SECTION 702
INTERIOR COVERING
702.1
General.
Interior coverings or wall finishes shall
be installed in accordance with this chapter and Table 702.1(1), Table
702.1(2), Table 702.1(3) and Table 702.3.5. Interior masonry veneer shall
comply with the requirements of Section 703.7.1 for support and Section 703.7.4
for anchorage, except an airspace is not required. Interior finishes and
materials shall conform to the flame spread and smoke-development requirements
of Section 302.9.
TABLE 702.1(1)
THICKNESS OF PLASTER
|
PLASTER BASE
|
FINISHED THICKNESS OF PLASTER
FROM FACE OF LATH, MASONRY, CONCRETE (inches)
|
|
|
Gypsum
Plaster
|
Cement
Plaster
|
|
Expanded metal lath
|
5/8,
minimuma
|
5/8,
minimuma
|
|
Wire lath
|
5/8,
minimuma
|
3/4, minimum
(interior)b 7/8, minimum
(exterior)b
|
|
Gypsum
lathg
|
1/2, minimum
|
3/4, minimum
(interior)b
|
|
Masonry
wallsc
|
1/2, minimum
|
1/2, minimum
|
|
Monolithic concrete
wallsc, d
|
5/8,
maximum
|
7/8,
maximum
|
|
Monolithic concrete
ceilingsc, d
|
3/8,
maximume
|
1/2, maximum
|
|
Gypsum veneer basef,
g
|
1/16,
minimum
|
3/4, minimum
(interior)b
|
|
Gypsum
sheathingg
|
-
|
3/4, minimum
(interior)b 7/8, minimum
(exterior)b
|
For SI: 1 inch = 25.4 mm.
a.
Where measured
from back plane of expanded metal lath, exclusive of ribs, or self-furring
lath, plaster thickness shall be3/4 inch minimum.
b.
Where measured
from face of support or backing.
c.
Because masonry
and concrete surfaces vary in plane, thickness of plaster need not be
uniform.
d.
Where applied over a liquid bonding agent, finish coat
shall be permitted to be applied directly to concrete surface.
e.
Approved
acoustical plaster shall be permitted to be applied directly to concrete or
over base coat plaster, beyond the maximum plaster thickness
shown.
f.
Attachment shall be in accordance with Table
702.3.5.
g.
Where gypsum board is used as a base for cement
plaster, a water-resistive barrier complying with Section 703.2 shall be
provided.
TABLE 702.1(2)
GYPSUM PLASTER
PROPORTIONSa
|
NUMBER
|
COAT
|
PLASTER BASE OR
LATH
|
MAXIMUM VOLUME AGGREGATE PER 100
POUNDS NEAT PLASTERb (cubic
feet)
|
|
Damp Loose
Sanda
|
Perlite or
Vermiculitec
|
|
Two-coat
|
Base coat
|
Gypsum lath
|
2.5
|
2
|
|
work
|
Base coat
|
Masonry
|
3
|
3
|
|
|
First coat
|
Lath
|
2d
|
2
|
|
Three-coat
|
Second coat
|
Lath
|
3d
|
2e
|
|
work
|
First and second coats
|
Masonry
|
3
|
3
|
For SI: 1 inch = 25.4 mm, 1 cubic foot = 0.0283
m3, 1 pound = 0.454 kg.
a.
Wood-fibered
gypsum plaster shall be mixed in the proportions of 100 pounds of gypsum to not
more than 1 cubic foot of sand where applied on masonry or
concrete.
b.
Where determining the amount of aggregate in set
plaster, a tolerance of 10 percent shall be allowed.
c.
Combinations of
sand and lightweight aggregate shall be permitted to be used, provided the
volume and weight relationship of the combined aggregate to gypsum plaster is
maintained.
d.
If used for both first and second coats, the volume of
aggregate shall be permitted to be 2.5 cubic feet.
e.
Where plaster is 1
inch or more in total thickness, the proportions for the second coat may be
increased to 3 cubic feet.
TABLE 702.1(3)
CEMENT PLASTER PROPORTIONS, PARTS BY
VOLUME
|
|
|
CEMENTITIOUS
MATERIALS
|
|
|
COAT
|
CEMENT PLASTER
TYPE
|
Portland Cement Type I, II or
III; Blended Hydraulic Cement Type IP, I (S < 70), IL, or IT (S < 70); or
Hydraulic Cement Type GU, HE, MS, HS or MH
|
Plastic
Cement
|
Masonry Cement Type M, S or
N
|
Lime
|
VOLUME OF AGGREGATE PER SUM OF
SEPARATE VOLUMES OF CEMENTITIOUS
MATERIALSb
|
|
First
|
Portland or blended
|
1
|
-
|
-
|
3/4 -
11/2a
|
21/2 - 4
|
|
Masonry
|
-
|
|
1
|
-
|
21/2 - 4
|
|
Plastic
|
-
|
1
|
-
|
-
|
21/2 - 4
|
|
Second
|
Portland or blended
|
1
|
-
|
-
|
3/4 - 11/2
|
3 - 5
|
|
Masonry
|
-
|
|
1
|
-
|
3 - 5
|
|
Plastic
|
-
|
1
|
-
|
-
|
3 - 5
|
|
Finish
|
Portland or blended
|
1
|
-
|
-
|
11/2 - 2
|
11/2 - 3
|
|
Masonry
|
-
|
-
|
1
|
-
|
11/2 - 3
|
|
Plastic
|
-
|
1
|
|
-
|
11/2 - 3
|
For SI: 1 inch = 25.4 mm, 1 pound = 0.454
kg.
a.
Lime by volume of 0 to3/4 shall be used where the
plaster will be placed over low-absorption surfaces such as dense clay tile or
brick.
b.
The same or greater sand proportion shall be used in
the second coat than used in the first coat.
702.2
Interior
plaster.
702.2.1
Gypsum plaster.
Gypsum
plaster materials shall conform to ASTM C5, C22, C28, C35, C59, C61, C587,
C631, C847, C933, C1032 and C1047, and shall be installed or applied in
compliance with ASTM C841, C842 and C843. Gypsum lath or gypsum base for veneer
plaster shall conform to ASTM C1396 and shall be installed in compliance with
ASTM C844. Plaster shall be not less than three coats where applied over metal
lath and not less than two coats where applied over other bases permitted by
this section, except that veneer plaster shall be applied in one coat not to
exceed3/16 inch ( 4.76 mm) thickness, provided the
total thickness is in accordance with Table 702.1(1).
702.2.2
Cement
plaster.
Cement plaster materials shall
conform to ASTM C91 (Type M, S or N), C150 (Types I, II and III), C595 [Types
IP, I (PM), IS and I (SM), C847, C897, C933, C1032, C1047 and C1328, and shall
be installed or applied in compliance with ASTM C926 and C1063. Gypsum lath
shall conform to ASTM C1396. Plaster shall be not less than three coats where
applied over metal lath and not less than two coats where applied over other
bases permitted by this section.
702.2.2.1
Application.
Each coat
shall be kept in a moist condition for not less than 24 hours prior to
application of the next coat.
Exception:
Applications installed in accordance with ASTM
C926.
702.2.2.2
Curing.
The
finish coat for two-coat cement plaster shall not be applied sooner than 48
hours after application of the first coat. For three-coat cement plaster, the
second coat shall not be applied sooner than 24 hours after application of the
first coat. The finish coat for three-coat cement plaster shall not be applied
sooner than 48 hours after application of the second coat.
702.2.3
Support.
Support
spacing for gypsum or metal lath on walls or ceilings shall not exceed 16
inches (406 mm) for3/8 -inch-thick ( 9.5 mm) or 24
inches (610 mm) for1/2 -inch-thick ( 12.7 mm) plain gypsum lath. Gypsum
lath shall be installed at right angles to support framing with end joints in
adjacent courses staggered by not less than one framing space.
702.3
Gypsum board and gypsum panel products.
702.3.1
Materials.
Gypsum board
and gypsum panel product materials and accessories shall conform to ASTM C22,
C475, C514, C1002, C1047, C1177, C1178, C1278, C1396, C1658 or C1766 and shall
be installed in accordance with the provisions of this section. Adhesives for
the installation of gypsum board and gypsum panel products shall conform to
ASTM C557.
02.3.1.1
Adhesives.
Expandable foam adhesives for the installation of gypsum
board and gypsum panel products shall conform to ASTM C6464. Other adhesives
for the installation of gypsum board and gypsum panel products shall conform to
ASTM C557. Supports and fasteners used to attach gypsum board and gypsum panel
products shall comply with Table 702.3.5 or other approved
method.
702.3.2
Wood framing.
Wood
framing supporting gypsum board and gypsum panel products shall be not less
than 2 -inches (51 mm) nominal thickness in the least dimension except that
wood furring strips not less than 1 -inch by 2-inch (25 mm by 51 mm) nominal
dimension shall be permitted to be used over solid backing or framing spaced
not more than 24 -inches (610 mm) on center.
702.3.3
Cold-formed steel framing.
Cold-formed steel framing supporting gypsum board and gypsum
panel products shall be not less than 11/4 -inches (32 mm) wide in the
least dimension. Nonload-bearing cold-formed steel framing shall comply with
AISI S220. Load-bearing cold-formed steel framing shall comply with AISI
S240.
702.3.4
Insulating concrete form walls.
Foam plastics for insulating concrete form walls
constructed in accordance with Sections 404.1.2 and 608 on the interior of
habitable spaces shall be protected in accordance with Section 316.4. Use of
adhesives in conjunction with mechanical fasteners is permitted. Adhesives used
for interior and exterior finishes shall be compatible with the insulating form
materials.
702.3.5
Application.
Supports
and fasteners used to attach gypsum board and gypsum panel products shall
comply with Table 702.3.5. Gypsum sheathing shall be attached to exterior walls
in accordance with Table 602.3(1). Gypsum board and gypsum panel products shall
be applied at right angles or parallel to framing members. All edges and ends
of gypsum board and gypsum panel products shall occur on the framing members,
except those edges and ends that are perpendicular to the framing members.
Interior gypsum board shall not be installed where it is directly exposed to
the weather or to water.
TABLE 702.3.5
MINIMUM THICKNESS AND APPLICATION OF
GYPSUM BOARD AND GYPSUM PANEL PRODUCTS
|
THICKNESS OF GYPSUM BOARD OR
GYPSUM PANEL PRODUCTS (inches)
|
APPLICATION
|
ORIENTATION OF GYPSUM BOARD OR
GYPSUM PANEL PRODUCTS TO FRAMING
|
MAXIMUM SPACING OF FRAMING
MEMBERS (inches o.c.)
|
MAXIMUM SPACING OF FASTENERS
(inches)
Nailsa
|
Screwsb
|
SIZE OF NAILS FOR APPLICATION TO
WOOD FRAMINGc
|
|
Application without
adhesive
|
|
|
|
3/8
|
Ceilingd
|
Perpendicular
|
16
|
7
|
12
|
13 gage, 11/4" long,
19/64 head; 0.098 " diameter, 11/4"
long, annular-ringed;
|
|
Wall
|
Either direction
|
16
|
8
|
16
|
or 4d cooler nail, 0.080 " diameter,
13/8" long, 732"
head.
|
|
1/2
|
Ceiling
|
Either direction
|
16
|
7
|
12
|
13 gage,
13/8" long, 1
9/64" head;
|
|
Ceilingd
|
Perpendicular
|
24
|
7
|
12
|
0.098 " diameter, 11/4" long,
annular-ringed;
|
|
Wall
|
Either direction
|
24
|
8
|
12
|
5d cooler nail, 0.086 " diameter,
15/8 long, "15/64" head;
or gypsum board nail,
|
|
Wall
|
Either direction
|
16
|
8
|
16
|
0.086 " diameter,
15/8" long,
9/ 32" head.
|
|
5/8
|
Ceiling
|
Either direction
|
16
|
7
|
12
|
13 gage,
15/8" long,
1964/" head; 0.098 " diameter,
13/8" long, annular-ringed;
|
|
Ceiling
|
Perpendicular
|
24
|
7
|
12
|
6d cooler nail, 0.092"
diameter, 17/8" long,
1/4" head; or gypsum board nail, 0.0915 diameter,
17/8" long,
19/64" head.
|
|
Type X at garage ceiling beneath
habitable rooms
|
Perpendicular
|
24
|
6
|
6
|
17/8" long
6d coated nails or equivalent drywall screws. Screws shall comply with Section
702.3.5.1
|
|
Wall
|
Either direction
|
24
|
8
|
12
|
13 gage,
15/8" long,
19/64" head; 0.098 diameter,
13/8" long, annular-ringed; 6d cooler nail, 0.092 "
diameter, 17/8" long,
|
|
Wall
|
Either direction
|
16
|
8
|
16
|
1/4" head; or gypsum board nail,
0.0915 " diameter,
17/8" long,
19/64" head.
|
|
Application with
adhesive
|
|
3/8
|
Ceilingd
|
Perpendicular
|
16
|
16
|
16
|
Same as above
for3/8" gypsum board and
|
|
|
Wall
|
Either direction
|
16
|
16
|
24
|
gypsum panel products.
|
|
|
Ceiling
|
Either direction
|
16
|
16
|
16
|
Same as above for
1/2" and
5/8" gypsum board and gypsum panel
products, respectively.
|
|
1/2 or
5/8
|
Ceilingd
|
Perpendicular
|
24
|
12
|
16
|
|
|
Wall
|
Either direction
|
24
|
16
|
24
|
|
3
|
Ceiling
|
Perpendicular
|
16
|
16
|
16
|
Base ply nailed as above for1/2"
gypsum installed with adhesive.
|
|
8
|
Wall
|
Either direction
|
24
|
24
|
24
|
For SI: 1 inch = 25.4 mm.
a.
