N.J. Admin. Code § 7:14A-23.27 - Sludge pumps

(a) Duplicate sludge pumps shall be provided and shall be so arranged with appropriate valves such that either may be used, in emergencies, for handling either raw or digested sludge.
(b) The capacity of each pump for handling raw sludge shall be such as to remove sludge from hoppers of settling or concentration tanks in not less than one hour nor more than two hours. Pump capacity shall be adjustable.
(c) A minimum positive head of 24 inches shall be provided at the suction side of centrifugal pumps and is desirable for all types of pumps. Maximum dynamic suction lift of plunger pumps shall be 10 feet.
(d) Sludge sampling facilities shall be provided in accordance with 7:14A-23.14. The size of valve and piping shall be at least 1 1/2 inches.
(e) Pressure gauges shall be provided on the discharge line of sludge pumps to denote pumping and to indicate unusual discharge heads due to clogging.

Notes

N.J. Admin. Code § 7:14A-23.27

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.