(1) Delete sub-section 5.1.1 and replace with
the following:
5.1.1 Installation of Piping Systems over Five
Million BTU/hr. In addition to the permit requirements of
248 CMR 3.00: General
Provisions Governing the Conduct of Plumbing and Gas Fitting Work Performed in
the Commonwealth, for gas installations of over 5,000,000 BTU/hr the
following is required:
(a) All piping
systems over 5,000,000 BTU/hr shall be designed by a Massachusetts registered
professional engineer. The design shall assure that the piping installation,
including pipe sizing, dimension, and other aspects, meet the requirements for
proper functioning, safety, and this code. The installer must submit drawings
to the Inspector stamped by the engineer reflecting this design prior to being
issued a permit. The installer shall also submit with the drawings a written
statement from the serving gas supplier that it is able to provide fuel meeting
the volume, pressure, and maximum gas demand required by the drawings as well
as that required by any existing gas systems.
(b) Once the installation is complete but
prior to final inspection, the installer must provide the Inspector with a
written certification by a Massachusetts registered professional engineer that
the installation complies with the stamped drawings and specifications. The
Inspector shall not be responsible for approving or inspecting design
specifications, but must ensure the installation adheres to the provisions of
248 CMR
5.00.
(2) Add a new sub-section 5.1.3 as follows:
5.1.3 Dual Fuels Installed in Buildings and
Structures. When Utility/Natural Gas and Undiluted Liquefied
Petroleum Gas (Propane Gas) systems are installed within the same building or
structure, the following additional conditions must be satisfied as well as
those conditions required for each individual fuel system:
(a) Written permission for the installation
must be obtained by local fire officials and applicable utilities.
(b) The natural gas and propane gas piping
systems shall be labeled in the following manner:
1.at a minimum of every ten feet;
2.at all changes of direction;
3.on each side of a penetration through a
partition, wall or ceiling;
4.at
every gas shut off valve;
5.for
natural gas (color-coded yellow) and propane gas (color coded light green), the
labels shall be;
a.black lettering indicating
the type of gas within the piping system;
b.the letters shall be sized equal to a
minimum of the pipe diameter. However, for piping with a diameter exceeding two
inches, said lettering does not need to be larger than two inches.
(3) Add a
new sub-section 5.4.2.3 as follows:
5.4.2.3 Diversity Factor for Domestic
Ranges. Diversity factor is an important factor determining the
correct gas piping size to be used for supplying domestic ranges in multiple
family dwellings; it applies to domestic ranges only and shall not apply to any
other gas appliances.
TABLE 5.4.2.3
Multi-family Dwellings Diversity Factor in Percent of
Total Load for Domestic Gas Ranges with connected Load Ratings of 63,000
Btu/hr. or more per Range
|
No. of Ranges
|
Demand cubic ft/hour
|
Percent of Ratings
|
No. of Ranges
|
Demand cubic ft/hour
|
Percent of Ratings
|
|
1
|
63
|
100
|
13
|
270
|
33
|
|
2
|
107
|
85
|
14
|
283
|
32
|
|
3
|
132
|
70
|
15
|
293
|
31
|
|
4
|
151
|
60
|
16
|
312
|
31
|
|
5
|
173
|
55
|
17
|
33
|
30
|
|
6
|
189
|
50
|
18
|
340
|
30
|
|
7
|
198
|
50
|
19
|
346
|
29
|
|
8
|
212
|
42
|
20
|
353
|
28
|
|
9
|
225
|
39
|
21
|
358
|
27
|
|
10
|
233
|
38
|
22
|
374
|
27
|
|
11
|
243
|
37
|
23
|
390
|
27
|
|
12
|
257
|
35
|
24 & Over
|
408
|
27
|
(4)
Replace sub-section 5.5.1 with the following:
5.5.1 Maximum Design Operating
Pressure.
(b)
Elevated
Pressure.
1.All elevated
pressure systems shall be designed by a Massachusetts registered professional
engineer. The design shall assure that the piping installation, including pipe
sizing, dimension, and other aspects, meet the requirements for proper
functioning, safety, and this code. The installer must submit drawings to the
Inspector stamped by the engineer reflecting this design prior to being issued
a permit. The installer shall also submit with the drawings a written statement
from the serving gas supplier that it is able to provide fuel meeting the
volume, pressure, and maximum gas demand required by the drawings as well as
that required by any existing gas systems. The provisions of this paragraph
shall not be in effect until July 1, 2015. Prior to July 1, 2015, elevated
pressure systems shall be subject to the special permission requirements of
248 CMR
3.04(3).
