(C)2. of this rule, must comply with requirements
contained in subparagraphs (3)(C)3.B. or (3)(C)3.C. of this rule. Systems must
calculate compliance quarterly, beginning after the system has collected twelve
(12) months of data, by determining an annual average using the following
method:
(I) Determine actual monthly TOC
percent removal, equal to: (1 - (treated water TOC/source water TOC)) ×
100;
(II) Determine the required
monthly TOC percent removal;
(III)
Divide the value in part (3)(C)4.A.(I) by the value in part (3)(C)4.A.(II);
and
(IV) Add together the results
of part (3)(C)4.A.(III) for the last twelve (12) months and divide by twelve
(12). If the value calculated is less than 1.00, the system is not in
compliance with the TOC percent removal requirements.
B. Systems may use the following provisions
in lieu of the calculations in subparagraph (3)(C)4.A. of this rule to
determine compliance with TOC percent removal requirements:
(I) In any month that the system's treated or
source water TOC level, measured according to
10 CSR
60-5.010, is less than 2.0 mg/L, the system may assign
a monthly value of 1.0 (in lieu of the value calculated in part (3)(C)4.A.(III)
of this rule);
(II) In any month
that a system practicing softening removes at least 10 mg/L of magnesium
hardness (as CaCO3), the system may assign a monthly
value of 1.0 (in lieu of the value calculated in part (3)(C)4.A.(III) of this
rule);
(III) In any month that the
system's source water SUVA, prior to any treatment and measured according to
10 CSR
60-5.010, is less than or equal to 2.0 L/mg-m, the
system may assign a monthly value of 1.0 (in lieu of the value calculated in
part (3)(C)4.A.(III) of this rule);
(IV) In any month that the system's finished
water SUVA, measured according to
10 CSR
60-5.010, is less than or equal to 2.0 L/mg-m, the
system may assign a monthly value of 1.0 (in lieu of the value calculated in
part (3)(C)4.A.(III) of this rule); and
(V) In any month that a system practicing
enhanced softening lowers alkalinity below sixty (60) mg/L (as
CaCO3), the system may assign a monthly value of 1.0 (in
lieu of the value calculated in part (3)(C)4.A.(III) of this rule).
C. Systems using conventional
treatment and surface water or ground water under the direct influence of
surface water may also comply with the requirements of this rule by meeting the
criteria in paragraphs (3)(C)1. or (3)(C)2. of this rule.