For application
without adhesive, a pair of nails spaced not less than 2 inches apart or more
than 21/2 inches apart shall be permitted to be used with the pair of
nails spaced 12 inches on center.
b.
Screws shall be in
accordance with Section 702.3.5.1. Screws for attaching gypsum board or gypsum
panel products to structural insulated panels shall penetrate the wood
structural panel facing not less than7/16
inch.
c.
Where cold-formed steel framing is used with a
clinching design to receive nails by two edges of metal, the nails shall be not
less than
5/8 inch longer than the gypsum board or gypsum
panel product thickness and shall have ringed shanks. Where the cold-formed
steel framing has a nailing groove formed to receive the nails, the nails shall
have barbed shanks or be 5d, 131/2 gage,
15/8 inches long,
15/64-inch head for 1/2-inch
gypsum board or gypsum panel product; and 6d, 13 gage,
17/8 inches long,
15/64-inch head
for5/8-inch gypsum board or gypsum panel
product.
d.
Three-eighths-inch-thick single-ply gypsum board or
gypsum panel product shall not be used on a ceiling where a water-based
textured finish is to be applied, or where it will be required to support
insulation above a ceiling. On ceiling applications to receive a water-based
texture material, either hand or spray applied, the gypsum board or gypsum
panel product shall be applied perpendicular to framing. Where applying a
water-based texture material, the minimum gypsum board thickness shall be
increased from3/8 inch to1/2 inch for 16-inch
on center framing, and from1/2 inch to5/8 inch
for 24-inch on center framing or 1/2-inch sag-resistant gypsum ceiling
board shall be used.
702.3.5.1
Screw
fastening.
Screws for attaching gypsum
board and gypsum panel products to wood framing shall be Type W or Type S in
accordance with ASTM C1002 and shall penetrate the wood not less than
5/8 inch ( 15.9 mm). Gypsum board and gypsum panel
products shall be attached to cold-formed steel framing with minimum No. 6
screws. Screws for attaching gypsum board and gypsum panel products to
cold-formed steel framing less than 0.033 inch (1 mm) thick shall be Type S in
accordance with ASTM C1002 or bugle head style in accordance with ASTM C1513
and shall penetrate the steel not less than3/8 inch
( 9.5 mm). Screws for attaching gypsum board and gypsum panel products to
cold-formed steel framing 0.033 inch to 0.112 inch (1 mm to 3 mm) thick shall
be in accordance with ASTM C954 or bugle head style in accordance with ASTM
C1513. Screws for attaching gypsum board and gypsum panel products to
structural insulated panels shall penetrate the wood structural panel facing
not less than7/16 inch ( 11.1 mm).
702.3.6
Horizontal gypsum board diaphragm ceilings.
Gypsum board and gypsum panel products
shall be permitted on wood joists to create a horizontal diaphragm in
accordance with Table 702.3.6. Gypsum board and gypsum panel products shall be
installed perpendicular to ceiling framing members. End joints of adjacent
courses of board and panels shall not occur on the same joist. The maximum
allowable diaphragm proportions shall be 11/2:1 between shear resisting
elements. Rotation or cantilever conditions shall not be permitted. Gypsum
board or gypsum panel products shall not be used in diaphragm ceilings to
resist lateral forces imposed by masonry or concrete construction. Perimeter
edges shall be blocked using wood members not less than 2-inch by 6-inch (51 mm
by 152 mm) nominal dimension. Blocking material shall be installed flat over
the top plate of the wall to provide a nailing surface not less than 2 inches
(51 mm) in width for the attachment of the gypsum board or gypsum panel
product.
TABLE 702.3.6
SHEAR CAPACITY FOR HORIZONTAL WOOD-FRAMED
GYPSUM BOARD DIAPHRAGM CEILING ASSEMBLIES
|
MATERIAL
|
THICKNESS OF MATERIAL (min.)
(inch)
|
SPACING OF FRAMING MEMBERS (max.)
(inch)
|
SHEAR VALUEa,
b(plf of ceiling)
|
MINIMUM FASTENER
SIZEc,
d
|
|
Gypsum board or gypsum panel
product
|
1/2
|
16 o.c.
|
90
|
5d cooler or wallboard nail; 15/8-inch
long; 0.086 -inch shank; 15/64-inch head
|
|
Gypsum board or gypsum panel
product
|
1/2
|
24 o.c.
|
70
|
5d cooler or wallboard nail; 15/8-inch
long; 0.086 -inch shank; 15/64-inch head
|
For SI: 1 inch = 25.4 mm, 1 pound per linear
foot = 1.488 kg/m.
a.
Values are not cumulative with other horizontal
diaphragm values and are for short-term loading caused by wind or seismic
loading. Values shall be reduced 25 percent for normal loading.
b.
Deleted
c.
11/4-inch,
No. 6 Type S or W screws shall be permitted to be substituted for the listed
nails.
d.
Fasteners shall be spaced not more than 7 inches on
center at all supports, including perimeter blocking, and not less
than3/8 inch from the edges and ends of the gypsum
board.
702.3.7
Water-resistant gypsum backing board.
Gypsum board used as the base or backer
for adhesive application of ceramic tile or other required nonabsorbent finish
material shall conform to ASTM C1178, C1278 or C1396. Use of water-resistant
gypsum backing board shall be permitted on ceilings. Water-resistant gypsum
board shall not be installed over a Class I or II vapor retarder in a shower or
tub compartment. Cut or exposed edges, including those at wall intersections,
shall be sealed as recommended by the manufacturer.
702.3.7.1
Limitations.
Water-resistant gypsum backing board shall not be used where
there will be direct exposure to water, or in areas subject to continuous high
humidity.
702.4
Ceramic
tile.
702.4.1
General.
Ceramic tile
surfaces shall be installed in accordance with ANSI A 108.1, A 108.4, A 108.5,
A 108.6, A 108.11, A 118.1, A 118.3, A 136.1 and A 137.1.
702.4.2
Backer
boards.
Materials used as backers for wall
tile in tub and shower areas and wall panels in shower areas shall be of
materials listed in Table 702.4.2, and installed in accordance with the
manufacturer's recommendations.
TABLE 702.4.2
BACKER BOARD
MATERIALS
|
MATERIAL
|
STANDARD
|
|
Glass mat gypsum backing
panel
|
ASTM C1178
|
|
Fiber-reinforced gypsum
panels
|
ASTM C1278
|
|
Nonasbestos fiber-cement backer
board
|
ASTM C1288 or ISO 8336, Category
C
|
|
Nonasbestos fiber mat-reinforced
cementitious backer units
|
ASTM C1325
|
702.5
Other
finishes.
Wood veneer paneling and
hardboard paneling shall be placed on wood or cold-formed steel framing spaced
not more than 16 inches (406 mm) on center. Wood veneer and hard board paneling
less than 1/4-inch (6 mm) nominal thickness shall not have less than a
3/8-inch (10 mm) gypsum board or gypsum panel
product backer. Wood veneer paneling not less than 1/4-inch (6 mm) nominal
thickness shall conform to ANSI/HPVA HP-1. Hardboard paneling shall conform to
CPA/ANSI A 135.5.
702.6
Wood shakes and shingles.
Wood shakes and shingles shall conform to CSSB
Grading Rules for Wood Shakes and Shingles and shall be
permitted to be installed directly to the studs with maximum 24 inches (610 mm)
on-center spacing.
702.6.1
Attachment.
Nails,
staples or glue are permitted for attaching shakes or shingles to the wall, and
attachment of the shakes or shingles directly to the surface shall be permitted
provided the fasteners are appropriate for the type of wall surface material.
Where nails or staples are used, two fasteners shall be provided and shall be
placed so that they are covered by the course above.
702.6.2
Furring
strips.
Where furring strips are used,
they shall be 1 inch by 2 inches or 1 inch by 3 inches (25 mm by 51 mm or 25 mm
by 76 mm), spaced a distance on center equal to the desired exposure, and shall
be attached to the wall by nailing through other wall material into the
studs.
702.7
Vapor retarders.
Class I or II vapor retarders are required on the interior
side of frame walls in Climate Zones 5, 6, 7, 8 and Marine 4.
Exceptions:
1.
Basement
walls.
2.
Below-grade portion of any wall.
3.
Construction where
moisture or its freezing will not damage the materials.
702.7.1
Class
III vapor retarders.
Class III vapor
retarders shall be permitted where any one of the conditions in Table 702.7.1
is met.
TABLE 702.7.1
CLASS III VAPOR
RETARDERS
|
CLIMATE ZONE
|
CLASS III VAPOR RETARDERS
PERMITTED FOR:a
|
|
5
|
Vented cladding over wood structural
panels.
Vented cladding over
fiberboard.
Vented cladding over
gypsum.
|
|
|
Continuous insulation with
R-value> 5 over 2 × 4 wall.
Continuous insulation with
R-value> 7.5 over 2 × 6 wall.
|
|
6
|
Vented cladding over
fiberboard.
Vented cladding over
gypsum.
Continuous insulation with
R-value > 7.5 over 2 × 4 wall.
Continuous insulation with
R-value > 11.25 over 2 × 6 wall.
|
For SI: 1 pound per cubic foot = 16
kg/m3.
a.
Spray foam with a maximum permeance of 1.5 perms at the
installed thickness, applied to the interior cavity side of wood structural
panels, fiberboard, insulating sheathing or gypsum is deemed to meet the
continuous insulation requirement where the spray foam R-value
meets or exceeds the specified continuous insulation
R-value.
702.7.2
Material vapor retarder class.
The vapor retarder class shall be based on the
manufacturer's certified testing or a tested assembly.
The following shall be deemed to meet the class
specified:
1.
Class I: Sheet polyethylene, on perforated aluminum
foil.
2.
Class II: Kraft-faced fiberglass batts.
3.
Class III: Latex
or enamel paint.
702.7.3
Minimum
clear airspaces and vented openings for vented cladding.
For the purposes of this section, vented
cladding shall include the following minimum clear airspaces. Other openings
with the equivalent vent area shall be permitted.
1.
Vinyl
polypropylene or horizontal aluminum siding applied over a weather-resistive
barrier as specified in Table 703.3(1).
2.
Brick veneer with
a clear airspace as specified in Table 703.8.4.
3.
Other approved
vented claddings.
SECTION 703
EXTERIOR COVERING
703.1
General.
Exterior walls shall provide the building
with a weather-resistant exterior wall envelope. The exterior wall envelope
shall include flashing as described in Section 703.4.
Exception:
Log walls designed and constructed in accordance with the
provisions of ICC 400.
703.1.1
Water resistance.
The exterior wall envelope shall be designed and constructed
in a manner that prevents the accumulation of water within the wall assembly by
providing a water-resistant barrier behind the exterior cladding as required by
Section 703.2 and a means of draining to the exterior water that penetrates the
exterior cladding.
Exceptions:
1.
A
weather-resistant exterior wall envelope shall not be required over concrete or
masonry walls designed in accordance with Chapter 6 and flashed in accordance
with Section 703.4 or 703.8.
2.
Compliance with
the requirements for a means of drainage, and the requirements of Sections
703.2 and 703.4, shall not be required for an exterior wall envelope that has
been demonstrated to resist wind-driven rain through testing of the exterior
wall envelope, including joints, penetrations and intersections with dissimilar
materials, in accordance with ASTM E331 under the following
conditions:
2.1.
Exterior wall envelope test assemblies shall include at
least one opening, one control joint, one wall/eave interface and one wall
sill. All tested openings and penetrations shall be representative of the
intended end-use configuration.
2.2.
Exterior wall
envelope test assemblies shall be at least 4 feet by 8 feet (1219 mm by 2438
mm) in size.
2.3.
Exterior wall assemblies shall be tested at a minimum
differential pressure of 6.24 pounds per square foot (299 Pa).
2.4.
Exterior wall
envelope assemblies shall be subjected to the minimum test exposure for a
minimum of 2 hours.
The exterior wall envelope design shall be
considered to resist wind-driven rain where the results of testing indicate
that water did not penetrate control joints in the exterior wall envelope,
joints at the perimeter of openings penetration or intersections of
terminations with dissimilar materials.
