Ohio Admin. Code 4101:8-34-01 - Electrical
[Comment: When a reference is made within this rule to a federal statutory provision, an industry consensus standard, or any other technical publication, the specific date and title of the publication as well as the name and address of the promulgating agency are listed in rule 4101:8-44-01 of the Administrative Code. The application of the referenced standards shall be limited and as prescribed in section 102.5 of rule 4101:8-1-01 of the Administrative Code.]
ELECTRICAL
For the purposes of this Chapter, any reference in NFPA 70 to "one- and two-family dwellings" will include "one-, two- and three-family dwellings." Where the NFPA 70 requirement identifies a one-family dwelling or a two-family dwelling, a three-family dwelling is regulated as a "multi-family dwelling" (i.e. Section 210.52(E)(1)).
Exceptions:
1. A receptacle supplying only a
permanently installed fire alarm or burglar alarm system shall not be required
to have groundfault circuit-interrupter protection.
2.
Exception No 5: A single receptacle located to serve a
sump pump shall not be required to have ground-fault circuitinterrupter
protection when there is a duplex receptacle with ground-fault
circuit-interrupter protection within six (6) feet of the sump
pump.
3. Section
210.8(D) shall
be deleted.
If equipment supplied by an outlet covered under the requirements of this section is replaced, the outlet is to be supplied with GFCI protection.
Exception No. 1: GFCI protection is not required on lighting outlets other than those covered in 210.8(C)
Exception No. 2: GFCI protection is not required for listed HVAC equipment.
4. Section
210.12(A)
shall be modified to read:
All 120-volt single-phase, 15- and 20-ampere
branch circuits supplying outlets or devices installed in dwelling unit
kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens,
bedrooms, sun rooms, recreational rooms, closets, hallways, laundry rooms, or
similar rooms or areas shall be protected by any of the means described in
210.12(A)(1) through (6):
(l) A listed combination-type arc-fault
circuit interrupter, installed to provide protection of the entire branch
circuit.
(2) A listed branch/feeder-type AFCI
installed at the origin of the branchcircuit in combination with a listed
outlet branch-circuit type arc-fault circuit interrupter installed at the first
outlet box on the branch circuit. The first outlet box in the branch circuit
shall be marked to indicate that it is the first outlet of the
circuit.
(3) A listed supplemental arc protection
circuit breaker installed at the origin of the branch circuit in combination
with a listed outlet branch-circuit type arc-fault circuit interrupter
installed at the first outlet box on the branch circuit where all of the
following conditions are met:
a. The branch-circuit wiring shall be
continuous from the branchcircuit overcurrent device to the outlet
branch-circuit arc-fault circuit interrupter.
b. The maximum length of the branch-circuit
wiring from the branchcircuit overcurrent device to the first outlet shall not
exceed 15.2 m (50 ft.) for a 14 AWG conductor or 21.3 m (70 ft.) for a 12 AWG
conductor.
c. The first outlet box in the branch
circuit shall be marked to indicate that it is the first outlet of the
circuit.
(4) A listed outlet branch-circuit type
arc-fault circuit interrupter installed at the first outlet on the branch
circuit in combination with a listed branch-circuit overcurrent protective
device where all of the following conditions are met:
a. The branch-circuit wiring shall be
continuous from the branchcircuit overcurrent device to the outlet
branch-circuit arc-fault circuit interrupter.
b. The maximum length of the branch-circuit
wiring from the branchcircuit overcurrent device to the first outlet shall not
exceed 15.2 m (50 ft.) for a 14 AWG conductor or 21.3 m (70 ft.) for a 12 AWG
conductor.
c. The first outlet box in the branch
circuit shall be marked to indicate that it is the first outlet of the
circuit.
d. The combination of the branch-circuit
overcurrent device and outlet branch-circuit AFCI shall be identified as
meeting the requirements for a system combination-type AFCI and shall be listed
as such.
(5) If RMC, IMC, EMT, Type MC, or
steel-armored Type AC cables meeting the requirements of 250.118, metal
wireways, metal auxiliary gutters, and metal outlet and junction boxes are
installed for the portion of the branch circuit between the branch-circuit
overcurrent device and the first outlet, it shall be permitted to install a
listed outlet branchcircuit type AFCI at the first outlet to provide protection
for the remaining portion of the branch circuit.
(6) Where a listed metal or nonmetallic
conduit or tubing or Type MC cable is encased in not less than 50 mm (2 in.) of
concrete for the portion of the branch circuit between the branch-circuit
overcurrent device and the first outlet, it shall be permitted to install a
listed outlet branch-circuit type AFCI at the first outlet to provide
protection for the remaining portion of the branch circuit.
Exception No 1
: Where an individual branch circuit to a fire alarm
system installed in accordance with 760.41(B) or 760.121(B) is installed in
RMC, IMC, EMT, or steel-sheathed cable, Type AC or Type MC, meeting the
requirements of 250.118, with metal outlet and junction boxes, AFCI protection
shall be permitted to be omitted.
Exception No. 2: Branch circuits
supplying receptacle outlets installed to serve only the kitchen countertop
surfaces shall be permitted to be installed without arc-fault circuit
interrupter protection.
5. Section
210.64 shall be modified to
read:
At least one 125-volt, single-phase, 15- or
20-ampere-rated receptacle outlet shall be installed in an accessible location
within 7.5m (25 ft.) of the indoor electrical service equipment. The required
receptacle outlet shall be located within the same room or area as the service
equipment.
Exception No. 1: The receptacle outlet shall
not be required to be installed in one-, two-,
or three-
family dwellings.
Exception No. 2: Where the service voltage
is greater than 120 volts to ground, a receptacle outlet shall not be required
for services dedicated to equipment covered in Articles 675 and
682.
EMERGENCY AND STANDBY POWER SYSTEMS
Notes
Promulgated Under: 119.03
Statutory Authority: 3781.10(A)(1)
Rule Amplifies: 3781.01, 3781.06, 3781.10, 3781.11, 3791.04, 4740.14
Prior Effective Dates: 01/01/2013, 01/01/2016, 07/01/2019
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.