2.Once the installation is complete but prior
to final inspection, the installer must provide the Inspector with a written
certification by a Massachusetts registered professional engineer that the
installation complies with the stamped drawings and specifications. The
Inspector shall not be responsible for approving or inspecting design
specifications, but must ensure the installation adheres to the provisions of
248 CMR
5.00.
3.When the maximum design operating pressure
exceeds five PSIG, all piping shall be welded in accordance with subsection
5.6.2.2.1.
4.Elevated pressure
piping shall be labeled in the following manner:
a.At a minimum of every ten feet;
b.At all changes of direction;
c.On each side of a penetration through a
partition, wall or ceiling;
d.At
every gas shutoff valve; and
e.The
labels shall be yellow with black lettering that:
i.indicates the type of gas and the pressure
contained within the piping system,and
ii.the letters shall be sized equal to a
minimum of the pipe diameter. However,for piping with a diameter exceeding two
inches, said lettering does not need to be larger than two inches; and
iii.for elevated dual fuel
applications, labels for propane systems shall be color-coded light green.
f.Labeling shall not be
required for elevated pressure piping that is between the first and second
stage regulator in a liquefied petroleum gas installation.
5.
Exceptions. The
requirements of a professional engineer for elevated pressure installations
shall not be required for:
a.installations of
propane gas piping systems utilizing elevated pressure that are located between
the first and second stage regulator when the second stage regulator is located
on the exterior of a building; and
b.installations of gas piping between a meter
and a regulator not installed/supplied by a gas company when the gas piping
from the meter to the regulator does not exceed ten feet.
(5) Add a new
sub-section 5.5.1.1 as follows:
5.5.1.1 Gas Pressure Boosters. Gas
pressure boosters may be installed in that portion of the gas piping system
extending from the outlet of the meter set assembly to the inlet of the
equipment requiring elevated or increased pressure when the following
conditions have been satisfied:
(a)
All gas pressure boosters must meet Product-acceptance requirements;
(b) the serving gas supplier has provided
written authorization;
(c) If not
part of the booster, the equipment served by the booster shall be equipped with
a manual re-set low gas pressure switch and a check valve upstream of the
booster. By-passes for pressure boosters shall include a manual shut off and a
check valve;
(d) A pressure
regulator shall be provided to maintain a constant outlet pressure and be
installed immediately downstream of the booster except when the pressure
booster is equipped with an integral pressure regulator;
(e) Gas pressure boosters shall be installed
on a firm foundation or surface capable of supporting the imposed load, and the
booster shall be kept free of vibration by the installation of vibration
arrestors; and
(f) Gas pressure
boosters shall be located in well ventilated spaces and be readily accessible
for examination, maintenance or replacement.
(6) Add a new sub-section 5.6.2.2.1 with the
following:
5.6.2.2.1 Welding of Steel and Wrought Iron
Pipe.
(a) Welding shall
not be construed as the practice of gas-fitting, however, a licensed plumber or
gas fitter may not utilize welded pipes and fittings unless they conform to the
specifications cited in subsections 5.6.2.2 and A.5.5.1 (1).
(b) Gas piping systems with pressures under
or equal to 70 P.S.I.G shall only be permitted to utilize welded pipes and
fittings when:
1.The inspector has performed
a visual inspection as to the quality of the weld; and
2.The test pressure used during an Inspection
complies with the following:
a.Systems with a
maximum operating pressure of ten P.S.I.G. or less, shall be tested to a
minimum of three P.S.I.G. or ten times the operating pressure, whichever is
greater.
b.Systems with an
operating pressure greater than ten P.S.I.G. and less than or equal to 70
P.S.I.G. shall be tested at 100 P.S.I.G.
c.The test duration shall be one hour for
every 100 feet of pipe, or fraction thereof.
The minimum test duration shall be one hour and the maximum
test duration shall be 24 hours, irrespective of system design. (c) Gas piping
systems with pressures over 70 P.S.I.G. may only utilize welded pipes and
fittings when:
1.All welds are of full
penetration; and
2.The welds are
subjected to the following tests:
a.All welds
are subjected to a 100% X-ray or 100% Ultrasonic Examination (UT) test unless
they are socket welded;
b.All
socket welded type joints must be subjected to a magnetic particle test or
other non-destructive test;
c.The
gas piping system shall be pressure tested to a minimum of 1.25 times the gas
piping systems working pressure. However, the test duration must be a minimum
of one hour and the test must be witnessed by the Inspector; and,
d.Any testing company or field agent that
provides a (UT) field examination must meet the requirements of
248 CMR
3.04(6). A copy of the
testing certification shall be submitted to the Inspector.
