N.J. Admin. Code § 7:14B-6.5 - Methods of release detection for tanks
(a) The owner and
operator shall use each method of release detection for tanks according to the
requirements of N.J.A.C. 7:14B-6.2
,
6.3, and 6.4, and in accordance with the
following:
1. Product inventory control shall be
conducted monthly to detect a release of at least 1.0 percent of throughput plus 130
gallons on a monthly basis in the following manner:
i. Inventory volume measurements for regulated
substance inputs, withdrawals, and the amount still remaining in the tank shall be
recorded each operating day;
ii. The
equipment used shall be capable of measuring the level of product over the full
range of the tank's height to the nearest one-eighth of an inch;
iii. The regulated substance inputs shall be
reconciled with delivery receipts by measurement of the tank inventory volume before
and after delivery;
iv. Deliveries shall
be made through a drop tube that extends to within one foot of the tank
bottom;
v. Product dispensing shall be
metered and recorded within the standards for meter calibration pursuant to
13:47B-1.20;
vi. The measurement of any water level in the
bottom of the tank shall be made to the nearest one-eighth of an inch at least once
a month; and
vii. The practices
described in American Petroleum Institute, Recommended Practice 1621 "Bulk Liquid
Stock Control at Retail Outlets," may be used, where applicable, as guidance in
meeting the requirements of N.J.A.C. 7:14B-6.5(a)1i through vi
above.
2. Manual tank gauging
shall meet the following requirements:
i. Tank
liquid level measurements shall be taken at the beginning and ending of a period, as
appropriate, to the minimum duration of test value given in the table at (a)2v
below, during which no liquid is added to or removed from the tank;
ii. Level measurements shall be based on an
average of two consecutive stick readings at both the beginning and ending of the
period;
iii. The equipment used shall be
capable of measuring the level of product over the full range of the tank's height
to the nearest one-eighth of an inch;
iv. Only tanks of 550 gallons or less nominal
capacity and tanks with a nominal capacity of 551 to 1,000 gallons that meet the
tank diameter criteria in the table in (a)2v below may use manual tank gauging as
the sole method of release detection. Tanks of 551 to 2,000 gallons nominal capacity
may use the method in place of manual inventory control as set forth in (a)1 above.
Tanks of greater than 2,000 gallons nominal capacity may not use manual tank gauging
to meet the requirements of this subchapter; and
v. A release shall be suspected and subject to the
requirements of N.J.A.C. 7:14B-7 if the variation between beginning and ending
measurements exceeds the weekly or monthly standards in the following table:
Nominal Tank Capacity | Minimum Duration of Test | Weekly Standard (one test) | Monthly Standard (average of four tests) |
550 gallons or less | 36 hours | 10 gallons | 5 gallons |
551 to 1,000 gallons (when tank diameter is 64 inches) | 44 hours | 9 gallons | 4 gallons |
551 to 1,000 gallons (when tank diameter is 48 inches) | 58 hours | 12 gallons | 6 gallons |
551 to 1,000 gallons (also requires periodic tank tightness testing) | 36 hours | 13 gallons | 7 gallons |
1,001 to 2,000 gallons (also requires periodic tank tightness testing) | 36 hours | 26 gallons | 13 gallons |
3. Tank tightness testing shall be capable of
detecting a 0.1 gallon per hour leak rate from any portion of the tank that
routinely contains product while accounting for the effects of thermal expansion or
contraction of the product, vapor pockets, tank deformation, evaporation or
condensation, and the location of the water table.
4. Equipment for automatic tank gauging that tests
for the loss of product and conducts inventory control shall meet the following
requirements:
i. The automatic product level
monitor test shall detect a 0.2 gallon per hour leak rate, from any portion of the
tank that routinely contains product, when performing a test in one of the following
modes:
(1) In-tank static testing conducted with
passing results at least once every 30 days; or
(2) Continuous in-tank leak detection operating
either on an uninterrupted basis, or with a process that allows the system to gather
incremental measurements to ensure an accurate, passing test at least once every 30
days; and
ii. Inventory
control (or another test of equivalent performance) shall be conducted in accordance
with the requirements of
7:14B-6.5(a)1.
5. Testing or monitoring for vapors
within the soil gas of the excavation zone shall meet the following requirements:
i. The materials used as backfill shall be
sufficiently porous (for example, gravel, sand, crushed rock) to readily allow
diffusion of vapors from releases into the excavation area;
ii. The stored regulated substance, or a tracer
compound placed in the tank system, shall be sufficiently volatile to result in a
vapor level that is detectable by the monitoring devices located in the excavation
zone in the event of a release from the tank;
iii. The measurement of vapors by the monitoring
device shall not be rendered inoperative by the ground water, rainfall, soil
moisture or other known interferences so that a release could go undetected for more
than 30 calendar days;
iv. The level of
background contamination in the excavation zone shall not interfere with the method
used to detect releases from the tank;
v. The vapor monitors shall be designed and
operated to detect any significant increase in concentration above background of the
regulated substance stored in the tank system, a component or components of that
substance, or a tracer compound placed in the tank system;
vi. In the underground storage tank excavation
zone, the site shall be assessed to ensure compliance with the requirements in (a)5i
through iv and to establish the number and positioning of monitoring wells that will
detect releases within the excavation zone from any portion of the tank that
routinely contains product; and
vii.