703.1.2
Wind
resistance.
Wall coverings, backing
materials and their attachments shall be capable of resisting wind loads in
accordance with Tables 301.2(2) and 301.2(3). Wind-pressure resistance of the
siding, soffit and backing materials shall be determined by ASTM E330 or other
applicable standard test methods. Where wind-pressure resistance is determined
by design analysis, data from approved design standards and analysis conforming
to generally accepted engineering practice shall be used to evaluate the
siding, soffit and backing material and its fastening. All applicable failure
modes including bending rupture of siding, fastener withdrawal and fastener
head pull-through shall be considered in the testing or design analysis. Where
the wall covering, soffit and backing material resist wind load as an assembly,
use of the design capacity of the assembly shall be permitted.
703.2
Water-resistive barrier.
One layer of No. 15 asphalt felt, free from holes and
breaks, complying with ASTM D226 for Type 1 felt or other approved
water-resistive barrier shall be applied over studs or sheathing of all
exterior walls. No.15 asphalt felt shall be applied horizontally, with the
upper layer lapped over the lower layer not less than 2 inches (51 mm). Where
joints occur, felt shall be lapped not less than 6 inches (152 mm). Other
approved materials shall be installed in accordance with the water-resistive
barrier manufacturer's installation instructions. The No. 15 asphalt felt or
other approved water-resistive barrier material shall be continuous to the top
of walls and terminated at penetrations and building appendages in a manner to
meet the requirements of the exterior wall envelope as described in Section
703.1.
703.3
Wall covering nominal thickness and attachments.
The nominal thickness and attachment of
exterior wall coverings shall be in accordance with Table 703.3(1), the wall
covering material requirements of this section, and the wall covering
manufacturer's installation instructions. Cladding attachment over foam
sheathing shall comply with the additional requirements and limitations of
Sections 703.15 through
703.17. Nominal material
thicknesses in Table 703.3(1) are based on a maximum stud spacing of 16 inches
(406 mm) on center. Where specified by the siding manufacturer's instructions
and supported by a test report or other documentation, attachment to studs with
greater spacing is permitted. Fasteners for exterior wall coverings attached to
wood framing shall be in accordance with Section 703.3.3 and Table 703.3(1).
Exterior wall coverings shall be attached to cold-formed steel light frame
construction in accordance with the cladding manufacturer's installation
instructions, the requirements of Table 703.3(1) using screw fasteners
substituted for the nails specified in accordance with Table 703.3(2), or an
approved design.
TABLE 703.3(1)
SIDING MINIMUM ATTACHMENT AND MINIMUM
THICKNESS
|
SIDING
MATERIAL
|
NOMINAL THICKNESS
(inches)
|
JOINT
TREATMENT
|
TYPE OF SUPPORTS FOR THE SIDING
MATERIAL AND FASTENERS
|
|
Wood or wood structural panel
sheathing into stud
|
Fiberboard sheathing into
stud
|
Gypsum sheathing into
stud
|
Foam plastic sheathing into
stud1
|
Direct to
studs
|
Number or spacing of
fasteners
|
|
Anchored veneer: brick, concrete,
masonry or stone (see Section 703.8)
|
2
|
Section 703.8
|
Section 703.8
|
|
Adhered veneer: concrete, stone or
masonry (see Section 703.12)
|
-
|
Section
703.12
|
Section
703.12
|
|
Fiber cement siding
|
Panel siding (see Section
703.10.1)
|
5/16
|
Section 703.10.1
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ")
|
4d common (11/2" x 0.099
")
|
6" panel edges 12" inter.
sup.
|
|
Lap siding (see Section
703.10.2)
|
5/16
|
Section 703.10.2
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ")
|
6d common (2"x 0.113 ") or 11 gage
roofing nail
|
Note f
|
|
Hardboard panel siding (see Section
703.5)
|
7/16
|
-
|
0.120 " nail (shank) with 0.225 "
head
|
0.120 " nail (shank) with 0.225 "
head
|
0.120 " nail (shank) with 0.225 "
head
|
0.120 " nail (shank) with 0.225 "
head
|
0.120 " nail (shank) with 0.225 "
head
|
6" panel edges 12" inter.
sup.d
|
|
Hardboard lap siding (see Section
703.5)
|
7/16
|
Note e
|
0.099 " nail (shank) with 0.240 "
head
|
0.099 " nail (shank) with 0.240 "
head
|
0.099 " nail (shank) with 0.240 "
head
|
0.099 " nail (shank) with 0.240 "
head
|
0.099 " nail (shank) with 0.240 "
head
|
Same as stud spacing 2 per
bearing
|
|
Horizontal
aluminuma
|
Without insulation
|
0.019
b
|
Lap
|
Siding nail 11/2"x 0.120
"
|
Siding nail 2"x 0.120 "
|
Siding nail 2"× 0.120
"
|
Siding nail
h 11/2" x 0.120 "
|
Not allowed
|
Same as stud spacing
|
|
0.024
|
Lap
|
Siding nail 11/2" x 0.120
"
|
Siding nail 2"x 0.120 "
|
Siding nail 2"× 0.120 "
|
Siding nail
h 11/2" x 0.120 "
|
Not allowed
|
|
With insulation
|
0.019
|
Lap
|
Siding nail 11/2" x 0.120
"
|
Siding nail 21/2" x 0.120
"
|
Siding nail 21/2" x 0.120
"
|
Siding nail
h 11/2" x 0.120 "
|
Siding nail 11/2" x 0.120
"
|
|
Insulated vinyl
sidingj
|
0.035
(vinyl siding layer
only)
|
Lap
|
0.120 nail (shank) with a 0.313 head
or 16-gage Crownh,
i
|
0.120 nail (shank) with a 0.313 head
or 16-gage Crownh
|
0.120 nail (shank) with a 0.313 head
or 16-gage Crown
h
|
0.120 nail (shank) with a 0.313 head
Section 703.11.2
|
Not allowed
|
16 inches on center or specified by
manufacturer instructions, test report or other sections of this
code
|
|
Particleboard panels
|
3/8
|
-
|
6d box nail (2" x 0.099
")
|
6d box nail (2" x 0.099
")
|
6d box nail (2" x 0.099
")
|
6d box nail (2" x 0.099
")
|
Not allowed
|
6" panel edges 12" inter.
sup.
|
|
1/2
|
-
|
6d box nail (2" x 0.099
n)
|
6d box nail (2" x 0.099
")
|
6d box nail (2" x 0.099
")
|
6d box nail (2"x 0.099
")
|
6d box nail (2"x 0.099
n)
|
|
5/8
|
-
|
6d box nail (2"x 0.099
")
|
8d box nail (21/2x 0.113
")
|
8d box nail (21/2× 0.113
)
|
6d box nail (2" x 0.099
")
|
6d box nail (2" x 0.099
")
|
|
Polypropylene siding
k
|
Not applicable
|
Lap
|
Section 703.14.1
|
Section 703.14.1
|
Section 703.14.1
|
Section 703.14.1
|
Not allowed
|
As specified by the manufacturer
instructions, test report or other sections of this code
|
|
Steel
c
|
29 ga.
|
Lap
|
Siding nail
(13/4" 0.113 ")
Staple-13/4'
|
Siding nail (23/4" 0.113
")Staple-21/2"
|
Siding nail (21/2 x 0.113)
Staple. 21/4
|
Siding nail (13/4 "x 0.113 ")
Staple-13/4"
|
Not allowed
|
Same as stud spacing
|
|
Vinyl siding (see Section
703.11)
|
0.035
|
Lap
|
0.120 " nail (shank) with a 0.313 "
head or 16-gage staple
with3/8- to 1/2-inch
crownh, i
|
0.120 " nail (shank) with a 0.313 "
head or 16-gage staple with
3
/8- to
1
/2-inch crown
h
|
0.120 " nail (shank) with a 0.313 "
head or 16-gage staple with
3/8- to
1/2-inch crown
h
|
0.120 "nail (shank) with a 0.313 head
Section 703.11.2
|
Not allowed
|
16 inches on center or as specified
by the manufacturer instructions or test report
|
|
Wood siding (see Section 703.5
)
|
Wood rustic, drop
|
3/8
min.
|
Lap
|
6d box or siding nail (2"x 0.099
")
|
6d box or siding nail (2"x 0.099
")
|
6d box or siding nail (2"x 0.099
")
|
6d box or siding nail (2"x 0.099
")
|
8d box or siding nail (21/2" 0.113 ")
Staple-2"
|
Face nailing up to 6" widths, 1 nail
per bearing; 8" widths and over, 2 nails per bearing
|
|
Shiplap
|
19/32
average
|
Lap
|
|
Bevel
|
7/16
|
|
Butt tip
|
3/16
|
Lap
|
|
Wood structural panel ANSI/APA
PRP-210 siding (exterior grade) (see Section 703.5)
|
3
/8 -1/2
|
Note e
|
2"x 0.099 "siding nail
|
21/2"x 0.113 " siding nail
|
21/2"x 0.113 " siding
nail
|
21/2"x 0.113 " siding nail
|
2"x 0.099 " siding nail
|
6" panel edges 12" inter.
sup.
|
|
Wood structural panel lap siding (see
Section 703.5)
|
3/8
-1/2
|
Note e Note g
|
2"x 0.099 "siding nail
|
21/2"x 0.113 " siding nail
|
21/2"x 0.113 " siding
nail
|
21/2"x 0.113 " siding nail
|
2"x 0.099 " siding nail
|
8" along bottom edge
|
For SI: 1 inch = 25.4 mm.
a.
Aluminum nails
shall be used to attach aluminum siding.
b.
Aluminum ( 0.019
inch) shall be unbacked only where the maximum panel width is 10 inches and the
maximum flat area is 8 inches. The tolerance for aluminum siding shall be +
0.002 inch of the nominal dimension.
c.
Shall be of
approved type.
d.
Where used to resist shear forces, the spacing must be
4 inches at panel edges and 8 inches on interior supports.
e.
Vertical end
joints shall occur at studs and shall be covered with a joint cover or shall be
caulked.
f.
Face nailing: one 6d common nail through the
overlapping planks at each stud. Concealed nailing: one 11-gage 11/2
-inch-long galv. roofing nail through the top edge of each plank at each stud
in accordance with the manufacturer's installation
instructions.
g.
Vertical joints, if staggered, shall be permitted to be
away from studs if applied over wood structural panel
sheathing.
h.
Minimum fastener length must be sufficient to penetrate
sheathing other nailable substrate and framing a total of a minimum of
11/4 inches or in accordance with the manufacturer's installation
instructions.
i.
Where specified by the manufacturer's instructions and
supported by a test report, fasteners are permitted to penetrate into or fully
through nailable sheathing or other nailable substrate of minimum thickness
specified by the instructions or test report, without penetrating into
framing.
j.
Insulated vinyl siding shall comply with ASTM
D7793.
k.
Polypropylene siding shall comply with ASTM
D7254.
l.
Cladding attachment over foam sheathing shall comply
with the additional requirements and limitations of Sections
703.15,
703.16 and
703.17.
TABLE 703.3(2)
SCREW FASTENER SUBSTITUTION FOR SIDING
ATTACHMENT TO COLD-FORMED STEEL LIGHT FRAME CONSTRUCTIONa, b, c,
d, e
|
NAIL DIAMETER PER TABLE
703.3(1)
|
MINIMUM SCREW FASTENER
SIZE
|
|
0.099 "
|
No. 6
|
|
0.113 "
|
No. 7
|
|
0.120 "
|
No. 8
|
For SI: 1 inch = 25.4 mm
a.
Screws shall
comply with ASTM C1513 and shall penetrate a minimum of three threads through
minimum 33 mil (20 gage) cold-formed steel frame construction.
b.
Screw head
diameter shall be not less than the nail head diameter required by Table
703.3(1).
c.
Number and spacing of screw fasteners shall comply with
Table 703.3(1).
d.
Pan head, hex washer head, modified truss head or other
screw head types with a flat attachment surface under the head shall be used
for vinyl siding attachment.
e.
Aluminum siding
shall not be fastened directly to cold-formed steel light frame
construction.
703.3.1
Soffit installation.
Soffits shall comply with Section 703.3.1.1, Section
703.3.1.2 or the manufacturer's installation instructions.
703.3.1.1
Wood
structural panel soffit.
The minimum
nominal thickness for wood structural panel soffits shall
be3/8 inch ( 9.5 mm) and shall be fastened to
framing or nailing strips with 2-inch by 0.099 -inch (51 mm × 2.5 mm)
nails. Fasteners shall be in spaced not less than 6 inches (152 mm) on center
at panel edges and 12 inches (305 mm) on center at intermediate
supports.
703.3.1.2
Vinyl soffit panels.
Soffit panels shall be fastened at fascia and wall ends and
to intermediate nailing strips as necessary to ensure that there is no
unsupported span greater than 16 inches (406 mm), or as specified by the
manufacturer's instructions.
