248 CMR 4.03 - Scope of the Massachusetts Fuel Gas Code and Adoption of Relevant Codes

The Massachusetts Fuel Gas Code is comprised of the following:

(1) For most installations of gas piping systems in Massachusetts, the Board adopts NFPA 54 as modified by 248 CMR 5.00: Amendments to NFPA 54 . The scope of this adoption shall be governed by NFPA 54 Chapter 1, Administration, subject to the following modifications:
(a) Replace NFPA 54 sub-section 1.1.1.1(A) with the following:

Jurisdiction of gases as defined in subsection 3.3.51 of NFPA 54 shall extend from the point of delivery to the provided connections with each gas utilization device as follows:

1. For natural and manufactured gas systems, the point of delivery shall be considered the outlet of the service meter assembly or the outlet of the service regulator or service shut off valve where no meter is provided.
2. For undiluted liquefied petroleum gas systems, the point of delivery shall be considered the supply source, or, if it exists, the outlet of the first regulator located at the cylinder/vessel.
3. This code shall regulate piping systems in permanent structures, buildings under construction, as well as exterior installations.
(b) Replace NFPA 54 sub-section 1.1.1.1(B) with the following:

All gas piping systems shall be low pressure, not in excess of 0.5 P.S.I.G. or 14 inch water column. Systems may exceed these requirements if designed and installed in accordance with 248 CMR 5.05(4)(B).

(c) Delete NFPA 54 sub-section 1.1.1.2 and replace with the following:

The provisions of NFPA 54 shall not apply to applications utilizing acetylene, hydrogen, ammonia, carbon monoxide, oxygen, or nitrogen; such installations shall be governed by 248 CMR 4.03(6).

(d) Delete NFPA 54 section 1.4
(2) For installations of undiluted liquefied petroleum gas not explicitly covered by NFPA 54 as modified, the Board adopts NFPA 58 as modified by 248 CMR 8.00: Amendments to NFPA 58 . The scope of this adoption shall be governed by NFPA 58 Chapter 1, Administration, subject to the following modifications:
(a) Delete NFPA 58 sub-section 1.1 and replace it with the following:

1.1 Scope. This code applies to the installation of undiluted liquefied petroleum gas systems and appliances.

(b) Delete NFPA 58 sub-section 1.3.1 and replace it with the following:

1.3.1 Application of the Code. This code shall apply to the installation of undiluted liquefied petroleum gas systems commencing upon the point of delivery. For purposes of this code, the point of delivery shall be considered the supply source, or, if it exists, the outlet of the first regulator located at the cylinder/vessel. This code shall regulate piping systems in permanent structures, buildings under construction, as well as exterior installations.

(c) Delete NFPA 58 subsections 1.3.2(3), (4), (5), (6) and (11)
(3) For installations of fuel gas boilers with an input of 12,500,000 BTU per hour or greater or fuel gas fired steam generators, the Board adopts NFPA 85 chapters 1 to 8. The scope of this adoption shall be governed by NFPA 85 Chapter 1, Administration, subject to the following modifications:
(a) Delete NFPA 85 sub-section 1.1 and replace it with the following:

1.1 Scope. This code applies to the installation of single burner boilers, multiple burner boilers, and atmospheric fluidized bed boilers with a fuel input rating 3.7 of MWt (12.5 million BTU/hr) or greater. This code also applies to fuel gas fired steam generators used to recover heat from combustion turbines and other combustion turbine exhaust systems at any heat input rate. However, this code shall not be deemed to apply to any equipment that does not utilize a fuel gas.

(b) Delete NFPA 85 sub-sections 1.1.8, 1.1.9, and 1.1.9.1.
(4) For installations of fuel gas fired ovens, dryers, furnaces, thermal oxidizers, and other heated enclosures used for the processing of materials and related equipment, the Board adopts NFPA 86. The scope of this adoption shall be governed by NFPA 86 Chapter 1, Administration, subject to the following modifications:
(a) Modify NFPA 86 sub-section 1.1.7 by adding sub-section 1.1.7(5) as follows: Installations of equipment that utilize oil or any other non-gas liquid fuel.
(b) Delete NFPA 86 sub-section 1.3.5, 1.3.7, and 1.3.8.
(5) All installations of fuel gas utilization equipment not governed by NFPA 85 or 86 (as amended) having inputs over 400,000 BTU per hour per combustion chamber shall be governed by 248 CMR 7.00: Large Gas Utilization Equipment .
(6) For all other fuel gas installations not referred to, including, but not necessarily limited to, installations of piping systems conveying acetylene, hydrogen, ammonia, carbon monoxide, oxygen, nitrogen, or any other gas used as a fuel gas, from the supply source, or, if it exists, beyond a gas meter outlet or regulator, the system must be designed by a Massachusetts registered professional engineer. The design must assure that the piping installation, including pipe sizing, dimension, and other aspects, meet the requirements for proper functioning, safety, and this code. The installer must submit drawings to the Inspector stamped by the engineer reflecting this design prior to being issued a permit.

Notes

248 CMR 4.03
Amended by Mass Register Issue 1275, eff. 12/5/2014. Amended by Mass Register Issue 1442, eff. 4/30/2021.

State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.


No prior version found.