3.Repairs that are made to welded joints that
fail the X-Ray or (UT) test shall be re-tested and re-certified. For future
reference; the failed welded joint that is re-tested shall be identified by
stenciling 1/2 inch high white lettering at the weld location the date of
the re-test.
4.The Inspector shall
require an affidavit signed by the individual who performed the X-ray or (UT)
examination for the testing agency. The affidavit shall state that all welds
meet the requirements of the applicable specifications and tests.
(7) Add a new sub-section 5.6.2.7 as follows:
5.6.2.7 Galvanized. Galvanized pipe
shall not be used.
(8)
Replace sub-section 5.6.3.4 with the following:
5.6.3.4 Corrugated Stainless
Steel.
(a)
CSST Fittings. All fittings and accessories used in
the installation of CSST piping systems shall be approved by the CSST
manufacturer for use with their system and shall only be installed by licensees
who have completed manufacturer training/certification acceptable to the
Board.
(b)
CSST
Concealed Fittings.
1.Where gas
piping is to be concealed:
a.connections
shall only be made with CSST fittings listed for use in concealed spaces;
and
b.connections shall be produced
by the manufacturer of the CSST piping system.
2.Malleable fittings shall be permitted in
concealed locations when used in combination with CSST fittings.
3.For each malleable fitting there shall only
be a single CSST connection.
(c)
Repairs to Concealed CSST
Piping.
1.Repairs required in a
CSST system which is concealed, or otherwise not readily accessible, shall be
repaired with a fitting listed for the CSST system being used.
2.Installation of an access panel shall be
required at the repair site.
(d)
Interior Meter
Connections. Interior meter connections may be directly connected
to the CSST system as long as the meter is securely affixed to the building,
and the CSST is secured to the building structure when 24 inches or more of
tubing is exposed.
(e)
Exterior Meter Connections.
1.No CSST shall be connected to an exterior
meter.
2.The tubing shall terminate
at the foundation wall with a termination fitting, and the meter shall be
rigidly connected with steel piping to the building structure.
(f)
Sleeved Gas
CSST.
1.CSST shall be sleeved
when passing through a metal or concrete deck to protect the integrity of the
tubing. Licensees should be aware that the tubing may be required to be fire
stopped/rated per 780 CMR:
Massachusetts Amendments to the
International Building Code 2009. If applicable, this requirement will
be regulated/ enforced by the Building Inspector, not the Inspector as defined
in
248 CMR
3.01:
Definitions.
2.The sleeve shall be Schedule 40 black or
galvanized pipe and shall extend a minimum six inches from the top of the
finished floor and the underside of the deck.
(g) Only manifolds for CSST systems supplied
and listed by the CSST manufacturer may be concealed.
1.Assembled manifolds shall be installed in
an accessible location.
2.Assembled
manifold is a piping combination made up of close nipples and malleable
tees.
(h)
Fireplace Log Installations.
1.CSST shall terminate with a termination
fitting at the entrance to the masonry fire box.
2.The workmanship shall be performed and
completed in such a manner so that the termination will not be exposed to any
adverse effects.
(i)
Fixed Appliance Connection Using CSST. CSST may be
directly connected to a fixed appliance when the following conditions are met.
1.The tubing is securely attached to the
building structure or other means of solid support.
2.Tubing shall not run exposed for a distance
greater than or equal to 30 inches without being physically attached to the
building structure or other means of solid support.
3.CSST terminates with a proper fitting and
gas cock.
(j)
CSST Used Underground. .
1.When in contact with the earth or other
material that could corrode the piping, the CSST shall be installed within a
sleeve designed to withstand the superimposed loads.
2.Except for pre-engineered sleeves that are
Product-accepted by the Board, the sleeve shall allow free movement of the
CSST.
3.All sleeve ends shall be
sealed liquid tight.
4.An
acceptable tape marking system shall be in place no more than six inches from
the top of the grade indicating that a gas line is below.
5.The minimum depth for buried gas piping as
describe herein is 18 inches from the top of grade.