703.3.2
Wind
limitations.
Where the design wind
pressure exceeds 30 psf or where the limits of Table 703.3.2 are exceeded, the
attachment of wall coverings and soffits shall be designed to resist the
component and cladding loads specified in Table 301.2(2) for walls, adjusted
for height and exposure in accordance with Table 301.2(3). For the
determination of wall covering and soffit attachment, component and cladding
loads shall be determined using an effective wind area of 10 square feet ( 0.93
m2).
TABLE 703.3.2
LIMITS FOR ATTACHMENT PER TABLE
703.3(1)
|
MAXIMUM MEAN ROOF HEIGHT
(feet)
|
|
Ultimate Wind Speed (mph 3-second
gust)
|
Exposure
|
|
B
|
C
|
D
|
|
115
|
NL
|
50'
|
20'
|
|
120
|
NL
|
30'
|
DR
|
|
130
|
60'
|
15'
|
DR
|
|
140
|
35'
|
DR
|
DR
|
For SI: 1 foot = 304.8 mm, 1 mile per hour =
0.447 m/s.
NL = Not Limited by Table 703.3.2, DR = Design
Required.
703.3.3
Fasteners.
Exterior wall coverings and roof overhang soffits shall be
securely fastened with aluminum, galvanized, stainless steel or
rust-preventative coated nails or staples in accordance with Table 703.3(1) or
with other approved corrosion-resistant fasteners in accordance with the wall
covering manufacturer's installation instructions. Nails and staples shall
comply with ASTM F1667. Nails shall be T-head, modified round head, or round
head with smooth or deformed shanks. Staples shall have a minimum crown width
of7/16 inch ( 11.1 mm) outside diameter and be
manufactured of minimum 16-gage wire. Where fiberboard, gypsum, or foam plastic
sheathing backing is used, nails or staples shall be driven into the studs.
Where wood or wood structural panel sheathing is used, fasteners shall be
driven into studs unless otherwise permitted to be driven into sheathing in
accordance with either the siding manufacturer's installation instructions or
Table 703.3.3.
TABLE 703.3.3
OPTIONAL SIDING ATTACHMENT SCHEDULE FOR
FASTENERS WHERE NO STUD PENETRATION NECESSARY
|
APPLICATION
|
NUMBER AND TYPE OF
FASTENER
|
SPACING OF
FASTENERSb
|
|
Exterior wall covering (weighing 3 psf
or less) attachment to wood structural panel sheathing,
|
Ring shank roofing nail ( 0.120 " min.
dia.)
|
12" o.c.
|
|
either direct or over foam sheathing a
maximum of 2 inches thick.a
|
Ring shank nail ( 0.148 " min.
dia.)
|
15" o.c.
|
|
No. 6 screw ( 0.138 " min.
dia.)
|
12" o.c.
|
|
Note: Does not apply to vertical
siding.
|
No. 8 screw ( 0.164 " min.
dia.)
|
16" o.c.
|
For SI: 1 inch = 25.4 mm, 1 pound per square
foot = 0.479 kPa.
a.
Fastener length shall be sufficient to penetrate the
back side of the wood structural panel sheathing by at least1/4 inch. The
wood structural panel sheathing shall be not less
than7/16 inch in thickness.
b.
Spacing of
fasteners is per 12 inches of siding width. For other siding widths, multiply
"Spacing of Fasteners" above by a factor of 12/s, where
"s" is the siding width in inches. Fastener spacing shall
never be greater than the manufacturer's minimum
recommendations.
703.3.4
Minimum
fastener length and penetration.
Fasteners
shall have the greater of the minimum length specified in Table 703.3(1) or as
required to provide a minimum penetration into framing as follows:
1.
Fasteners for
horizontal aluminum siding, steel siding, particleboard panel siding, wood
structural panel siding in accordance with ANSI/APA-PRP 210, fiber-cement panel
siding and fiber-cement lap siding installed over foam plastic sheathing shall
penetrate not less than 11/2 inches (38 mm) into framing or shall be in
accordance with the manufacturer's installation instructions.
2.
Fasteners for
hardboard panel and lap siding shall penetrate not less than 11/2 inches
(38 mm) into framing.
3.
Fasteners for vinyl siding and insulated vinyl siding
installed over wood or wood structural panel sheathing shall penetrate not less
than 11/4 inches (32 mm) into sheathing and framing combined. Vinyl siding
and insulated vinyl siding shall be permitted to be installed with fasteners
penetrating into or through wood or wood structural sheathing of minimum
thickness as specified by the manufacturer's instructions or test report, with
or without penetration into the framing. Where the fastener penetrates fully
through the sheathing, the end of the fastener shall extend not less
than1/4 inch ( 6.4 mm) beyond the opposite face of the sheathing.
Fasteners for vinyl siding and insulated vinyl siding installed over foam
plastic sheathing shall be in accordance with Section 703.11.2. Fasteners for
vinyl siding and insulated vinyl siding installed over fiberboard or gypsum
sheathing shall penetrate not less than 11/4 inches (32 mm) into
framing.
4.
Fasteners for vertical or horizontal wood siding shall
penetrate not less than 11/2 inches (38 mm) into studs, studs and wood
sheathing combined, or blocking.
5.
Fasteners for
siding material installed over foam plastic sheathing shall have sufficient
length to accommodate foam plastic sheathing thickness and to penetrate framing
or sheathing and framing combined, as specified in Items 1 through
4.
703.4
Flashing.
Approved corrosion-resistant flashing
shall be applied shingle-fashion in a manner to prevent entry of water into the
wall cavity or penetration of water to the building structural framing
components. Self-adhered membranes used as flashing shall comply with AAMA 711.
Fluid-applied membranes used as flashing in exterior walls shall comply with
AAMA 714. The flashing shall extend to the surface of the exterior wall finish.
Approved corrosion-resistant flashings shall be installed at the following
locations:
1.
Exterior window and door openings. Flashing at exterior window and door
openings shall extend to the surface of the exterior wall finish or to the
water-resistive barrier complying with Section 703.2 for subsequent drainage.
Mechanically attached flexible flashings shall comply with AAMA 712. Flashing
at exterior window and door openings shall be installed in accordance with one
or more of the following:
1.1.
The fenestration manufacturer's installation and
flashing instructions, or for applications not addressed in the fenestration
manufacturer's instructions, in accordance with the flashing manufacturer's
instructions. Where flashing instructions or details are not provided, pan
flashing shall be installed at the sill of exterior window and door openings.
Pan flashing shall be sealed or sloped in such a manner as to direct water to
the surface of the exterior wall finish or to the water-resistive barrier for
subsequent drainage. Openings using pan flashing shall incorporate flashing or
protection at the head and sides.
1.2.
In accordance
with the flashing design or method of a registered design
professional.
1.3.
In accordance with other approved
methods.
2.
At the intersection of chimneys or other masonry
construction with frame or stucco walls, with projecting lips on both sides
under stucco copings.
3.
Under and at the ends of masonry, wood or metal
copings and sills.
4.
Continuously above all projecting wood
trim.
5.
Where exterior porches, decks or stairs attach to a
wall or floor assembly of wood-frame construction.
6.
At wall and roof
intersections.
7.
At built-in gutters.
703.5
Wood,
hardboard and wood structural panel siding.
Wood, hardboard, and wood structural panel siding shall be
installed in accordance with this section and Table 703.3(1). Hardboard siding
shall comply with CPA/ANSI A 135.6.
Hardboard siding used as architectural trim
shall comply with CPA/ANSI A 135.7.
703.5.1
Vertical wood siding.
Wood siding applied vertically shall be nailed to horizontal
nailing strips or blocking set not more than 24 inches (610 mm) on
center.
703.5.2
Panel siding.
Three-eighths-inch ( 9.5 mm) wood structural panel siding
shall not be applied directly to studs spaced more than 16 inches (406 mm) on
center where long dimension is parallel to studs. Wood structural panel
siding7/16 inch ( 11.1 mm) or thinner shall not be
applied directly to studs spaced more than 24 inches (610 mm) on center. The
stud spacing shall not exceed the panel span rating provided by the
manufacturer unless the panels are installed with the face grain perpendicular
to the studs or over sheathing approved for that stud spacing.
Joints in wood, hardboard or wood structural
panel siding shall be made as follows unless otherwise approved. Vertical
joints in panel siding shall occur over framing members, unless wood or wood
structural panel sheathing is used, and shall be shiplapped or covered with a
batten. Horizontal joints in panel siding shall be lapped not less than 1 inch
(25 mm) or shall be shiplapped or flashed with Z-flashing and occur over solid
blocking, wood or wood structural panel sheathing.
703.5.3
Horizontal wood siding.
Horizontal lap siding shall be installed in accordance with
the manufacturer's recommendations. Where there are no recommendations the
siding shall be lapped not less than 1 inch (25 mm), or1/2 inch ( 12.7 mm)
if rabbeted, and shall have the ends caulked, covered with a batten or sealed
and installed over a strip of flashing.
703.6
Wood
shakes and shingles.
Wood shakes and
shingles shall conform to CSSB Grading Rules for Wood Shakes and
Shingles.
703.6.1
Application.
Wood
shakes or shingles shall be applied either single course or double course over
nominal 1/2-inch ( 12.7 mm) wood-based sheathing or to furring strips over
1/2-inch ( 12.7 mm) nominal nonwood sheathing. A water-resistive barrier
shall be provided over all sheathing, with horizontal overlaps in the membrane
of not less than 2 inches (51 mm) and vertical overlaps of not less than 6
inches (152 mm). Where horizontal furring strips are used, they shall be 1 inch
by 3 inches or 1 inch by 4 inches (25 mm by 76 mm or 25 mm by 102 mm) and shall
be fastened to the studs with minimum 7d or 8d box nails and shall be spaced a
distance on center equal to the actual weather exposure of the shakes or
shingles, not to exceed the maximum exposure specified in Table 703.6.1. When
installing shakes or shingles over a nonpermeable water-resistive barrier,
furring strips shall be placed first vertically over the barrier and in
addition, horizontal furring strips shall be fastened to the vertical furring
strips prior to attaching the shakes or shingles to the horizontal furring
strips. The spacing between adjacent shingles to allow for expansion shall
be1/8 inch ( 3.2 mm) to1/4 inch ( 6.4 mm)
apart, and between adjacent shakes shall be3/8 inch
( 9.5 mm) to1/2 inch ( 12.7 mm) apart. The offset spacing between joints
in adjacent courses shall be not less than 11/2 inches (38 mm).
TABLE 703.6.1 MAXIMUM WEATHER EXPOSURE
FOR WOOD SHAKES AND SHINGLES ON EXTERIOR
WALLSa, b, c
(Dimensions are in
inches)
|
LENGTH
|
EXPOSURE FOR SINGLE
COURSE
|
EXPOSURE FOR DOUBLE
COURSE
|
|
Shinglesa
|
|
16
|
7
|
12b
|
|
18
|
8
|
14c
|
|
24
|
101/2
|
16d
|
|
Shakesa
|
|
18
|
8
|
14
|
|
24
|
101/2
|
18
|
For SI: 1 inch = 25.4 mm.
a.
Dimensions given
are for No. 1 grade.
b.
A maximum 9-inch exposure is permitted for No. 2
grade.
c.
A maximum 10-inch exposure is permitted for No. 2
grade.
d.
A maximum 14-inch exposure is permitted for No. 2
grade.
703.6.2
Weather exposure.
The maximum weather exposure for shakes and shingles shall
not exceed that specified in Table 703.6.1.
703.6.3
Attachment.
Wood shakes
or shingles shall be installed according to this chapter and the manufacturer's
instructions. Each shake or shingle shall be held in place by two stainless
steel Type 304, Type 316 or hot-dipped zinc-coated galvanized
corrosion-resistant box nails in accordance with Table 703.6.3(1) or
703.6.3(2). The hot-dipped zinc-coated galvanizing shall be in compliance with
ASTM A153, 1.0 ounce per square foot. Alternatively, 16-gage stainless steel
Type 304 or Type 316 staples with crown widths7/16
inch (11 mm) minimum, 3/4 inch (19 mm) maximum, shall be used and the
crown of the staple shall be placed parallel with the butt of the shake or the
shingle. In single-course application, the fasteners shall be concealed by the
course above and shall be driven approximately 1 inch (25 mm) above the butt
line of the succeeding course and3/4 inch (19 mm) from the edge. In
double-course applications, the exposed shake or shingle shall be face-nailed
with two fasteners, driven approximately 2 inches (51 mm) above the butt line
and3/4 inch (19 mm) from each edge. Fasteners installed within 15 miles
(24 km) of salt water coastal areas shall be stainless steel Type 316.