Monitoring wells shall be clearly marked and secured to avoid unauthorized access
and tampering.
6. Testing or
monitoring for liquids floating on the ground water shall meet the following
requirements:
i. The regulated substance stored
shall be immiscible in water and has a specific gravity of less than one;
ii. Ground water shall never be more than 20 feet
from the ground surface and the hydraulic conductivity of the soil(s) between the
underground storage tank system and the monitoring wells or devices is not less than
0.01 cm/sec (for example, the soil should consist of gravels, coarse to medium
sands, coarse silts or other permeable materials);
iii. The slotted portion of the monitoring well
casing shall be designed to prevent migration of natural soils or filter pack into
the well and to allow entry of regulated substance on the water table into the well
under both high and low ground-water conditions;
iv. All monitoring systems using screen and casing
shall be constructed and permitted in accordance with the Subsurface and Percolating
Waters Act (N.J.S.A. 58:4A-4.1 et seq.) unless
constructed in the manner described in N.J.A.C.
7:14B-4.1(c) or sealed
from the ground surface to the top of the filter pack in accordance with
N.J.A.C.
7:14B-4.1(d);
v. Monitoring wells or devices shall intercept the
excavation zone or are as close to it as is technically feasible;
vi. The continuous monitoring devices or manual
methods used shall detect the presence of at least one-eighth of an inch of
free-phase non-aqueous phase liquid on top of the ground water in the monitoring
wells;
vii. Within and immediately below
the underground storage tank system excavation zone, the site shall be assessed to
ensure compliance with the requirements in (a)6i through v and to establish the
number and positioning of monitoring wells or devices that will detect releases from
any portion of the tank that routinely contains product; and
viii. Monitoring wells shall be clearly marked and
secured to avoid unauthorized access and tampering.
7. Interstitial monitoring between the underground
storage tank system and a secondary barrier immediately around or beneath it may be
used, but only if the monitoring system is designed, constructed, and installed to
detect a leak from any portion of the tank and/or piping that routinely contains
product and also meets one of the following requirements:
i. For double walled underground storage tank
systems, the sampling or testing method shall detect a leak through the inner wall
in any portion of the tank and/or piping that routinely contains product;
ii.For underground storage tank systems with a
secondary barrier within the excavation zone, the sampling or testing method used
shall detect a leak between the underground storage tank system and the secondary
barrier. The secondary barrier shall meet the following requirements:
(1) The secondary barrier shall consist of
artificially constructed material that is sufficiently thick and impermeable (at
least 10-6 cm/sec for the regulated substance stored) to direct a leak to the
monitoring point and permit its detection;
(2) The secondary barrier shall be compatible with
the regulated substance stored so that a leak from the underground storage tank
system shall not cause a deterioration of the barrier allowing a release to pass
through undetected;
(3) For cathodically
protected underground storage tank systems, the secondary barrier shall be installed
so that it does not interfere with the proper operation of the cathodic protection
system;
(4) The ground water, soil
moisture, or rainfall shall not render the testing or sampling method used
inoperative so that a release could go undetected for more than 30 calendar
days;
(5) The site shall be assessed to
ensure that the secondary barrier is always above the ground water and not in a
25-year flood plain, unless the barrier and monitoring designs are for use under
such conditions; and
(6) Monitoring
wells shall be clearly marked and secured to avoid unauthorized access and
tampering; or
iii. For tanks
with an internally fitted liner, an automated device shall detect a leak between the
inner wall of the tank and the liner, and the liner shall be compatible with the
substance stored.
8. Any
other type of release detection method, or combination of methods, including
statistical inventory reconciliation (SIR), can be used if the method can detect a
0.2 gallon per hour leak rate or a release of 150 gallons within a month with a
probability of detection of 0.95 and a probability of false alarm of 0.05.
i. Statistical inventory reconciliation release
detection methods based on the application of statistical principles to inventory
data shall, in addition to (a)8 above:
(1) Report
a quantitative result with a calculated leak rate;
(2) Use a threshold that does not exceed one-half
the minimum detectible leak rate; and
(3) Be conducted at least once every 30
days.
9. The
Department shall approve another method, through the issuance of a permit for a
substantial modification issued pursuant to N.J.A.C. 7:14B-10, if the owner and
operator can demonstrate that the method can detect a release as effectively as any
of the methods allowed in (a)3 through 8 above. In comparing methods, the Department
shall consider the size of release that the method can detect and the frequency and
reliability with which it can be detected. The owner and operator shall obtain a
permit issued by the Department pursuant to N.J.A.C. 7:14B-10 and comply with any
conditions imposed by the Department on its use to ensure the protection of human
health and the environment.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.