(k)
CSST Used as an Appliance
Connection. CSST shall not be used as a flexible appliance
connector downstream of the appliance shutoff device.
(l)
Sizing CSST
Systems. CSST systems shall be sized and installed with a maximum
14 inch water column (0.5 P.S.I.G.) gas pressure.
(m)
CSST Installation and
Modifications. Installation of CSST in the Commonwealth of
Massachusetts shall be in strict compliance with the manufacturer's
instructions and the Massachusetts State Plumbing and Gas Code
248 CMR
3.00:
General
Provisions Governing the Conduct of Plumbing and Gas Fitting Work Performed in
the Commonwealth through 7.00:
Large Gas Utilization
Equipment.
(n)
Testing Requirements for CSST Systems.
1.Before any piping is covered, when CSST
piping systems are installed in new construction or remodeling, the system
shall be tested as part of the Inspection as prescribed under Section 7.1 as
modified under 248 CMR
5.05.
2.Before piping is connected to any appliance
the licensed plumber or gas fitter shall do a second test of the
system.
3.A tag shall be:
a.affixed to the meter or service manifold
acknowledging this test; and
b.signed and dated by the licensed plumber or
gas fitter.
(o)
Liquid Leak
Detector. No corrosive liquids shall be used in the testing of the
CSST system. Some household soaps and detergents may be corrosive to gas and
plumbing products.
(p)
Exposed CSST Tubing. When CSST is installed outdoors
or is subject to corrosive chemicals, exposed stainless CSST tubing (where the
jacket has been removed) shall be recovered with tape as specified by the CSST
manufacturer. Said re-covering of CSST shall occur following the
testing.
(q)
CSST
Piping Installed on Roofs. CSST shall be installed for roof top
equipment only when it is supported by one of the following methods:
1.The CSST tubing with a UV stabilized jacket
is supported the full length of the CSST run.
a.The tubing shall be affixed to a wooden
plank or a steel channel that is securely attached by an appropriate method
every six feet to the roof structure.
b.The tubing shall be attached directly to
the support every six feet.
2.The CSST tubing is installed within a metal
or plastic conduit that is securely attached by an appropriate method every six
feet to the roof structure. Where the piping system requires a tee to be
installed within the line, the sleeve shall terminate no more than 12 inches
from the tee on both runs and the branch line.
3.For CSST tubing having sizes of 1.5 and two
inches and having a UV stabilized jacket, the following requirements shall be
satisfied:
a.the CSST shall be supported on
blocks which are spaced not more than 48 inches apart.
b.The blocks shall be constructed of
materials appropriate for outdoor conditions and shall be securely attached by
an appropriate method to the roof structure, and:
c.The method used to attach the CSST to the
block shall not damage the plastic coating.
d.The maximum length of tubing not supported
by any method listed shall not exceed 30 inches when connected to a gas fired
roof top unit or similar gas equipment.
(9) Replace subsection
5.6.8.4(1) with the following:
Pipe and Fittings in excess of four inches in diameter shall be
welded.
(10) Amend
subsection 5.6.8.4(2) by deleting "or cast iron"
(11) Replace subsection 5.6.8.4(5) with the
following:
Cast iron is only permitted for flanges, valves, strainers, and
filters.
(12) Add a new
subsection 5.6.8.5 as follows:
5.6.8.5 Other Fittings.
Notwithstanding the provisions of this section, metallic piping joints and
fittings which do not otherwise meet the requirements of this section may be
utilized if approved by the Board or otherwise have met the product acceptance
requirements of
248 CMR
3.04(1): Board
Required Product-acceptance.
(13) Add a new subsection 5.7.6 as follows:
5.7.6 Limitation. The provisions of
this section shall only apply to premises owned gas meters, which are comprised
of a secondary meter and meter assembly installed on the downstream portion of
the gas piping system of a serving gas supplier's meter.
(14) Replace section 5.12 with the following:
5.12 Manual Shutoff Valves.
Acceptable Shutoff Devices: Gas Cocks and Ball Valves installed
for use shall be listed. The Valves shall:
(a) Have clearly indicated open and closed
positions and rigidly secured stops to limit both extremes of rotation;
(b) shall be marked in a
conspicuous place with the manufacturer's name or registered trademark;
and
(c) Where in contact with
material or atmosphere exterting a corrosive action, a corrosion resistant
handle shall be utilized.