Fasteners for fire-retardant-treated shakes or shingles in accordance with
Section 902 or pressure-impregnated-preservative-treated shakes or shingles in
accordance with AWPA U1 shall be stainless steel Type 316. The fasteners shall
penetrate the sheathing or furring strips by not less than1/2 inch (13 mm)
and shall not be overdriven. Fasteners for untreated (natural) and treated
products shall comply with ASTM F1667.
TABLE 703.6.3(1)
SINGLE-COURSE SIDEWALL
FASTENERS
|
SINGLE-COURSE SIDEWALL
FASTENERS
|
|
Product type
|
Nail type and minimum length
(inches)
|
Minimum head diameter
(inches)
|
Minimum shank thickness
(inches)
|
|
R & R and sanded
shingles
|
|
|
|
|
16" and 18" shingles
|
3d box 11/4
|
0.19
|
0.08
|
|
24" shingles
|
4d box 11/2
|
0.19
|
0.08
|
|
Grooved
shingles
|
|
|
|
|
16" and 18" shingles
|
3d box 11/4
|
0.19
|
0.08
|
|
24" shingles
|
4d box 11/2
|
0.19
|
0.08
|
|
Split and sawn
shakes
|
|
|
|
|
18" straight-split shakes
|
5d box 13/4
|
0.19
|
0.08
|
|
18" and 24" handsplit
shakes
|
6d box 2
|
0.19
|
0.0915
|
|
24" tapersplit shakes
|
5d box 13/4
|
0.19
|
0.08
|
|
18" and 24" tapersawn
shakes
|
6d box 2
|
0.19
|
0.0915
|
For SI: 1 inch = 25.4 mm.
TABLE 703.6.3(2)
DOUBLE-COURSE SIDEWALL
FASTENERS
|
DOUBLE-COURSE SIDEWALL
FASTENERS
|
|
Product type
|
Nail type and minimum length
(inches)
|
Minimum head diameter
(inches)
|
Minimum shank thickness
(inches)
|
|
R & R and sanded
shingles
|
|
|
|
|
16", 18" and 24" shingles
|
5d box 13/4 or same size casing
nails
|
0.19
|
0.08
|
|
Grooved
shingles
|
|
|
|
|
16", 18" and 24" shingles
|
5d box 13/4
|
0.19
|
0.08
|
|
Split and sawn
shakes
|
|
|
|
|
18" straight-split shakes
|
7d box 21/4 or 8d
21/2
|
0.19
|
0.099
|
|
18" and 24" handsplit
shakes
|
7d box 21/4 or 8d
21/2
|
0.19
|
0.099
|
|
24" tapersplit shakes
|
7d box 21/4 or 8d
21/2
|
0.19
|
0.099
|
|
18" and 24" tapersawn
shakes
|
7d box 21/4 or 8d
21/2
|
0.19
|
0.099
|
For SI: 1 inch = 25.4 mm.
703.6.4
Bottom courses.
The
bottom courses shall be doubled.
703.7
Exterior
plaster (stucco).
Installation of exterior
plaster shall be in compliance with ASTM C926, ASTM C1063 and the provisions of
this code.
703.7.1
Lath.
Lath and lath
attachments shall be of corrosion-resistant materials. Expanded metal or woven
wire lath shall be attached with 11/2-inch-long (38 mm), 11-gage nails
having a7/16-inch ( 11.1 mm) head,
or7/8-inch-long ( 22.2 mm), 16-gage staples, spaced
not more than 6 inches (152 mm) or as otherwise approved.
Exception:
Lath is not required over masonry, cast-in-place concrete,
precast concrete or stone substrates prepared in accordance with ASTM
C1063.
703.7.2
Plaster.
Plastering with cement plaster shall be in accordance with
ASTM C926. Cement materials shall be in accordance with one of the
following:
1.
Masonry cement conforming to ASTM C91 Type M, S or
N.
2.
Portland cement conforming to ASTM C150 Type I, II, or
III.
3.
Blended hydraulic cement conforming to ASTM C595 Type
IP, IS (< 70), IL, or IT (S < 70).
4.
Hydraulic cement
conforming to ASTM C1157 Type GU, HE, MS, HS, or MH.
5.
Plastic (stucco)
cement conforming to ASTM C1328.
Plaster shall be not less than three coats
where applied over metal lath or wire lath and shall be not less than two coats
where applied over masonry, concrete, pressure-preservative-treated wood or
decay-resistant wood as specified in Section 317.1 or gypsum backing. If the
plaster surface is completely covered by veneer or other facing material or is
completely concealed, plaster application need be only two coats, provided the
total thickness is as set forth in Table 702.1(1).
On wood-frame construction with an on-grade
floor slab system, exterior plaster shall be applied to cover, but not extend
below, lath, paper and screed.
The proportion of aggregate to cementitious
materials shall be as set forth in Table 702.1(3).
703.7.2.1
Weep
screeds.
A minimum 0.019 -inch ( 0.5 mm)
(No. 26 galvanized sheet gage), corrosion-resistant weep screed or plastic weep
screed, with a minimum vertical attachment flange of 31/2 inches (89 mm),
shall be provided at or below the foundation plate line on exterior stud walls
in accordance with ASTM C926. The weep screed shall be placed not less than 4
inches (102 mm) above the earth or 2 inches (51 mm) above paved areas and shall
be of a type that will allow trapped water to drain to the exterior of the
building. The weather-resistant barrier shall lap the attachment flange. The
exterior lath shall cover and terminate on the attachment flange of the weep
screed.
703.7.3
Water-resistive barriers.
Water-resistive barriers shall be installed as required in
Section 703.2 and, where applied over wood-based sheathing, shall include a
water-resistive, vapor-permeable barrier with a performance at least equivalent
to two layers of Grade D paper. The individual layers shall be installed
independently such that each layer provides a separate continuous plane and any
flashing, installed in accordance with Section 703.4 and intended to drain to
the water-resistive barrier, is directed between the layers.
Exception:
Where the water-resistive barrier that is applied over
wood-based sheathing has a water resistance equal to or greater than that of
60-minute Grade D paper and is separated from the stucco by an intervening,
substantially nonwater-absorbing layer or designed drainage space.
703.7.4
Application.
Each coat
shall be kept in a moist condition for at least 48 hours prior to application
of the next coat.
Exception:
Applications installed in accordance with ASTM
C926.
703.7.5
Curing.
The
finish coat for two-coat cement plaster shall not be applied sooner than seven
days after application of the first coat. For three-coat cement plaster, the
second coat shall not be applied sooner than 48 hours after application of the
first coat. The finish coat for three-coat cement plaster shall not be applied
sooner than seven days after application of the second coat.
703.8
Anchored stone and masonry veneer, general.
Anchored stone and masonry veneer shall be
installed in accordance with this chapter, Table 703.3(1) and Figure 703.8.
These veneers installed over a backing of wood or cold-formed steel shall be
limited to the first story above grade plane and shall not exceed 5 inches (127
mm) in thickness. See Section 602.10 for wall bracing requirements for masonry
veneer for wood-framed construction and Section 603.9.5 for wall bracing
requirements for masonry veneer for cold-formed steel construction.
Exceptions:
1.
For buildings in
Seismic Design Categories A, B and C, exterior stone or masonry veneer, as
specified in Table 703.8(1), with a backing of wood or steel framing shall be
permitted to the height specified in Table 703.8(1) above a noncombustible
foundation.
2.
Deleted
Click to
view image
For SI: 1 inch = 24.5 mm.
FIGURE 703.8
TYPICAL MASONRY VENEER WALL
DETAILS
e
Click to
view image
For SI: 1 inch = 25.4 mm.
a.
See Sections
703.4, 703.8.5 and 703.8.6.
b.
See Sections
703.2 and 703.8.4.
c.
See Table 703.8.4 and Section
703.8.4.2.
d.
See Section 703.8.3.
e.
Figure 703.8
illustrates typical construction details for a masonry veneer wall. For the
actual mandatory requirements of this code, see the indicated sections of text.
Other details of masonry veneer wall construction shall be permitted provided
the requirements of the indicated sections of text are met.
FIGURE 703.8
-continued
TYPICAL MASONRY VENEER WALL
DETAILS
e
TABLE 703.8(1)
STONE OR MASONRY VENEER LIMITATIONS AND
REQUIREMENTS, WOOD OR STEEL FRAMING, SEISMIC DESIGN CATEGORIES A, B and
C
|
SEISMIC DESIGN
CATEGORY
|
NUMBER OF WOOD- OR STEEL-FRAMED
STORIES
|
MAXIMUM HEIGHT OF VENEER ABOVE
NONCOMBUSTIBLE FOUNDATIONa(feet)
|
MAXIMUM NOMINAL THICKNESS OF
VENEER (inches)
|
MAXIMUM WEIGHT OF VENEER
(psf)b
|
WOOD- OR STEEL-FRAMED
STORY
|
|
A or B
|
Steel: 1 or 2 Wood: 1, 2 or
3
|
30
|
5
|
50
|
all
|
|
C
|
1
|
30
|
5
|
50
|
1 only
|
|
2
|
30
|
|
|
top
|
|
5
|
50
|
bottom
|
|
Wood only: 3
|
30
|
|
|
top
|
|
5
|
50
|
middle
|
|
|
|
bottom
|
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1
pound per square foot = 0.479 kPa.
a.
An additional 8
feet is permitted for gable end walls. See also story height limitations of
Section 301.3.
b.
Maximum weight is installed weight and includes weight
of mortar, grout, lath and other materials used for installation. Where veneer
is placed on both faces of a wall, the combined weight shall not exceed that
specified in this table.
TABLE 703.8(2)
Deleted
703.8.1
Interior veneer support.
Veneers used as interior wall finishes shall be permitted to
be supported on wood or cold-formed steel floors that are designed to support
the loads imposed.
703.8.2
Exterior veneer support.
Except in Seismic Design Categories D0, D1 and D2, exterior
masonry veneers having an installed weight of 40 pounds per square foot (195
kg/m2) or less shall be permitted to be supported on
wood or cold-formed steel construction. Where masonry veneer supported by wood
or cold-formed steel construction adjoins masonry veneer supported by the
foundation, there shall be a movement joint between the veneer supported by the
wood or cold-formed steel construction and the veneer supported by the
foundation. The wood or cold-formed steel construction supporting the masonry
veneer shall be designed to limit the deflection
to1/600 of the span for the supporting members. The
design of the wood or cold-formed steel construction shall consider the weight
of the veneer and any other loads.
703.8.2.1
Support by steel angle.
A minimum 6-inch by 4-inch
by5/16-inch (152 mm by 102 mm by 8 mm) steel angle,
with the long leg placed vertically, shall be anchored to double 2-inch by
4-inch (51 mm by 102 mm) wood studs or double 350S162 cold-formed steel studs
at a maximum on-center spacing of 16 inches (406 mm). Anchorage of the steel
angle at every double stud spacing shall be not less than
two7/16-inch-diameter (11 mm) by 4-inch (102 mm) lag
screws for wood construction or two7/16-inch ( 11.1
mm) bolts with washers for cold-formed steel construction. The steel angle
shall have a minimum clearance to underlying construction
of1/16 inch ( 1.6 mm). Not less than two-thirds the
width of the masonry veneer thickness shall bear on the steel angle. Flashing
and weep holes shall be located in the masonry veneer in accordance with Figure
703.8.2.1. The maximum height of masonry veneer above the steel angle support
shall be 12 feet 8 inches (3861 mm). The airspace separating the masonry veneer
from the wood backing shall be in accordance with Sections 703.8.4 and
703.8.4.2. The method of support for the masonry veneer on wood construction
shall be constructed in accordance with Figure 703.8.2.1.
The maximum slope of the roof construction
without stops shall be 7:12. Roof construction with slopes greater than 7:12
but not more than 12:12 shall have stops of a minimum 3-inch by 3-inch by
1/4-inch (76 mm by 76 mm by 6.4 mm) steel plate welded to the angle at 24
inches (610 mm) on center along the angle or as approved by the building
official.
Click to
view image
FIGURE 703.8.2.1
EXTERIOR MASONRY VENEER SUPPORT BY STEEL
ANGLES
703.8.2.2
Support by roof construction.
A steel angle shall be placed directly on top of the roof
construction. The roof supporting construction for the steel angle shall
consist of not fewer than three 2-inch by 6-inch (51 mm by 152 mm) wood members
for wood construction or three 550S162 cold-formed steel members for
cold-formed steel light frame construction. A wood member abutting the vertical
wall stud construction shall be anchored with not fewer than
three5/8-inch ( 15.9 mm) diameter by 5-inch (127 mm)
lag screws to every wood stud spacing. Each additional wood roof member shall
be anchored by the use of two 10d nails at every wood stud spacing. A
cold-formed steel member abutting the vertical wall stud shall be anchored with
not fewer than nine No. 8 screws to every cold-formed steel stud. Each
additional cold-formed steel roof member shall be anchored to the adjoining
roof member using two No. 8 screws at every stud spacing. Not less than
two-thirds the width of the masonry veneer thickness shall bear on the steel
angle. Flashing and weep holes shall be located in the masonry veneer wythe in
accordance with Figure 703.8.2.2. The maximum height of the masonry veneer
above the steel angle support shall be 12 feet 8 inches (3861 mm). The airspace
separating the masonry veneer from the wood backing shall be in accordance with
Sections 703.8.4 and 703.8.4.2. The support for the masonry veneer shall be
constructed in accordance with Figure 703.8.2.2.
The maximum slope of the roof construction
without stops shall be 7:12. Roof construction with slopes greater than 7:12
but not more than 12:12 shall have stops of a minimum 3-inch by 3-inch by
1/4-inch (76 mm by 76 mm by 6.4 mm) steel plate welded to the angle at 24
inches (610 mm) on center along the angle or as approved by the building
official.
Click to
view image
FIGURE 703.8.2.2
EXTERIOR MASONRY VENEER SUPPORT BY ROOF
MEMBERS
703.8.3
Lintels.
Masonry veneer
shall not support any vertical load other than the dead load of the veneer
above. Veneer above openings shall be supported on lintels of noncombustible
materials. The lintels shall have a length of bearing not less than 4 inches
(102 mm). Steel lintels shall be shop coated with a rust-inhibitive paint,
except for lintels made of corrosion-resistant steel or steel treated with
coatings to provide corrosion resistance. Construction of openings shall comply
with either Section 703.8.3.1 or 703.8.3.2.
703.8.3.1
Allowable span.
The
allowable span shall not exceed the values set forth in Table 703.8.3.1.
TABLE 703.8.3.1
ALLOWABLE SPANS FOR LINTELS SUPPORTING
MASONRY VENEERa, b, c, d
|
SIZE OF STEELANGLEa,
c, d
(inches)
|
NO STORY
ABOVE
|
ONE STORY
ABOVE
|
TWO STORIES
ABOVE
|
NO. OF 1/2-INCH OR
EQUIVALENT REINFORCING BARS IN REINFORCED LINTELb,
d
|
|
3 × 3 ×
1/4
|
6'-0"
|
4'-6"
|
3'-0"
|
1
|
|
4 × 3 ×
1/4
|
8'-0"
|
6'-0"
|
4'-6"
|
1
|
|
5 × 31/2
×5/16
|
10'-0"
|
8'-0"
|
6'-0"
|
2
|
|
6 × 31/2
×5/16
|
14'-0"
|
9'-6"
|
7'-0"
|
2
|
|
2-6 × 31/2
×5/16
|
20'-0"
|
12'-0"
|
9'-6"
|
4
|
For SI: 1 inch = 25.4 mm, 1 foot = 304.8
mm.
a.
Long leg of the angle shall be placed in a vertical
position.
b.
Depth of reinforced lintels shall be not less than 8
inches and all cells of hollow masonry lintels shall be grouted solid.
Reinforcing bars shall extend not less than 8 inches into the
support.
c.
Steel members indicated are adequate typical examples;
other steel members meeting structural design requirements shall be permitted
to be used.
d.
Either steel angle or reinforced lintel shall span
opening.
703.8.3.2
Maximum span.
The allowable span shall not exceed 18 feet 3 inches (5562
mm) and shall be constructed to comply with Figure 703.8.3.2, Table
703.8.3.2 and the following:
1.
Provide a minimum
length of 18 inches (457 mm) of masonry veneer on each side of opening as shown
in Figure 703.8.3.2.
2.
Provide a minimum 5-inch by 31/2-inch
by5/16-inch (127 mm by 89 mm by 7.9 mm) steel angle
above the opening and shore for a minimum of 7 days after
installation.
3.
Provide double-wire joint reinforcement extending 12
inches (305 mm) beyond each side of the opening. Lap splices of joint
reinforcement not less than 12 inches (305 mm). Comply with one of the
following:
3.1.
Double-wire joint reinforcement shall
be3/16-inch ( 4.8 mm) diameter and shall be placed
in the first two bed joints above the opening.
3.2.
Double-wire
joint reinforcement shall be 9 gauge ( 0.144 inch or 3.66 mm diameter) and
shall be placed in the first three bed joints above the
opening.
4.
Provide the height of masonry veneer above opening, in
accordance with Table 703.8.3.2.
TABLE 703.8.3.2
HEIGHT OF MASONRY VENEER ABOVE
OPENING
|
MINIMUM HEIGHT OF MASONRY VENEER
ABOVE OPENING (INCH)
|
MAXIMUM HEIGHT OF MASONRY VENEER
ABOVE OPENING (FEET)
|
|
13
|
< 5
|
|
24
|
5 to < 12
|
|
60
|
12 to height above support allowed by
Section 703.8
|
For SI: 1 inch = 25.4 mm, 1 foot = 304.8
mm.
Click to
view image
For SI: 1 inch = 25.4 mm, 1 foot = 304.8
mm.
FIGURE 703.8.3.2
MASONRY VENEER
OPENING
703.8.4
Anchorage.
Masonry
veneer shall be anchored to the supporting wall studs with corrosion-resistant
metal ties embedded in mortar or grout and extending into the veneer a minimum
of 11/2 inches (38 mm), with not less than
5/8-inch ( 15.9 mm) mortar or grout cover to
outside face. Masonry veneer shall conform to Table 703.8.4(1). For masonry
veneer tie attachment through insulating sheathing not greater than 2 inches
(51 mm) in thickness to not less than7/16
performance category wood structural panel, see Table 703.8.4(2).
TABLE 703.8.4(1)
TIE ATTACHMENT AND AIRSPACE
REQUIREMENTS
|
BACKING AND
TIE
|
MINIMUM TIE
|
MINIMUM TIE
FASTENERa
|
AIRSPACEc
|
|
Wood stud backing with corrugated sheet
metal
|
22 U.S. gage ( 0.0299
in.)×7/8 in. wide
|
8d common nail
b(21/2 in.× 0.131 in.)
|
Nominal 1 in. between sheathing and
veneer
|
|
Wood stud backing with metal strand
wire
|
W 1.7 (No. 9 U.S. gage;
0.148 in.) with hook embedded in mortar
joint
|
8d common nail
b(21/2 in.× 0.131
in.)
|
Minimum nominal 1 in. between sheathing
and veneer
|
Maximum 41/2 in. between backing
and veneer
|
|
Cold-formed steel stud backing with
adjustable metal strand wire
|
W 1.7 (No. 9 U.S. gage;
0.148 in.) with hook embedded in mortar
joint
|
No. 10 screw extending through the
steel framing a minimum of three exposed threads
|
Minimum nominal 1 in. between sheathing
and veneer
|
Maximum 41/2 in. between backing
and veneer
|
For SI: 1 inch = 25.4 mm.
a.
Deleted.
b.
All fasteners
shall have rust-inhibitive coating suitable for the installation in which they
are being used, or be manufactured from material not susceptible to
corrosion.
c.
An airspace that provides drainage shall be permitted
to contain mortar from construction.
TABLE 703.8.4(2)
REQUIRED BRICK TIE SPACING FOR DIRECT
APPLICATION TO WOOD STRUCTURAL PANEL SHEATHING
a, b, c
|
FASTENER
TYPEd
|
SIZE (DIA. OR SCREW
#)
|
REQUIRED BRICK-TIE SPACING
(VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING)
(inches/inches)
|
|
115 mph V
Ultimate
|
|
Zone 5, Exposure
B
|
Zone 5, Exposure
C
|
Zone 5, Exposure
D
|
|
Ring Shank Nails
|
0.091
|
16/16,
|
|
|
|
16/12,
|
16/12,
|
|
|
12/16,
|
12/16,
|
12/12
|
|
12/12
|
12/12
|
|
|
0.148
|
24/16,
|
|
|
|
16/24,
|
16/16,
|
16/16,
|
|
16/16,
|
16/12,
|
16/12,
|
|
16/12,
|
12/16,
|
12/16,
|
|
12/16, 12/12
|
12/12
|
12/12
|
|
Screws
|
#6
|
24/16,
|
|
|
|
16/24,
|
16/16,
|
16/16,
|
|
16/16,
|
16/12,
|
16/12,
|
|
16/12,
|
12/16,
|
12/16,
|
|
12/16, 12/12
|
12/12
|
12/12
|
|
|
24/16,
|
|
|
|
|
16/24,
|
16/16,
|
16/16,
|
|
|
16/16,
|
16/12,
|
16/12,
|
|
#8
|
16/12,
|
12/16,
|
12/16,
|
|
|
12/16,
|
12/12
|
12/12
|
|
|
12/12
|
|
|
|
#10
|
24/16,
|
24/16,
|
|
|
16/24,
|
16/24,
|
16/16,
|
|
16/16,
|
16/16,
|
16/12,
|
|
16/12,
|
16/12,
|
12/16,
|
|
12/16,
|
12/16,
|
12/12
|
|
12/12
|
12/12
|
|
|
#14
|
24/16,
|
24/16,
|
24/16,
|
|
16/24,
|
16/24,
|
16/24,
|
|
16/16, 16/12,
|
16/16, 16/12,
|
16/16, 16/12,
|
|
12/16, 12/12
|
12/16, 12/12
|
12/16, 12/12
|
For SI: 1 inch = 25.4 mm, 1 mph = 0.447
m/s.
a.
This table is based on attachment of brick ties
directly to wood structural panel sheathing only. Additional attachment of the
brick tie to lumber framing is not required. The brick ties shall be permitted
to be placed over any insulating sheathing, not to exceed 2 inches in
thickness. Wood structural panel sheathing shall be a
minimum7/16 performance category. The table is based
on a building height of 30 feet or less.
b.
Wood structural
panels shall have a specific gravity of 0.42 or greater in accordance with
NDS.
c.
Foam sheathing shall have a minimum compressive
strength of 15 psi in accordance with ASTM C578 or ASTM C1289.
d.
Fasteners shall
be sized such that the tip of the fastener passes completely through the wood
structural panel sheathing by not less than1/4 inch.
703.8.4.1
Size
and spacing.
Veneer ties, if strand wire,
shall be not less in thickness than No. 9 U.S. gage [( 0.148 inch) (4 mm)] wire
and shall have a hook embedded in the mortar joint, or if sheet metal, shall be
not less than No. 22 U.S. gage by [( 0.0299 inch) ( 0.76
mm)]7/8 inch (22 mm) corrugated. Each tie shall
support not more than 2.67 square feet ( 0.25 m2) of
wall area and shall be spaced not more than 32 inches (813 mm) on center
horizontally and 24 inches (635 mm) on center vertically.
Exception:
Deleted
703.8.4.1.1
Veneer ties around wall openings.
Additional metal ties shall be provided around wall openings
greater than 16 inches (406 mm) in either dimension. Metal ties around the
perimeter of openings shall be spaced not more than 3 feet (9144 mm) on center
and placed within 12 inches (305 mm) of the wall opening.
703.8.4.2
Grout fill.
As an
alternative to the airspace required by Table 703.8.4, grout shall be permitted
to fill the airspace. Where the airspace is filled with grout, a
water-resistive barrier is required over studs or sheathing. Where the airspace
is filled, replacing the sheathing and water-resistive barrier with a wire mesh
and approved water-resistive barrier or an approved water-resistive
barrier-backed reinforcement attached directly to the studs is
permitted.
703.8.5
Flashing.
Flashing shall be located beneath the first course of
masonry above finished ground level above the foundation wall or slab and at
other points of support, including structural floors, shelf angles and lintels
where masonry veneers are designed in accordance with Section 703.8. See
Section 703.4 for additional requirements.
703.8.6
Weepholes.
Weepholes
shall be provided in the outside wythe of masonry walls at a maximum spacing of
33 inches (838 mm) on center. Weepholes shall be not less
than3/16 inch (5 mm) in diameter. Weepholes shall be
located immediately above the flashing.
703.9
Exterior
insulation and finish system (EIFS)/EIFS with drainage.
Exterior insulation and finish systems (EIFS)
shall comply with this chapter and Section 703.9.1. EIFS with drainage shall
comply with this chapter and Section 703.9.2.
703.9.1
Exterior insulation and finish systems (EIFS).
EIFS shall comply with the following:
1.
ASTM
E2568.
2.
EIFS shall be limited to applications over substrates
of concrete or masonry wall assemblies.
3.
Flashing of EIFS
shall be provided in accordance with the requirements of Section
703.4.
4.
EIFS shall be installed in accordance with the
manufacturer's instructions.
5.
EIFS shall
terminate not less than 6 inches (152 mm) above the finished ground
level.
6.
Decorative trim shall not be face-nailed through the
EIFS.
703.9.2
Exterior insulation and finish system (EIFS)
with drainage.
EIFS with drainage shall
comply with the following:
1.
ASTM E2568.
2.
EIFS with
drainage shall be required over all wall assemblies with the exception of
substrates of concrete or masonry wall assemblies.
3.
EIFS with
drainage shall have an average minimum drainage efficiency of 90 percent when
tested in accordance with ASTM E2273.
4.
The
water-resistive barrier shall comply with Section 703.2 or ASTM
E2570.
5.
The water-resistive barrier shall be applied between
the EIFS and the wall sheathing.
6.
Flashing of EIFS
with drainage shall be provided in accordance with the requirements of Section
703.4.
7.
EIFS with drainage shall be installed in accordance
with the manufacturer's instructions.
8.
EIFS with
drainage shall terminate not less than 6 inches (152 mm) above the finished
ground level.
9.
Decorative trim shall not be face-nailed through the
EIFS with drainage.
703.10
Fiber
cement siding.
703.10.1
Panel siding.
Fiber-cement panels shall comply with the requirements of
ASTM C1186, Type A, minimum Grade II or ISO 8336, Category A, minimum Class 2.
Panels shall be installed with the long dimension either parallel or
perpendicular to framing. Vertical and horizontal joints shall occur over
framing members and shall be protected with caulking, or with battens or
flashing, or be vertical or horizontal shiplap, or otherwise designed to comply
with Section 703.1. Panel siding shall be installed with fasteners in
accordance with Table 703.3(1) or the approved manufacturer's
instructions.
703.10.2
Lap siding.
Fiber-cement lap siding having a maximum width of 12 inches
(305 mm) shall comply with the requirements of ASTM C1186, Type A, minimum
Grade II or ISO 8336, Category A, minimum Class 2. Lap siding shall be lapped a
minimum of 11/4 inches (32 mm) and lap siding not having tongue-and-groove
end joints shall have the ends protected with caulking, covered with an
H-section joint cover, located over a strip of flashing, or shall be designed
to comply with Section 703.1. Lap siding courses shall be installed with the
fastener heads exposed or concealed, in accordance with Table 703.3(1) or
approved manufacturer's instructions.
703.11
Vinyl
siding.
Vinyl siding shall be certified
and labeled as conforming to the requirements of ASTM D3679 by an approved
quality control agency.
703.11.1
Installation.
Vinyl siding, soffit and accessories shall be installed in
accordance with the manufacturer's instructions.
703.11.1.1
Fasteners.
Unless
specified otherwise by the manufacturer's instructions, fasteners for vinyl
siding shall be 0.120 -inch (3 mm) shank diameter nail with a 0.313 -inch (8
mm) head or 16-gage staple with a 3/8-inch ( 9.5 mm) to 1/2-inch ( 12.7
mm) crown.
703.11.1.2
Penetration depth.
Unless specified otherwise by the manufacturer's
instructions, fasteners shall penetrate into building framing. The total
penetration into sheathing, furring framing or other nailable substrate shall
be a minimum 11/4 inches (32 mm). Where specified by the manufacturer's
instructions and supported by a test report, fasteners are permitted to
penetrate into or fully through nailable sheathing or other nailable substrate
of minimum thickness specified by the instructions or test report without
penetrating into framing. Where the fastener penetrates fully through the
sheathing, the end of the fastener shall extend a minimum of1/4 inch ( 6.4
mm) beyond the opposite face of the sheathing or nailable
substrate.
703.11.1.3
Spacing.
Unless specified otherwise by the manufacturer's
instructions, the maximum spacing between fasteners for horizontal siding shall
be 16 inches (406 mm), and for vertical siding 12 inches (305 mm) both
horizontally and vertically. Where specified by the manufacturer's instructions
and supported by a test report, greater fastener spacing is
permitted.
703.11.2
Installation over foam plastic sheathing.
Where vinyl siding or insulated vinyl siding is installed
over foam plastic sheathing, the vinyl siding shall comply with Section
703.11 and shall have a design
wind pressure resistance in accordance with Table 703.11.2.
Exceptions:
1.
Where the foam
plastic sheathing is applied directly over wood structural panels, fiberboard,
gypsum sheathing or other approved backing capable of independently resisting
the design wind pressure, the vinyl siding shall be installed in accordance
with Sections 703.3.3 and 703.11.1.
2.
Where the vinyl
siding manufacturer's product specifications provide an approved design wind
pressure rating for installation over foam plastic sheathing, use of this
design wind pressure rating shall be permitted and the siding shall be
installed in accordance with the manufacturer's installation
instructions.
3.
Where the foam plastic sheathing and its attachment
have a design wind pressure resistance complying with Sections 316.8 and
301.2.1, the vinyl siding shall be installed in accordance with Sections
703.3.3 and 703.11.1.
TABLE 703.11.2
ADJUSTED MINIMUM DESIGN WIND PRESSURE
REQUIREMENT FOR VINYL SIDING
|
ULTIMATE DESIGN WIND SPEED
(MPH)
|
ADJUSTED MINIMUM DESIGN WIND
PRESSURE (ASD) (PSF)a,
b
|
|
Case 1: With interior gypsum
wallboardc
|
Case 2: Without interior gypsum
wallboardc
|
|
Exposure
|
Exposure
|
|
|
B
|
C
|
D
|
B
|
C
|
D
|
|
110
|
- 44.0
|
- 61.6
|
- 73.1
|
- 62.9
|
- 88.1
|
- 104.4
|
|
115
|
- 49.2
|
- 68.9
|
- 81.7
|
- 70.3
|
- 98.4
|
- 116.7
|
|
120
|
- 51.8
|
- 72.5
|
- 86.0
|
- 74.0
|
- 103.6
|
- 122.8
|
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1
square foot = 0.0929 m2, 1 mile per hour = 0.447 m/s, 1 pound per square foot =
0.0479 kPa.
a.
Linear interpolation is permitted.
b.
The table values
are based on a maximum 30-foot mean roof height, and effective wind area of 10
square feet Wall Zone 5 (corner), and the ASD design wind pressure from Table
301.2(2) multiplied by the following adjustment factors: 2.6 (Case 1) and 3.7
(Case 2) for wind speeds less than 130 mph and 3.7 (Case 2) for wind speeds
greater than 130 mph.
c.
Gypsum wallboard, gypsum panel product or
equivalent.
d.
For the indicated wind speed condition, foam sheathing
only on the exterior of frame walls with vinyl siding is not allowed unless the
vinyl siding complies with an adjusted minimum design wind pressure requirement
as determined in accordance with Note b and the wall assembly is capable of
resisting an impact without puncture at least equivalent to that of a wood
frame wall with minimum 7/16-inch OSB sheathing as tested in accordance with
ASTM E1886.
703.12
Adhered
masonry veneer installation.
Adhered
masonry veneer shall comply with the requirements of Section 703.7.3 and the
requirements in Sections 12.1 and 12.3 of TMS 402. Adhered masonry veneer shall
be installed in accordance with Section 703.7.1, Article 3.3 C of TMS 602 or
the manufacturer's instructions.
703.12.1
Clearances.
On exterior
stud walls, adhered masonry veneer shall be installed:
1.
Minimum of 4
inches (102 mm) above the earth;
2.
Minimum of 2
inches (51 mm) above paved areas; or
3.
Minimum
of1/2 inch ( 12.7 mm) above exterior walking surfaces that are supported
by the same foundation that supports the exterior wall.
703.12.2
Flashing at foundation.
A corrosion-resistant screed or flashing of a minimum 0.019
-inch ( 0.48 mm) or 26-gage galvanized or plastic with a minimum vertical
attachment flange of 31/2 inches (89 mm) shall be installed to extend a minimum
of 1 inch (25 mm) below the foundation plate line on exterior stud walls in
accordance with Section 703.4.
703.12.3
Water-resistive barrier.
A water-resistive barrier shall be installed as
required by Section 703.2 and shall comply with the requirements of Section
703.7.3. The water-resistive barrier shall lap over the exterior of the
attachment flange of the screed or flashing provided in accordance with Section
703.12.2.
703.13
Insulated vinyl siding.
Insulated vinyl siding shall be certified and labeled as
conforming to the requirements of ASTM D7793 by an approved quality control
agency.
703.13.1
Insulated
vinyl siding and accessories.
Insulated
vinyl siding and accessories shall be installed in accordance with the
manufacturer's installation instructions.
703.14
Polypropylene siding.
Polypropylene siding shall be certified and labeled as
conforming to the requirements of ASTM D7254, and those of Section 703.14.2 or
Section 703.14.3, by an approved quality control agency.
703.14.1
Polypropylene siding and accessories.
Polypropylene siding and accessories shall be installed in
accordance with manufacturer's installation instructions.
703.14.1.1
Installation.
Polypropylene siding shall be installed over and attached to
wood structural panel sheathing with minimum thickness
of7/16 inch ( 11.1 mm), or other substrate, composed
of wood or wood-based material and fasteners having equivalent withdrawal
resistance.
703.14.1.2
Fastener requirements.
Unless otherwise specified in the approved manufacturer's
instructions, nails shall be corrosion resistant, with a minimum 0.120 -inch (3
mm) shank and minimum 0.313 -inch (8 mm) head diameter. Nails shall be a
minimum of 11/4 inches (32 mm) long or as necessary to penetrate sheathing
or substrate not less than3/4 inch ( 19.1 mm). Where the nail fully
penetrates the sheathing or nailable substrate, the end of the fastener shall
extend not less than1/4 inch ( 6.4 mm) beyond the opposite face of the
sheathing or substrate. Staples are not permitted.
703.14.2
Fire
separation.
Polypropylene siding shall not
be installed on walls with a fire separation distance of less than 5 feet (1524
mm) and walls closer than 10 feet (3048 mm) to a building on another lot.
Exception:
Walls perpendicular to the line used to determine the fire
separation distance.
703.14.3
Flame
spread index.
The certification of the
flame spread index shall be accompanied by a test report stating that all
portions of the test specimen ahead of the flame front remained in position
during the test in accordance with ASTM E84 or UL 723.
703.15
Cladding attachment over foam sheathing to wood framing.
Cladding shall be specified and installed
in accordance with Section 703, the cladding manufacturer's approved
instructions, including any limitations for use over foam plastic sheathing, or
an approved design. In addition, the cladding or furring attachments through
foam sheathing to framing shall meet or exceed the minimum fastening
requirements of Section 703.15.1, Section 703.15.2, or an approved design for
support of cladding weight.
Exceptions:
1.
Where the
cladding manufacturer has provided approved installation instructions for
application over foam sheathing, those requirements shall
apply.
2.
For exterior insulation and finish systems, refer to
Section 703.9.
3.
For anchored masonry or stone veneer installed over
foam sheathing, refer to Section 703.8.
703.15.1
Direct
attachment.
Where cladding is installed
directly over foam sheathing without the use of furring, cladding minimum
fastening requirements to support the cladding weight shall be as specified in
Table 703.15.1.
TABLE 703.15.1
CLADDING MINIMUM FASTENING REQUIREMENTS
FOR DIRECT ATTACHMENT OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING
WEIGHTa
|
CLADDING FASTENER THROUGH FOAM
SHEATHING
|
CLADDING FASTENER TYPE AND
MINIMUM SIZEb
|
CLADDING FASTENER VERTICAL
SPACING (inches)
|
MAXIMUM THICKNESS OF FOAM
SHEATHINGc (inches)
|
|
16" o.c. Fastener Horizontal
Spacing Cladding Weight:
|
24" o.c. Fastener Horizontal
Spacing Cladding Weight:
|
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
|
Wood framing
(minimum 11/4-inch
penetration)
|
0.113 " diameter nail
|
6
|
2.00
|
1.45
|
0.75
|
DR
|
2.00
|
0.85
|
DR
|
DR
|
|
8
|
2.00
|
1.00
|
DR
|
DR
|
2.00
|
0.55
|
DR
|
DR
|
|
12
|
2.00
|
0.55
|
DR
|
DR
|
1.85
|
DR
|
DR
|
DR
|
|
0.120 " diameter nail
|
6
|
3.00
|
1.70
|
0.90
|
0.55
|
3.00
|
1.05
|
0.50
|
DR
|
|
8
|
3.00
|
1.20
|
0.60
|
DR
|
3.00
|
0.70
|
DR
|
DR
|
|
12
|
3.00
|
0.70
|
DR
|
DR
|
2.15
|
DR
|
DR
|
DR
|
|
0.131 " diameter nail
|
6
|
4.00
|
2.15
|
1.20
|
0.75
|
4.00
|
1.35
|
0.70
|
DR
|
|
8
|
4.00
|
1.55
|
0.80
|
DR
|
4.00
|
0.90
|
DR
|
DR
|
|
12
|
4.00
|
0.90
|
DR
|
DR
|
2.70
|
0.50
|
DR
|
DR
|
|
0.162 " diameter nail
|
6
|
4.00
|
3.55
|
2.05
|
1.40
|
4.00
|
2.25
|
1.25
|
0.80
|
|
8
|
4.00
|
2.55
|
1.45
|
0.95
|
4.00
|
1.60
|
0.85
|
0.50
|
|
12
|
4.00
|
1.60
|
0.85
|
0.50
|
4.00
|
0.95
|
DR
|
DR
|
For SI: 1 inch = 25.4 mm, 1 pound per square
foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa.
DR = Design Required.
o.c. = On Center.
a.
Wood framing shall
be Spruce-pine-fir or any wood species with a specific gravity of 0.42 or
greater in accordance with AWC NDS.
b.
Nail fasteners
shall comply with ASTM F1667, except nail length shall be permitted to exceed
ASTM F1667 standard lengths.
c.
Foam sheathing
shall have a minimum compressive strength of 15 psi in accordance with ASTM
C578 or ASTM C1289.
703.15.2
Furred
cladding attachment.
Where wood furring is
used to attach cladding over foam sheathing, furring minimum fastening
requirements to support the cladding weight shall be as specified in Table
703.15.2. Where placed horizontally, wood furring shall be preservative-treated
wood in accordance with Section 317.1 or naturally durable wood and fasteners
shall be corrosion resistant in accordance Section 317.3.
TABLE 703.15.2
FURRING MINIMUM FASTENING REQUIREMENTS
FOR APPLICATION OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING
WEIGHTa, b
|
|
FRAMING
MEMBER
|
FASTENER TYPE AND MINIMUM
SIZE
|
MINIMUM PENETRATION INTO WALL
FRAMING (inches)
|
FASTENER SPACING IN FURRING
(inches)
|
MAXIMUM THICKNESS OF FOAM
SHEATHINGd (inches)
|
|
FURRING
MATERIAL
|
16'' o.c. Furringe
Siding Weight:
|
24'' o.c. Furringe
Siding Weight:
|
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Minimum 1X wood
furringc
|
Minimum 2X wood stud
|
0.131 "
diameter nail
|
|
8
|
4.00
|
2.45
|
1.45
|
0.95
|
4.00
|
1.60
|
0.85
|
DR
|
|
11/4
|
12
|
4.00
|
1.60
|
0.85
|
DR
|
4.00
|
0.95
|
DR
|
DR
|
|
|
16
|
4.00
|
1.10
|
DR
|
DR
|
3.05
|
0.60
|
DR
|
DR
|
|
0.162 "
diameter nail
|
|
8
|
4.00
|
4.00
|
2.45
|
1.60
|
4.00
|
2.75
|
1.45
|
0.85
|
|
11/4
|
12
|
4.00
|
2.75
|
1.45
|
0.85
|
4.00
|
1.65
|
0.75
|
DR
|
|
|
16
|
4.00
|
1.90
|
0.95
|
DR
|
4.00
|
1.05
|
DR
|
DR
|
|
No.10 wood screw
|
|
12
|
4.00
|
2.30
|
1.20
|
0.70
|
4.00
|
1.40
|
0.60
|
DR
|
|
1
|
16
|
4.00
|
1.65
|
0.75
|
DR
|
4.00
|
0.90
|
DR
|
DR
|
|
|
24
|
4.00
|
0.90
|
DR
|
DR
|
2.85
|
DR
|
DR
|
DR
|
|
1/4" lag screw
|
|
12
|
4.00
|
2.65
|
1.50
|
0.90
|
4.00
|
1.65
|
0.80
|
DR
|
|
11/2
|
16
|
4.00
|
1.95
|
0.95
|
0.50
|
4.00
|
1.10
|
DR
|
DR
|
|
|
24
|
4.00
|
1.10
|
DR
|
DR
|
3.25
|
0.50
|
DR
|
DR
|
For SI: 1 inch = 25.4 mm, 1 pound per square
foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa.
DR = Design Required.
o.c. = On Center.
a.
Wood framing and
furring shall be Spruce-pine-fir or any wood species with a specific gravity of
0.42 or greater in accordance with AWC NDS.
b.
Nail fasteners
shall comply with ASTM F1667, except nail length shall be permitted to exceed
ASTM F1667 standard lengths.
c.
Where the
required cladding fastener penetration into wood material exceeds3/4 inch
and is not more than 11/2 inches, a minimum 2" wood furring or an approved
design shall be used.
d.
Foam sheathing shall have a minimum compressive
strength of 15 psi in accordance with ASTM C578 or ASTM C1289.
e.
Furring shall be
spaced not more than 24 inches on center, in a vertical or horizontal
orientation. In a vertical orientation, furring shall be located over wall
studs and attached with the required fastener spacing. In a horizontal
orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall
be achieved by use of two fasteners into studs at 16 inches and 24 inches on
center, respectively.
703.16
Cladding attachment over foam sheathing to cold-formed steel framing.
Cladding shall be specified and installed
in accordance with Section 703, the cladding manufacturer's approved
instructions, including any limitations for use over foam plastic sheathing, or
an approved design. In addition, the cladding or furring attachments through
foam sheathing to framing shall meet or exceed the minimum fastening
requirements of Section 703.16.1, Section 703.16.2 or an approved design for
support of cladding weight.
Exceptions:
1.
Where the
cladding manufacturer has provided approved installation instructions for
application over foam sheathing, those requirements shall
apply.
2.
For exterior insulation and finish systems, refer to
Section 703.9.
3.
For anchored masonry or stone veneer installed over
foam sheathing, refer to Section 703.8.
703.16.1
Direct
attachment.
Where cladding is installed
directly over foam sheathing without the use of furring, cladding minimum
fastening requirements to support the cladding weight shall be as specified in
Table 703.16.1.
TABLE 703.16.1
CLADDING MINIMUM FASTENING REQUIREMENTS
FOR DIRECT ATTACHMENT OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING
WEIGHTa
|
CLADDING FASTENER THROUGH FOAM
SHEATHING INTO:
|
CLADDING FASTENER TYPE AND
MINIMUM SIZEb
|
CLADDING FASTENER VERTICAL
SPACING (inches)
|
MAXIMUM THICKNESS OF FOAM
SHEATHINGc (inches)
|
|
16n o.c. Fastener Horizontal
Spacing Cladding Weight:
|
24" o.c. Fastener Horizontal
Spacing Cladding Weight:
|
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
|
Steel framing (minimum penetration of
steel thickness + 3 threads)
|
No. 8 screw into 33-mil steel or
thicker
|
6
|
3.00
|
2.95
|
2.20
|
1.45
|
3.00
|
2.35
|
1.25
|
DR
|
|
8
|
3.00
|
2.55
|
1.60
|
0.60
|
3.00
|
1.80
|
DR
|
DR
|
|
12
|
3.00
|
1.80
|
DR
|
DR
|
3.00
|
0.65
|
DR
|
DR
|
|
No. 10 screw into 33-mil
steel
|
6
|
4.00
|
3.50
|
2.70
|
1.95
|
4.00
|
2.90
|
1.70
|
0.55
|
|
8
|
4.00
|
3.10
|
2.05
|
1.00
|
4.00
|
2.25
|
0.70
|
DR
|
|
12
|
4.00
|
2.25
|
0.70
|
DR
|
3.70
|
1.05
|
DR
|
DR
|
|
No. 10 screw into 43-mil steel or
thicker
|
6
|
4.00
|
4.00
|
4.00
|
3.60
|
4.00
|
4.00
|
3.45
|
2.70
|
|
8
|
4.00
|
4.00
|
3.70
|
3.00
|
4.00
|
3.85
|
2.80
|
1.80
|
|
12
|
4.00
|
3.85
|
2.80
|
1.80
|
4.00
|
3.05
|
1.50
|
DR
|
For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm, 1
pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895
kPa.
DR = Design Required.
o.c. = On Center.
a.
Steel framing
shall be minimum 33 ksi steel for 33 mil and 43 mil steel, and 50 ksi steel for
54 mil steel or thicker.
b.
Screws shall comply with the requirements of ASTM
C1513.
c.
Foam sheathing shall have a minimum compressive
strength of 15 psi in accordance with ASTM C578 or ASTM
C1289.
703.16.2
Furred cladding attachment.
Where steel or wood furring is used to attach cladding over
foam sheathing, furring minimum fastening requirements to support the cladding
weight shall be as specified in Table 703.16.2. Where placed horizontally, wood
furring shall be preservative-treated wood in accordance with Section 317.1 or
naturally durable wood and fasteners shall be corrosion resistant in accordance
with Section 317.3. Steel furring shall have a minimum G60 galvanized
coating.
TABLE 703.16.2
FURRING MINIMUM FASTENING REQUIREMENTS
FOR APPLICATION OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING
WEIGHTa
|
|
FRAMING
MEMBER
|
FASTENER TYPE AND MINIMUM
SIZEb
|
MINIMUM PENETRATION INTO WALL
FRAMING (inches)
|
FASTENER SPACING IN FURRING
(inches)
|
MAXIMUM THICKNESS OF FOAM
SHEATHINGd (inches)
|
|
FURRING
MATERIAL
|
16no.c. Furring e Cladding
Weight:
|
24no.c. Furring e Cladding
Weight:
|
|
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
3 psf
|
11 psf
|
18 psf
|
25 psf
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Minimum 33-mil steel furring or minimum
1x wood furringc
|
33-mil steel stud
|
No. 8 screw
|
Steel thickness + 3
threads
|
12
|
3.00
|
1.80
|
DR
|
DR
|
3.00
|
0.65
|
DR
|
DR
|
|
16
|
3.00
|
1.00
|
DR
|
DR
|
2.85
|
DR
|
DR
|
DR
|
|
24
|
2.85
|
DR
|
DR
|
DR
|
2.20
|
DR
|
DR
|
DR
|
|
No. 10 screw
|
Steel thickness + 3
threads
|
12
|
4.00
|
2.25
|
0.70
|
DR
|
3.70
|
1.05
|
DR
|
DR
|
|
16
|
3.85
|
1.45
|
DR
|
DR
|
3.40
|
DR
|
DR
|
DR
|
|
24
|
3.40
|
DR
|
DR
|
DR
|
2.70
|
DR
|
DR
|
DR
|
|
43-mil or thicker steel
stud
|
No. 8 Screw
|
Steel thickness + 3
threads
|
12
|
3.00
|
1.80
|
DR
|
DR
|
3.00
|
0.65
|
DR
|
DR
|
|
16
|
3.00
|
1.00
|
DR
|
DR
|
2.85
|
DR
|
DR
|
DR
|
|
24
|
2.85
|
DR
|
DR
|
DR
|
2.20
|
DR
|
DR
|
DR
|
|
|
Steel thickness + 3
threads
|
12
|
4.00
|
3.85
|
2.80
|
1.80
|
4.00
|
3.05
|
1.50
|
DR
|
|
No. 10
|
16
|
4.00
|
3.30
|
1.95
|
0.60
|
4.00
|
2.25
|
DR
|
DR
|
|
|
24
|
4.00
|
2.25
|
DR
|
DR
|
4.00
|
0.65
|
DR
|
DR
|
For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm, 1
pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895
kPa.
DR = Design Required.
o.c. = On Center.
a.
Wood furring shall
be Spruce-pine-fir or any softwood species with a specific gravity of 0.42 or
greater. Steel furring shall be minimum 33-ksi steel. Steel studs shall be
minimum 33-ksi steel for 33-mil and 43-mil thickness, and 50-ksi steel for
54-mil steel or thicker.
b.
Screws shall comply with the requirements of ASTM
C1513.
c.
Where the required cladding fastener penetration into
wood material exceeds3/4 inch and is not more than 11/2 inches, a
minimum 2-inch nominal wood furring or an approved design shall be
used.
d.
Foam sheathing shall have a minimum compressive
strength of 15 psi in accordance with ASTM C578 or ASTM C1289.
e.
Furring shall be
spaced not more than 24 inches (610 mm) on center, in a vertical or horizontal
orientation. In a vertical orientation, furring shall be located over wall
studs and attached with the required fastener spacing. In a horizontal
orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall
be achieved by use of two fasteners into studs at 16 inches and 24 inches on
center, respectively.
703.17
Cladding
attachment over foam sheathing to masonry or concrete wall
construction.
Cladding shall be specified
and installed in accordance with Section 703.3 and the cladding manufacturer's
instructions or an approved design. Foam sheathing shall be attached to masonry
or concrete construction in accordance with the insulation manufacturer's
installation instructions or an approved design. Furring and furring
attachments through foam sheathing into concrete or masonry substrate shall be
designed to resist design loads determined in accordance with Section 301,
including support of cladding weight as applicable. Fasteners used to attach
cladding or furring through foam sheathing to masonry or concrete substrates
shall be approved for application into masonry or concrete material and shall
be installed in accordance with the fastener manufacturer's instructions.
Exceptions:
1.
Where the cladding
manufacturer has provided approved installation instructions for application
over foam sheathing and connection to a masonry or concrete substrate, those
requirements shall apply.
2.
For exterior insulation and finish systems, refer to
Section 703.9.
3.
For anchored masonry or stone veneer installed over
foam sheathing, refer to Section 703.8.
Replaces: 4101:8-7-01